Control system 

Gate control mts2000/02 
R2.8 

Summary of Contents for mts2000/02

Page 1: ...Control system Gate control mts2000 02 R2 8 ...

Page 2: ...equipment 4 1 4 2 Scope 4 2 4 2 1 Overview of operating modes 4 2 4 2 2 Interfaces for input elements 4 2 4 2 3 Interfaces for output elements 4 2 4 3 Structure 4 3 4 4 Operating modes 4 5 4 4 1 Impulse control as sequence control 4 5 4 4 2 Impulse control defined up down 4 5 4 4 3 Single dual lane feedback control with light control and automatic closing 4 6 4 4 4 Special operating modes 4 6 4 4 ...

Page 3: ...bly and installation 5 1 Safety information regarding assembly 5 1 5 2 Fitting gate control mts2000 02 5 2 5 3 Electrical connection 5 4 6 Start up and operation 6 1 Programming gate control mts2000 02 6 1 6 1 1 Controls of gate control mts2000 02 6 1 6 1 1 1 Hardware settings 6 1 6 1 1 2 Function of keys 6 3 6 1 2 Menu structure of operating software 6 3 6 1 2 1 Language setting 6 3 6 1 3 Program...

Page 4: ...e systems Gate control operating manual mts2000 02 Table of contents 7 1 1 1 Testing 7 1 7 1 2 Fault rectification 7 1 7 1 3 Control PCB measurement points 7 2 7 2 Regular testing 7 5 7 3 Address of manufacturer 7 6 ...

Page 5: ......

Page 6: ...0 Safety of electrical devices for domestic consumption etc BGVA2 Electrical systems and operating equipment BGR 232 Guidelines for power assisted windows doors and gates Note The gate control system has been produced and inspected TÜV Bau und Betriebstechnik GmbH corporate group for southern Germany in Filderstadt in accordance with the standards and guidelines listed and was in perfect condition...

Page 7: ... symbol identifies important instructions on correct use of the device Failure to follow these instructions can result in malfunctions on the device Note This symbol identifies tips for application and particularly useful information which will help you to make the most of all the device s functions Liability exclusion This symbol indicates that operator error or failure on the part of the operato...

Page 8: ...possible risk and be able to take appropriate safety measures 2 3 Correct handling In order to keep the device in perfect condition from a technical safety standpoint and to be able to assure safe operation the user undertakes to comply with the points listed in this operating manual Operation of the control unit is only permitted while its covers and guards are all in position Ensure that all gas...

Page 9: ...iability for damage resulting from any failure by the purchaser to comply with the purchaser s obligations The purchaser undertakes to only allow trained groups of people to work with the device The purchaser is also responsible for ensuring that the operating instructions for gate control mts2000 02 are available to the group of users when working with the device 3 3 User obligation All users mus...

Page 10: ...anufactured and tested in accordance with the corresponding guidelines for EMC see Section 1 2 CE marking However it is possible that mains voltage peaks due to non EMC compatible loads for example may cause the processor to switch off This procedure is intentional and in no way affects the controller s safety functions The processor restarts automatically thereafter and the controller is set to R...

Page 11: ...th the exception of reversing the closing edge The possibility of uncontrolled gate movement triggered by the microprocessor is therefore ruled out and is prohibited by the hardware 4 1 2 Monitored safety equipment The evaluation of all safety equipment corresponds to the standard set by the me chanical engineering industry 1 Before every gate movement the gate s function is checked automatically ...

Page 12: ...mode with safety functions Emergency actuation without safety functions For more information refer to Chap 4 4 Operating modes 4 2 2 Interfaces for input elements The following external input elements can be connected up e g as impulse sen sors one or two command radio with without antenna optional plug in module pushbuttons pull buttons key operated keys continuously open switch gatekeeper s swit...

Page 13: ...housing of safety class IP54 with the dimensions 250 x 160 x 127 mm The function group consists of two PCBs connection PCB control PCB removable display PCB with programming keys Firstly release plug from connection X1 then remove PCB and bolts The operating and fault statuses appear on the LCD display on the control PCB Fig 4 1 Control PCB with controls ...

