background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7787  Rev.7  P. 1 / 9

INSTRUCTION MANUAL

ETHERNET INTERFACE MODULE

(Modbus/TCP, for 32-point analog signals)

MODEL

R6-NE1

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Network interface module ..................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside a panel.
• Install lightning surge protectors for those wires connect-

ed to remote locations.

• Insert a noise filter for the communication line connected 

to the unit.  NEC TOKIN Model ESD-SR-250 or equiva-
lent is recommended.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

HOT INSERTION/REMOVAL OF MODULES

• It is possible to replace the module with the power is sup-

plied.  Be sure to replace it when the module is not com-
municating with a host, as it is possible to affect the sys-
tem.  However, replacing multiple modules at once may 
greatly change line voltage levels.  We recommend that 
you replace them one by one.

 

GENERAL PRECAUTIONS

• Do not set the DIP switch on the side panel while the 

power is supplied.  The DIP switch is selectable for main-
tenance without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

Summary of Contents for R6-NE1

Page 1: ...tem The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity HOT INSERTION REMOVAL OF MODULES It is possible...

Page 2: ...to use the second channel of analog I O modules choose the Mode 2 The 2nd channel cannot be sent re ceived in the Mode 1 See COMPONENT IDENTIFICATION NETWORK SLOTS ON THE BASE Mount the Network Modul...

Page 3: ...smitting ON Blank OFF Note Be sure to set unused SW4 through 8 to OFF ETHERNET INDICATORS ID COLOR FUNCTION LINK Red ON at LINK DPLX Red ON with full duplex communication LINK10 Red ON with 10 Mbps co...

Page 4: ...info m system co jp EM 7787 Rev 7 P 4 9 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 90 3 54 5 6 22 90 3 54 LOCKING CLAMP POSITIONING GUIDE 18 71 CON...

Page 5: ...er IP address in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64...

Page 6: ...and a field of event bytes 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave read write 16 Preset Multiple Registers X General purpose register within th...

Page 7: ...address 1 Ai 1 INT 3 Module address 2 Ai 1 INT 4 Module address 3 Ai 1 INT 16 Module address 15 Ai 1 INT 17 18 Module address 0 Ai 1 Float 19 20 Module address 1 Ai 1 Float 21 22 Module address 2 Ai...

Page 8: ...0 0 Internal Communication Counter Every Internal Communication Cycle Adds 1 CHANNEL STATUS Channel Status shows the I O module s data error Input overrange 15 or 115 of Input modules except R6x TSx a...

Page 9: ...verted into 0 to 10000 binary With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converte...

Reviews: