background image

 

 
 
 

DCU20

 User Manual rev. 21 

Page 1/29 

 

 
 
 
 
 
 
 

DCU20 

 

12/24V 20A High Performance DC-UPS 

 

User Manual 

 
 
 

 

 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

 
 
 

Summary of Contents for DCU20

Page 1: ...DCU20 User Manual rev 21 Page 1 29 DCU20 12 24V 20A High Performance DC UPS User Manual...

Page 2: ...ication in which the failure of the NEXTYS product could create a situation where personal injury or death may occur Should Buyer purchase or use NEXTYS products for any such unintended or unauthorize...

Page 3: ...ge 18 5 2 2 Battery chemistry 18 5 2 3 Battery nominal voltage 18 5 2 4 Battery capacity 18 5 2 5 Battery charge voltage 18 5 2 6 Battery charge current 18 5 2 7 Battery deep discharge voltage 18 5 2...

Page 4: ...Manual rev 21 Page 4 29 5 3 3 Name 22 5 3 4 Power ON cycles counter 22 5 3 5 Operating time 23 5 3 6 Battery installation date 23 5 3 7 Battery operating time 23 5 4 Logs 23 5 5 Wizard 23 6 Events and...

Page 5: ...ays are present for remote monitoring See 3 1 for more details 5 Inhibit input A signal between 5VDC and 30VDC applied to this input inhibits the backup function this input is programmable to be activ...

Page 6: ...time Remote input to inhibit the UPS function Connection of a battery thermal sensor optional Integrated data logger with time stamp all events errors are logged in the internal memory and downloadabl...

Page 7: ...onitored by the microprocessor In case of a power outage the battery is connected to the load instantaneously through an active switch reducing the power loss to a minimum The product offers additiona...

Page 8: ...the recharge time avoiding discharging the battery when not needed During backup the internal Coulomb counter is used to give an estimation of the residual charge of the battery this information is g...

Page 9: ...FF signal PC status Output voltage Output current Input voltage T1 T2 T3 T4 T3 E3 E1 E2 E4 Ioff Figure 5 Shutdown and restart chart Parameter Name Description E1 Backup Power failure on the line happe...

Page 10: ...below the Ioff current threshold to trigger the automatic PC restart PC supply ON OFF ON cycle Ioff PC OFF detection current threshold User settable 5 2 27 Current threshold used to detect PC OFF sta...

Page 11: ...inals on the DCU20 The measured resistance will be in this case Rmeasured Ri Rcables When high Ah batteries and or small and long cables are used Rcables can be Ri Anyhow a connection problem as for e...

Page 12: ...rmined amount of time The value is automatically calculated by the device For Nickel batteries only the following conditions are also checked Temperature Cutoff TCO The battery temperature if higher t...

Page 13: ...procedure is used to turn ON the UPS to operate during a power interruption or to determine if the UPS will not turn ON due to a bad input power This practice is also a method to see if the battery co...

Page 14: ...the wiring polarity Please check the load and the power supply are rating compliant 4 3 Connecting the battery The DCU20 must be connected to a battery with nominal voltage between 12VDC and 28VDC wit...

Page 15: ...input fails with no battery backup The polarity of this input can be changed as explained in 5 2 15 4 6 Dry contacts 2 relays dry contacts are provided on the DCU20 Connect the 2 relays dry contact u...

Page 16: ...ce settings are configurable from this menu Use the UP DOWN KEY to navigate through the parameters Press the OK KEY to enter exit the editing mode In editing mode use the UP DOWN KEY to change the hig...

Page 17: ...nges from green to red and a message with the cause appears Battery The battery voltage current temperature resistance and charge are shown in this section In case of problems with the battery the bac...

Page 18: ...Battery capacity Used to set the nominal battery capacity of the battery The internal Coulomb counter uses this value to indicate the state of charge of the battery Default 2Ah Range 1 2Ah 150Ah Resol...

Page 19: ...0 Resolution 1 5 2 11 Battery maximum temperature An optional external temperature sensor P N WNTC 2MT is required Used to set the maximum temperature at which the battery can operate safely If the me...

Page 20: ...backlight Used to set the LCD screen backlight Default 2 Range 1 10 Resolution 1 5 2 18 Screen timeout To save the LCD backlight the system dims the LCD after the defined timeout value Default 5min Ra...

Page 21: ...backup and PC shutdown command sent by POWERMASTER see 3 3 for details Default 0s Range 0s 60min Resolution 1s 5 2 25 PC shutdown time Delay between start of PC shutdown and output power OFF see 3 3...

Page 22: ...arity and event associated with the relay See 3 1 3 for more details 5 3 Info While in the info menu use the UP DOWN KEY to navigate through the menu items 5 3 1 Firmware version Shows the current fir...

Page 23: ...Use the UP DOWN KEYS to navigate between logs For each event the following information is given Timestamp The time and date at which the event happened Event name The name identifying the event see 6...

Page 24: ...click next to confirm See 5 2 11 for more details 11 Insert the battery expected lifetime and click next to confirm See 5 2 13 for more details 12 Insert the battery installation date and click next t...

Page 25: ...START IUVS Threshold voltage triggering the alarm Description The measured input voltage is lower than the alarm threshold The threshold is calculated taking the lowest value between the input nominal...

Page 26: ...alarm Description The measured output current returns below the alarm threshold Name Short name Value ALARM_BATTERY_UNDERVOLT_START BUVS Threshold voltage triggering the alarm Description The measure...

Page 27: ...reached during the alarm Description The measured battery temperature returns below the alarm threshold Name Short name Value ALARM_BATTERY_UNDERTEMP_START BUTS Threshold temperature triggering the a...

Page 28: ...me Short name Value ALARM_SHORT_CIRCUIT Short circ None Description A short circuit has been detected on the output Name Short name Value ALARM_BATTERY_ERROR Batt error None Description The DCU20 was...

Page 29: ...DCU20 User Manual rev 21 Page 29 29 Physical dimensions...