Page 14: ...ner gate systems 4 4 Gate control operating manual mts2000 02 Description of product Supply lines are guided into the housing via screw connections Apertures which are not used must be sealed with blind plugs ...

Page 15: ...on from either radio triggers the following function motion status of gate changes in the following se quence OPEN STOP CLOSED STOP If the gate is in its upper or lower limit position the STOP status is jumped 4 4 2 Impulse control defined up down Function 1 Opening and closing the gate system after activation taking the safety equip ment and if necessary the pre warning time set into consideratio...

Page 16: ...ion of travel is approved using lights depending on gate control activation triggering from inside or outside In the event of alternating activation triggering from inside or outside within the hold open time the direction of travel is changed over using the lights after a pre warning time which may be set if necessary The gate shuts automatically once the hold open time and if necessary the pre w...

Page 17: ...o Fig 4 1 Control PCB with controls These switches have a direct impact on the drive The safety equipment fitted is bridged Operations without the control PCB attached are possible using the external emer gency control switches For reasons associated with safety the operator must be able to fully view the gate when pressing the emergency control switch Care must be taken to ensure that emergency c...

Page 18: ...to 8 opening closing cycles per day of the week The switching times of the week days can be programmed individually or as a group If the gate is opened the traffic is control by the light functions When the gate is closed the single dual lane feedback control system is operated by impulse inside impulse outside internal key Activation from either radio For more information please note the operatin...

Page 19: ...ed in Chapter Program gate 6 1 3 The following can be connected up optical system OS12 optical system OSE resistance strip R 8 2 K Note The function of the closing edge protection is checked before every gate move ment Configuration is undertaken via jumper J1 on the control system PCB 4 6 2 Stop in open closed position protection against anything being drawn in Function Stop after activation duri...

Page 20: ... Reset hold open time via passage protection also refer to option for RESET O TIME VIA PP in Chapter Program gate 6 1 4 the time expires despite the passage protection being triggered Note This applies to the single lane and dual lane feedback control operating modes 4 6 3 3 Extending the hold open time The hold open time is restarted by triggering the passage protection before the hold open time ...

Page 21: ...ed and before the hold open time lapses The closing process is then initiated The process is restarted when the gate is next driven through Note This applies to the single dual lane and dual lane feedback control operating modes 4 6 4 Run time monitoring In addition to the hardware safety equipment the control system is also fitted with software run time monitoring If the gate does not reach a lim...

Page 22: ...e key or outside impulse 24 V 100 mA key potential free contact at terminals 7 8 Key for impulse sequence or switch for continuously open external clock 24 V 100 mA key potential free contact at terminals 9 10 The line length of the impulse sensor should not exceed 15 m Longer lines must if necessary be disconnected e g potential free activation of connection via a relay contact 4 7 1 4 Interfaces...

Page 23: ...ply for receiver terminals 16 17 Switching output terminals 22 23 4 7 1 5 Connection for potential free contact e g bulb 230VAC 2 A at terminals 25 26 4 7 1 6 Connection for lights Lights bulb 230VAC 2 A at terminals 29 34 Supply to lights 230VAC 2 A at terminals 27 28 4 7 1 7 Connection for drive Drive close relay 230VAC 4A at terminals 41 42 Drive open relay 230VAC 4A at terminals 40 42 4 7 1 8 ...

Page 24: ......

Page 25: ...l system the always ensure compliance with applicable Health Safety at Work regulations for the specific application must be noted Amongst others these rulings include VDE 0100 Guidelines for setting up high power systems of up to 1000 V VDE 0105 Operating high current electrical systems EN 60204 Electrical systems with electronic operating equipment VDE 0160 Equipping high power systems and elect...

Page 26: ...n gate control cover and move cover to one side Release retaining bolts of control board Carefully and evenly withdraw board out of connection board Move board to one side Prevent static discharge on board Only touch the edges of the board Note ESD Directive Drill holes depending on the quantity and size of lines in the housing Insert PG screw connections in housing Fit gate control housing to pre...

Page 27: ...5 Gate control operating manual mts2000 02 5 3 meißner gate systems Assembly and installation Fig 5 1 Housing dimensions of gate control ...

