JTY2

EM-1573 Rev.1

P. 1 / 7

The shape of base socket may be different
for some models. 

INSTRUCTION  MANUAL

MODEL

JTY2

PULSE DURATION RECEIVER

(field-programmable; built-in excitation)

Body

Base Socket

Connection

Diagram Label

Front Cover

Specification

Label

Clamp

(top & bottom)

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

Shape and size of the base socket 
are slightly different with various 
socket types.

BEFORE USE ....

Thank you for choosing M-System.  Before use, check the
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.

■ 

PACKAGE INCLUDES:

Signal conditioner (body + base socket) ..................... (1)

■ 

MODEL NO.

Check that model No. described on specification label is
exactly what you ordered.

■ 

INSTRUCTION MANUAL

This manual describes necessary points of caution when you
use this product, including installation and connection, hard-
ware setting, operation of the Programming Unit (model: PU-
2x)* specific to this model and basic maintenance procedures.
This unit is factory adjusted and calibrated according to the
Ordering Information included in the product package.  If you
don’t need to change the pre-adjusted setting, you can skip
the sections on hardware setting and calibration and Soft-
ware Setting in this manual.
*When you need to change software settings, please refer to
the Operation Manual for Model PU-2x (EM-9255), Section
B: (B-1) Introduction, (B-2) General Operation Description,
(B-3) Operation Flowchart for general information.

POINTS OF CAUTION

■ 

POWER INPUT RATING & OPERATIONAL RANGE

• Check the power rating for the unit on the specification label.

85 – 132V AC rating: 85 – 132V, 47 – 66 Hz, approx. 6VA
12, 24, and 48V DC ratings: Rating 

±

10%, approx. 3.3W

110V DC rating: 85 – 150V DC, approx. 3.3W

■ 

UNPLUGGING THE UNIT

• Before you remove the unit from its base socket or mount it,
turn off the power supply and input signal for safety.

■ 

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventila-
tion.
• Do not install the unit where it is subjected to continuous
vibration.  Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +60

°

C (23

to 140

°

F) with relative humidity within 30 to 90% RH in order

to ensure adequate life span and operation.

■ 

WIRING

• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind the unit's cables together with cables where
high noise levels are present.  Do not install them in the same
duct.

■ 

AND ....

• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.

COMPONENT IDENTIFICATION

■ 

HOW TO OPEN THE FRONT COVER:

Position your finger on the hook at the top of front cover and
pull.

INSTALLATION

Detach the yellow clamps located at the top and bottom of the
unit for separating the body from the base socket.

■ 

DIN RAIL MOUNTING

Set the base socket so that its
DIN rail adaptor is at the bot-
tom.  Position the upper hook
at the rear side of
base socket on the DIN rail
and push in the lower.  When
removing the socket, push
down the DIN rail
adaptor utilizing a minus
screwdriver  and pull.

■ 

WALL MOUNTING

Refer to the drawings in the
next page.

Summary of Contents for JTY2

Page 1: ...AL RANGE Check the power rating for the unit on the specification label 85 132V AC rating 85 132V 47 66 Hz approx 6VA 12 24 and 48V DC ratings Rating 10 approx 3 3W 110V DC rating 85 150V DC approx 3...

Page 2: ...4 6 Vsns 2 WIRE PICK UP External DC Supply 5 4 6 Vsns 2 WIRE PICK UP DC SUPPLY 100 Voltage Pulse 5 4 6 Vsns PWR 100 CHECKING 1 Terminal wiring Check that all cables are correctly connected according t...

Page 3: ...0V p p 1 20 1 25 50V p p 1 10 2 10 25V p p 1 5 3 5 10V p p 1 2 4 1 5V p p 1 5 0 5 1V p p 5 6 0 1 0 5V p p 10 7 Open collector or 1 two wire current pulse EXAMPLE 1 VOLTAGE PULSE with Amplitude 5V p p...

Page 4: ...Check that the current value indicated on the ammeter is within the allowable limit If the value is greater than the limit lower the voltage value or connect a separate power source Otherwise the tran...

Page 5: ...XX 1 Low samples to be discarded 0 to 10 11 P 0 Linearization 0 STRAIGHT Without 1 CURVED With ITEM 60 to 91 for segment data input 12 P 0 00 Input zero duty ratio two methods are available Percentag...

Page 6: ...89 P Y 15 XXX XX 90 P X 16 XXX XX 91 P Y 16 XXX XX Modification Code S Modifiable at any time P Modifiable only when the MAINTENANCE SWITCH is in the PRG mode 15 0 Y01 X02 X03 X04 X05 115 Y02 X01 Y03...

Page 7: ...HANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE M SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL INCIDENTAL OR SPECIAL DAMAGES OF ANY KIND WHATSOEVER M System Co Ltd 5 2 55 Minamitsumori Nishinari k...