.   Concrete or masonry fire partition shown in figure 1a and 1b. Wood or steel stud fire partition shown in figure 2. See Wood Stud and/or

Steel Stud Framing for Fire Dampers In Drywall and/or Cavity Shaftwall Partitions Supplemental Installation In struc tions for further verti-

cal installation details. The square or round opening shall be a minimum 

1

/

4

(6)

larger than the damper sleeve/frame. Damper must be

installed with the leading edge of the closed blade within the par ti tion.  Damper may be installed with the blade a maximum of 15 degrees

from horizontal. For mounting angles that are up to and including 1-

1

/

2

" high, the opening shall be a maximum of 

3

/

4

(19)

larger than the

overall damper and sleeve assembly. When openings are larger than 

3

/

4

(19)

, but less than 6" 

(152)

the mounting angles must be a mini-

mum of 16 gauge 

(1.5)

and must be tall enough to overlap the opening by a minimum of 1" 

(25).

B.

The connecting duct shall not be continuous, and shall terminate at the sleeve/frame using one or more of commonly used break away

style con nec tions. Refer to Sleeve Termination Supplemental Installation Instructions for further details.  Damp er sleeve shall not extend

more than 16" 

(406)

beyond the rated partition on the actuator side. The opposite side extension shall be a maximum of 6" 

(152) 

unless

an access door is installed in the sleeve which then permits the extension to be a maximum of 16" 

(406).

C1. Dual Side Mounting Plate

The holding plate (on operator side) must be flush with the partition. Seat the holding plate (see figures 4, 4A and 5) into the mounting

grove on operator side of damper and place damper in the partition. Place the guide plate (see figure 4A) around opposite side of

damper sleeve and slide forward until it touches the partition. Secure both plates with joiner clips (see figure 3) using four #10 

(M5)

sheet metal screws, bolts or 

1

/

8

(3)

welds or rivets per joiner clip minimum. A minimum of three 1" x 1" x 2" x 20 GA. 

(25 x 25 x 51 x 1)

clip angles shall be arranged symmetrically around the damper and fastened to the damper sleeve flush with the guide plate. Fasteners

shall be a minimum of #10 

(M5)

screws, bolts, 

1

/

8

(3)

rivets or welds. The guide plate shall be attached to the partition with a minimum of

four fasteners, at the corners of square plates (for square openings) or equally spaced around the circumference of round plates (for

round openings).

For horizontal installation of the damper in a concrete floor, the holding plate must be installed on the top side of the floor opening.     

C2.

As an alternative to C1, for dampers ≤ 8" 

(203)

in diameter the guide and holding plates must be attached only to the sleeve, with clip

angles spaced a maximum of 8" 

(203)

O.C. For dampers > 8" 

(203)

and ≤ 12" 

(305)

in diameter, the clip angles must be spaced a maxi-

mum of 4" 

(102)

O.C. The clip angles must be staggered on either side of the partition.  

C3.

As a further option for round openings either or both plates may be replaced by  1-

1

/

2

x

1-

1

/

2

x

20 GA. (38 

x

38 

x

1) minimum angle rings.

The ring shall be fastened to the damper sleeve and not the partition at 8" 

(203)

on center maximum with a minimum of 3 fasteners using

#10 

(M5) 

sheet metal screws, bolts, masonry anchors, 

1

/

8

(3)

diameter rivets of welds.

C4. Single Side Mounting Plate

Single side mounting plates can be used for vertical masonry or steel stud partitions. The mounting plate must be 20 GA. 

(1)

minimum,

the clamping brackets must be 2" x 1" x 

1

/

2

" x 14 GA. 

(51 x 25 x 13 x 2)

minimum, and the clamping bolt shall be a 

1

/

4

" - 20 x 3" 

(M6 x 76)

bolt minimum. Each clamping bracket must be secured to the mounting plate with a minimum of two 

3

/

16

(5) 

diameter rivets or welds.

The mounting plate hinges on a  

3

/

16

(5) 

minimum diameter rivet. The mounting plate can be installed on either side of the partition

The

mounting plate must be positioned with the retaining bolt and nut facing 

AWAY

from the wall. 

The mounting plate may be placed

into the mounting groove or placed around the damper sleeve/frame. See Sheet 2 for mounting plate hole diameters.  

Tighten

clamping bolt to ensure the mounting plate is secured to the damper. The mounting plate must be fastened to the partition at all four

corners and for dampers D≥ 12" 

(25) 

the mounting plate must be fastened 1" 

(25) 

from the center of each side using a minimum of #10

(M5)

screws, concrete anchors, 

1

/

8

(3) 

rivets or welds. Fasteners must be a minimum of

1

/

4

(6) 

from the edge of the plate and 

must

engage the steel stud by 

1

/

2

(13) 

minimum

.  

D.

Fire/leakage rated damper and qualified operators are tested together by Underwriters Laboratories and are factory installed to qualify for

standard  damper/operator  warranties.  Damper  operator/actuator  must  be  tested  prior  to  system  start-up  to  ensure  proper  operation.

Before applying power to the actuator, the power must be verified.    

Figure 1b

Vertical Concrete Partition

Figure 1a

Horizontal Concrete Partition

Figure 2

Stud Partition

A

DUCT/SLEEVE

KNEE-LOCK

ASSEMBLY

aaaaaaa

aa

aaaaaaa

aa

C

2

C

2

 DAMPER DIA.

AIR FLOW

B

FASTENER

MOUNTING GROVE

A

DUCT/SLEEVE

C

2

C

2

 DAMPER DIA.

AIR FLO

W

B

FASTENER

MOUNTING GROVE

KNEE-LOCK
ASSEMBLY

KNEE-LOCK
ASSEMBLY

Model - FSD-125R

For Use in Dynamic or Static Systems.

1-1/2 Hour Rated.

Vertical or horizontal mounting.

Galvanized and Stainless Steel construction.

B

aaaaaaaaaaaaaa

C

1

C

1

A

L I

S T I N G

S

E R V I C E

ST

AT

E O

F CALIFOR

NIA

ST

AT

E FIRE MARSH

AL

L

SEE DETAILS ON UL 

CLASSIFICATION

MARKING ON 

ENCLOSED PROD UCT

POTTORFF

®

5101 Blue Mound Road, Fort Worth, Texas 76106

www.pottorff.com

Information is subject to change without notice or obligation.

NOTE:

Dimensions in parentheses ( ) are millimeters.

Fire 

Smoke 

Dampers 

IIFSD125R

(1/2) 

November 

2012

1

1

/

2

hour — combination fire smoke dampers

installation instructions

The following installation details apply to model

FSD-125R

®