Page 28: ...ation 5 3 Electrical connection The following diagram shows an overview of the connection board Follow the references on the detailed diagrams Connect the external inputs and outputs to gate control mts2000 02 as shown in these diagrams Fig 5 2 Connection boards of gate control mts2000 02 ...

Page 29: ...ch connections to connection board of gate control mts2000 02 24 V connections 1 Gate control controls 2 Closing edge protection 3 Protection against anything being snagged or pulled in 230 V connections 1 230 VAC connection 2 Lights potential free contact 3 Drive mains supply Fig 5 3 Impulse sensor ...

Page 30: ...5 meißner gate systems 5 6 Gate control operating manual mts2000 02 Assembly and installation Fig 5 4 Closing edge control ...

Page 31: ...5 Gate control operating manual mts2000 02 5 7 meißner gate systems Assembly and installation Fig 5 5 Passage protection and protection against anything being snagged or pulled in earthing 0 V ...

Page 32: ...5 meißner gate systems 5 8 Gate control operating manual mts2000 02 Assembly and installation Fig 5 6 Passage protection and protection against anything being snagged or pulled in earthing 0 V ...

Page 33: ...5 Gate control operating manual mts2000 02 5 9 meißner gate systems Assembly and installation Fig 5 7 Light connection and potential free contact ...

Page 34: ...5 meißner gate systems 5 10 Gate control operating manual mts2000 02 Assembly and installation Fig 5 8 Emergency control and mains connection ...

Page 35: ...5 Gate control operating manual mts2000 02 5 11 meißner gate systems Assembly and installation Fig 5 9 Drive ...

Page 36: ......

Page 37: ...trol mts2000 02 is programmed using 4 keys refer to Fig 4 1 on the control unit display board The individual menu items of the control unit software are shown on the display The keys are suppressed and have to be held down for around 1 second before they will respond 6 1 1 1 Hardware settings for more information refer to Fig 4 1 J1 Set according to the closing edge protection fitted J2 Apply jump...

Page 38: ...6 meißner gate systems 6 2 Gate control operating manual mts2000 02 Start up and operation Fig 6 1 Removable display module with programming keys ...

Page 39: ...viewing and setting Use the keys and to increase or decrease by a specified step width the parameter selected The value selected is entered by confirming the question Save 6 1 2 Menu structure of operating software Fig 6 2 Menu levels of operating software for gate control mts2000 02 6 1 2 1 Language setting The language is set on the display For more information refer to Chap 6 1 4 Service Langua...

Page 40: ...I N P U T S T A T U S Impulse inside Impulse outside Continuously open externally or clock Stop in open closed position 1 and 2 Stop Closing edge Stop in closed position Impulse open Impulse closed Impulse sequence open stop closed stop Transmitter stop in open and closed position 1 functioning Transmitter stop in open and closed position 2 functioning H A Z A R D F L A S H I N G 0 2 0 5 s P P P P...

Page 41: ... M O U T S I D E R E O P E N O P T I O N o n L I G H T S D U R I N G C O N T O P E N O P T 0 R E D L I G H T G A T E C L O S E D O P T I O o f f P P P Light times Clearing phase pre warn time Green phase hold open time P P P The potential free contact closes during every impulse from inside or outside or inside outside Set impulse period using light period If setting outside impulse also during co...

Page 42: ...s when closing opening Impulse period of potential free contact Only active if light activation is programmed in service Save settings hold down for 5 seconds Reject changes press M Press for 5 seconds Save is acknowledged H A Z A R D F L A S H I N G O P T I O N o n R U N T I M E 2 1 2 0 1 0 s C O N T I N U O U S L I G H T 1 1 8 0 1 s S A V E P H O L D D O W N S A V E P S A V E D P P P P P ...

Page 43: ...and hold down key to do this press key P Shown on LCD display Comments S E R V I C E Only accessible to service fitters Hold down then press P Use to select language Counter for gate cycles according to EN 12433 2 Chap 9 1 1 total cycle Activate manufacturer presettings Change hold down and then press P S E R V I C E P R E S S M L A N G U A G E G B G A T E C Y C L E S 1 P R E S E T T I N G R E V E...

