manualshive.com logo in svg
background image

Specifications subject to change

TECHNIC

TECHNIC

TECHNIC

TECHNIC

TECHNICAL BULLETIN

AL BULLETIN

AL BULLETIN

AL BULLETIN

AL BULLETIN

Headquarters:
5007 S. Howell Ave.
Milwaukee, WI 53207  USA
Tel: +1 (414) 769-5980
Fax: +1 (414) 769-5989
or +1 (414) 769-5996 (Int’l)

Northern Computers, Inc.

Worldwide Locations:

Crawley, Sussex, United Kingdom
Tel: (44) 1293-592700 • Fax: (44) 1293-523061

Sao Paulo, Brazil
Tel: (55)  (11) 826-4944 • Fax: (55) (11) 826-0649

Australia
Tel:  (612) 9699-3700  Fax:  (612) 9699-3101

Hong Kong
Tel: 852-2528-1897 • Fax: 852-2528 4599

Montreal, Quebec, Canada
Tel: 514-933-3363 • Fax: 514-933-3447

Moscow, Russia
Tel: (7) 095-723 2626 • Fax: (7) 095-956 5428

France
Tel:  33-1-30-13-03-93  Fax:  33-1-3- 13-03-90

Mexico
Tel:  (52) (5) 280-7890  Fax:  (52) (5) 280-8555

Ecuador
Tel:  (593) (2) 265-588/91  Fax:  (593) (2) 461-379

July 1998; Rev. 2.1 (page 1 of 2)

KP-13 Keypad Wiring Instructions

The KP-13 Keypad is a 5-wire Wiegand output keypad suitable for outdoor use. It is wired to a control
panel in the same manner as a card reader (see figure 1). The KP-13-ILL is the same keypad with illumina-
tion.

The KP-13 uses the 32-bit Wiegand format: _F=pn_2_32_S_0_D_0_B1_B2_B3_B4 (required for N-1000
with 4.17 or older firmware).
This format can be entered in a text file or Terminal Mode (not required for N-500). Refer to panel installa-
tion and programming manuals for more information.  As with all keypads, press the “#” key after code
entry. To clear an entry, press the “

*

” key. To toggle illumination off and on (KP-13-ILL only), press “

*

” and

“3” at the same time.

LED Operation.

 When the reader is first powered up, the green LED will remain on until after the first

valid card read. When the “M” option is enabled in the panel programming the LEDs operate as follows:

Normally, the red LED is on.

Upon valid code entry, the green LED comes on and the red LED goes off.

After the LED pulse time elapses, the green LED goes off and the red LED comes on.

Upon invalid code entry, no LED change occurs.

Grounding.

 The tan wire is a chassis ground. If the keypad is mounted directly on grounded metal, tie the

tan wire to the grounded metal. Tie the keypad cable shield to the control panel ground point and float
shield at keypad. If the keypad is mounted on ungrounded metal or nonmetallic material, tie the tan wire to
the keypad cable shield and connect the shield to the control panel ground point.

Wiring specifications

NCI Part #

Description

Maximum Distance

NC1861/BL

6-wire 18 AWG shielded

500 feet

TD2006

Figure 1. Wiring for the KP-13.
Power for the keypad can be
supplied from the control panel.

KP-13

Black

(Common)

Red

(+5VDC)

Green

(Data 0)

White

(Data 1)

Brown

Tan

(Earth Ground)

The Blue wire remains disconnected (not used)

(LED)