GETTING STARTED GUIDE

NI cRIO-9030

Embedded CompactRIO Controller with Real-Time Processor and
Reconfigurable FPGA

This document describes how to begin using the National Instruments cRIO-9030.

Safety Guidelines

Caution

 

Do not operate the cRIO-9030 in a manner not specified in this document.

Product misuse can result in a hazard. You can compromise the safety protection
built into the product if the product is damaged in any way. If the product is
damaged, return it to NI for repair.

Safety Guidelines for Hazardous Locations

The cRIO-9030 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous
locations; Class I, Zone 2, AEx nA IIC T4 and Ex nA IIC T4 hazardous locations; and
nonhazardous locations only. Follow these guidelines if you are installing the cRIO-9030 in a
potentially explosive environment. Not following these guidelines may result in serious injury
or death.

Summary of Contents for cRIO-9030

Page 1: ...romise the safety protection built into the product if the product is damaged in any way If the product is damaged return it to NI for repair Safety Guidelines for Hazardous Locations The cRIO 9030 is suitable for use in Class I Division 2 Groups A B C D T4 hazardous locations Class I Zone 2 AEx nA IIC T4 and Ex nA IIC T4 hazardous locations and nonhazardous locations only Follow these guidelines ...

Page 2: ...es must be used in a conduit or cable gland to wire to a nonhazardous location Do not disconnect a cable unless the cRIO 9030 is powered off or the area is known to be nonhazardous Table 1 Hazardous Location Retention Accessories Port Required Accessory Part Number USB Host Port NI Industrial USB Extender Cable 152166 xx USB Device Port NI Locking USB Cable 157788 01 Mini DisplayPort Mini DisplayP...

Page 3: ...hermore any changes or modifications to the product not expressly approved by National Instruments could void your authority to operate it under your local regulatory rules Caution To ensure the specified EMC performance operate this product only with shielded cables and accessories The DC power input cables may be unshielded Caution To ensure the specified EMC performance you must use an isolated...

Page 4: ...cifications Operating temperature IEC 60068 2 1 IEC 60068 2 2 20 C to 55 C Operating humidity IEC 60068 2 56 10 RH to 90 RH noncondensing Pollution degree 2 Maximum altitude 5 000 m Indoor use only Note Refer to the device specifications on ni com manuals for complete specifications Unpacking the Kit Caution To prevent electrostatic discharge ESD from damaging the device ground yourself using a gr...

Page 5: ...ware and device drivers on the host computer in this order 1 LabVIEW 2014 or later 2 LabVIEW Real Time Module 2014 or later 3 LabVIEW FPGA Module 2014 or later1 4 NI RIO Device Drivers August 2014 or later For minimum software support information visit ni com info and enter the Info Code swsupport Installing C Series Modules Complete the following steps to install a C Series module 1 LabVIEW FPGA ...

Page 6: ... module with a slot and seat it in the slot until the latches lock in place Removing C Series Modules Verify that power is not connected to the I O connector s on the C Series module before you remove a module from the cRIO 9030 If the system is in a nonhazardous location the cRIO 9030 can be powered on when you remove modules Connecting the cRIO 9030 The cRIO 9030 has the following connectors LED...

Page 7: ...erminal to the grounding electrode system of the facility What to Use Ring lug Wire 1 3 mm2 16 AWG or larger Screwdriver Phillips 2 What to Do Complete the following steps to ground the cRIO 9030 1 Attach the ring lug to the wire 2 Remove the grounding screw from the grounding terminal on the cRIO 9030 3 Attach the ring lug to the grounding terminal 4 Tighten the grounding screw to 0 5 N m 4 4 lb ...

Page 8: ...9030 has a primary power input V1 and a secondary power input V2 The POWER LED on the cRIO 9030 indicates which power input is in use as shown in the following table Table 2 POWER LED Indicators LED Color LED Pattern Indication Green Solid The cRIO 9030 is powered from the V1 input Yellow Solid The cRIO 9030 is powered from the V2 input Off The cRIO 9030 is powered off Caution Do not connect V2 to...

Page 9: ...itive leads of the power supply as shown in the following figure Figure 3 Installing a Ferrite on the Power Leads 2 1 1 Pass the leads through the ferrite twice leaving 50 mm to 75 mm 2 in to 3 in between the ferrite and the end of the leads 2 Close the ferrite around the leads 3 Remove the power connector from the cRIO 9030 Caution Do not tighten or loosen the terminal screws on the power connect...

Page 10: ... cRIO 9030 When you power on the cRIO 9030 for the first time the device boots into safe mode The POWER LED illuminates the STATUS LED illuminates briefly and then the STATUS LED blinks twice every few seconds Related Information STATUS LED Indicators on page 14 Connecting the cRIO 9030 to the Host Computer Complete the following steps to connect the cRIO 9030 to the host computer using the USB de...

Page 11: ... system password Note The default username for the cRIO 9030 is admin There is no default password for the cRIO 9030 so you must leave the password field blank when logging in until you set a system password 1 Right click your system and select Web Configuration The NI Web Based Configuration and Monitoring utility opens in your default browser and is where you set the password If you have not ins...

Page 12: ...Module Tip You can use this wizard at anytime to install additional software 7 Click Next 8 Verify that the summary of software to install is correct 9 Click Next to start the installation 10 Click Finish when the installation is complete Troubleshooting the cRIO 9030 The cRIO 9030 is Not Communicating with the Network Ensure that the USB connections between the cRIO 9030 and the host computer and...

Page 13: ...e System IP Configuration 1 Put the cRIO 9030 in safe mode and enable the RS 232 serial port by holding the RESET button down for 5 seconds The STATUS LED starts blinking three times every few seconds 2 Use the RS 232 serial port terminal to read the IP address or connect a monitor to the mini DisplayPort to view the IP address Note Refer to the user manual on ni com manuals for more information a...

Page 14: ...ld RESET button for 5 s Press and hold RESET button for 5 s Run Mode Safe Mode Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold RESET button for 5 s Console Out enabled Network settings reset RT Startup App disabled FPGA Startup App disabled Console Out enabled RT Startup App disabled FPGA Startup App disabled Safe Mode STAT...

Page 15: ...or longer than five seconds or by enabling safe mode in MAX Refer to the Measurement Automation Explorer MAX Help for information about safe mode Blinks four times and pauses The cRIO 9030 is in safe mode The software has crashed twice without rebooting or cycling power between crashes Continuously blinks The cRIO 9030 has not booted into NI Linux Real Time The cRIO 9030 either booted into an unsu...

Page 16: ...leshooting and application development self help resources to email and phone assistance from NI Application Engineers Visit ni com services for NI Factory Installation Services repairs extended warranty and other services Visit ni com register to register your National Instruments product Product registration facilitates technical support and ensures that you receive important information updates...

Page 17: ...n the United States create your service request at ni com support or dial 1 866 ASK MYNI 275 6964 For telephone support outside the United States visit the Worldwide Offices section of ni com niglobal to access the branch office websites which provide up to date contact information support phone numbers email addresses and current events NI cRIO 9030 Getting Started Guide National Instruments 17 ...

Page 18: ...nd third party legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the National Instruments global trade compliance policy and how to obtain relevant HTS codes ECCNs and other import export data NI MAKES NO EXPRESS OR IMPLIED WARRANTIES AS TO THE ACCURACY OF THE INFORMATION CONTAINED HEREIN AND SHALL NOT BE LIABLE FO...