Page 44: ... LIGHT ACTIVATION or FAULT MESSAGE can be selected Save settings hold down for 5 seconds Reject changes press M Press for 5 seconds Save is acknowledged 6 1 5 Operation Gate control mts2000 02 requires no operation It is operated as part of the entire gate system using the controls connected to the system such as remote control keys continuously open switch O P E R A T I N G M O D E S I N G L E L ...

Page 45: ...ons for weekly time indexing clock mts2000 02 The clock item 739 can be retrofitted 6 2 1 Assembly 1 De energise the system before assembly 2 Attach clock to the intended connection point refer to Fig 4 1 3 Re energise system 6 2 2 Programming In accordance with the programming instructions enclosed with the clock ...

Page 46: ...intended connection point refer to Fig 4 1 The setting and display elements for the radio plate must face the inside of the housing 3 The projectile antenna supplied should be in a vertical position An external antenna item 477 can be fitted if range problems are experienced 4 Re energise system 6 3 2 Setting instructions 1 The setting on the 10 pin code switch must match that of the handheld tran...

Page 47: ...1 0 0 0 No function Channel 2 On 0 0 1 1 Off 1 1 0 0 No function Channel 2 On 1 0 1 1 Off 0 1 0 0 Channel 1 Channel 2 On 1 0 0 1 Off 0 1 1 0 Channel 1 No function On 1 0 0 0 Off 0 1 1 1 Channel 1 No function On 1 1 0 1 Off 0 0 1 0 No function Channel 1 On 1 1 0 0 Off 0 0 1 1 No function Channel 1 On 1 1 1 0 Off 0 0 0 1 Channel 2 Channel 1 6 3 4 Displays Press left key LED 1 lights up Press right k...

Page 48: ......

Page 49: ...tested if ERROR TESTING appears on the control system display The cause may e g be light barriers not aligned or not adjusted light barrier receiver cannot be deactivated due to reflections light barrier transmitter not connected to test output light barrier receiver is affected by an external light e g sun jumper J2 or J3 set closing edge protection activated or defective closing edge type incorr...

Page 50: ...gency control drive OPEN 49 50 Resistance infinite Ohm Emergency control switch on PCB OPEN or external OPEN emergency control switch not pressed No voltage at terminals 38 and 39 Resistance 0 Ohm Outside green light active Outside green light 51 55 Resistance infinite Ohm Outside green light not active No voltage at terminals 27 and 28 Resistance 0 Ohm Inside green light active Outside red light ...

Page 51: ...ive Control voltage 64 63 Voltage 0 VDC Control system inactive or short circuit or ground earth connection Voltage 10 24 VDC Transmitter for stop in closed position active and receiver active contact closed Stop in closed position 65 63 Voltage 0 VDC Transmitter for stop in closed position inactive or receiver inactive contact open Voltage 10 12 VDC Control system active Auxiliary voltage for clo...

Page 52: ...se activated contact closed Impulse outside and or closed impulse 69 63 Voltage 0 VDC Impulse outside or closed impulse not activated contact closed Voltage 10 24 VDC Impulse inside or open impulse activated contact closed Impulse inside and or open impulse 70 63 Voltage 0 VDC Impulse inside or open impulse not activated contact closed Voltage 10 24 VDC Impulse for halt and stop not activated cont...

Page 53: ...it until the hold open and pre warning time has expired During impulse control operating mode issue close command 4 Status of LEDs during the test phase also refer to Fig 4 1 LED 1 LED 2 LED 3 LED 4 Before test 0 0 1 1 Test stage 1 1 0 1 1 Test stage 2 0 1 1 1 Test stage 3 0 0 0 1 Test stage 4 0 0 1 0 After test 0 0 1 1 5 Close housing again once test is complete If result of testing is negative s...

Page 54: ... operating manual mts2000 02 Maintenance service 7 3 Address of manufacturer Meißner GmbH Toranlagen Robert Koch Straße 5 77694 Kehl Auenheim Germany Tel 49 7851 9161 0 Fax 49 7851 9161 30 http www meissner gmbh de E mail info meissner gmbh de ...