background image

PAD300-SB

Addressable Sounder Base 

8830221 - REV A

  •   

10/22

 PAGE 1 OF 2

Potter Electric Signal Company, LLC   •   St. Louis, MO   •   Phone: 800-325-3936    •   www.pottersignal.com

Description

The Addressable Sounder Base 6” (PAD300-SB) is a sounder base that 

may be utilized in a variety of applications. The base has a locking 

feature for the detector that may be used or removed in the field. Once 

the detector is removed, the sounder is accessible in the bottom of the 

unit.
The base has an independent sounder module that may be programmed 

as a single station, zone or all call sounder. The PAD300-SB passes 

through the sound pattern sent to the sounder, therefore it may 

reproduce in any pattern the power supply provides. 
The panel will support any combination of detectors or modules on 

the SLC. The PAD300-SB does not consume an address on the loop 

and is fully programmable to operate with any input. Once activated 

the sounder will also follow the input from the power source and de-

activate accordingly.

Technical Specifications

SLC Voltage

24 VDC

SLC Standby Current

300 μA

PWR Voltage

16- 33 VDC

PWR Active Current

42mA

Alarm LED Current

1.4 mA

Sound Pressure

75dB @ 10ft per UL464

85dB @ 10ft per UL268

Installation Temperature Range 

32 to 150°F (0°C to 66°C)

Operating Humidity Range

< 93% (Non-condensing)

Dimension

6.4 in (163 mm)

Weight

199 g (7.40 oz)

Height

1.57 in (40 mm)

Features

•  Integrated Sounder in base
•  UL464 and UL268 Listed
•  Sounder independent of detector, allows for a single station, 

grouped or all-call

•  May be mapped to any device connected to the control panel
•  Terminals accept 22 to 12 AWG wire sizes
•  Supports Class A, Class X and Class B wiring
•  Does not require SLC Loop address
•  UUKL Listed for Smoke Control

Reviews: