background image

1

DI-000-RT15Z-00A

(65I00-4ZB)

2

3

4

5

6

7

8

9

10

DESCRIPTION
The RC-1500 is a precision digital thermostat designed for 24 VAC heating and cooling systems. 
The RC-1500 will support the following systems:
•   Single Stage Heat/Cool Conventional
•   Two Stage Conventional (2 Stage Heat / 2 Stage Cool) 
•   Heat Pump and Geothermal Heat Pump (2 Stage Heat / 1 Stage Cool)
•   Two Speed Heat Pump and Geothermal Two Speed Heat Pump (3 Stage Heat / 2 Stage Cool)
•   Dual Fuel Heat Pump and Geothermal Dual Fuel Heat Pump

The RC-1500 has the capability of being controlled both locally and by remote control. It offers 

programmability, stand-alone operation, and wireless communications with automation systems, utility 

control systems, and personal computers. 

Electrical rating: 

 24 V; 2 A; 50/60 Hz

Maximum current: 

 2 A on any circuit, 3 A total

The following requirements must be observed for installation in Europe: CE
1.   This equipment must be installed in accordance with National wiring rules for the country in which it is 

installed.

2.   All product labels, instructions and markings relating to safety must be translated to a language, which 

is acceptable in the country in which this equipment is to be installed.

INSTALLATION
Before installing this thermostat:
1.  Read all of the Installation Instructions carefully.
2.  Read the Owner’s Manual carefully.
3.  Ensure that this product is suitable for your application.
4.  Ensure that wiring complies with all codes and ordinances.
5.  Disconnect power to the control transformer to prevent electrical shock and damage to equipment.
6.  Select an appropriate location to ensure an accurate temperature reading.

LOCATION
When replacing an existing thermostat, install the RC-1500 in the same location. If the existing location 

doesn’t meet the following criteria, choose a new location to mount the RC-1500. When choosing a 

location for the thermostat:
1.  Ensure that the thermostat is mounted 5 feet above the floor and is at least 2 feet from an outdoor wall.
2.  Ensure that the thermostat is located in an area where there is adequate air circulation.
3.  Do not mount in the path of direct sunlight or of radiant heat generated by appliances.
4.  Do not mount behind an outdoor wall, near a fireplace, or in the path of any air ducts.

REMOVING AN EXISTING THERMOSTAT
1.  Disconnect the power to the control transformer.
2.  Remove the cover to the existing thermostat.
3.   Disconnect the wires going to each terminal on the thermostat. Label each wire with the letter or 

number at the terminal.

4.  Remove the existing plate or base from the wall.

MOUNTING
When mounting the RC-1500, grasp the thermostat by the sides, avoiding the keys, and unsnap the base 

from the face. Holding the base to the wall so that the word “UP” is upright and facing you:
1.  Mark the two mounting holes on the wall using a pencil. 
2.  Drill a hole using a 3/16” bit at each mounting hole marking. 
3.   Install the two wall anchors supplied. 
4.   Slide the system wires through the opening in the base. 
5.   Mount the base to the wall using the two #6 x 1/2” self-tapping 

screws supplied -

 See Figure 1.

 

Figure 1

 

Connect each wire to the terminal strip(s) on the thermostat base per the wiring diagram for your system 

application - 

See Figures 4 - 10. Form the thermostat wiring so that the cable lies flat between the 

terminal strip(s) and the center of the base - 

See Figure 2.

If a temperature sensor is being used with the thermostat, connect the remote system or temperature 

sensor wiring per the diagram for the application - 

See Figure 11

Upon completion of wiring the thermostat, push all excess wiring into the hole in the wall. Plug the hole 

with the supplied insulating foam to ensure an accurate temperature reading by the thermostat. 
Align the tabs of the thermostat face with the slots of the thermostat base. Gently push the thermostat 

face into the thermostat base locking it into place - 

See Figure 2.

 

 

Figure 2

 

 

 

 

 

 

   

Wall

Base

Tab

Slot

Temperature

Sensor

 

          

Figure 3

 

 

NOTE: Be sure that the thermostat temperature sensor is standing up, and that it has not been damaged 

during installation - 

See Figure 3.

TYPICAL WIRING DIAGRAMS
CAUTION:
 Be sure to disconnect the power to the control transformer before removing or installing thermostat.
CAUTION: Do not short gas valve, fan, heat relay, or cool relay...even momentarily. 
CAUTION: Do not attempt to hook up to live circuits. An accidental connection to a component on the 

thermostat circuit board could cause damage to the thermostat.

IMPORTANT NOTES:
1.   For HVAC systems with a single transformer for heating and cooling, the metal jumper between 

Terminal 1 (RC) and Terminal 2 (RH) on the left terminal strip must remain in place – 

See Figure 4.

2.  From the factory, the RC-1500 is configured to control a single stage conventional HVAC system. 

•    If the HVAC system is a heat pump, dual fuel heat pump, or if the thermostat is connected to a 

zone control system that requires a sub-base, before operating the thermostat, the “System Type” 

settings under “System Options” must be configured – See Installation Settings.

•    If the HVAC system is a two stage conventional or two speed heat pump, before operating the 

thermostat (making a call for heat or cool), the “Cool Stages” and “Heat Stages” settings under 

“Stage Settings” must be configured – See Installation Settings.

24VAC "HOT"

24VAC Common

24VAC

CONTROL

TRANSFORMER

THERMOSTAT

UP

(C)

(RC)

JUMPER

 

For HVAC systems with a single transformer, the metal jumper between Terminal 1 (RC) and 

 

Terminal 2 (RH) on the left terminal strip must remain in place.  

 

 

Figure 4 

– 

Thermostat power

-

up for test or configuration purposes

 

3.   When configured as a conventional thermostat, by default this thermostat does not turn the fan on with 

a call for heat. If the furnace requires the thermostat to turn the fan on with a call for heat, configure the 

“System Mode” to “Fan On With Heat” under “System Options”.

4.   A conventional thermostat can be configured for automatic changeover heat/cool, manual changeover 

heat/cool, heat only, or cool only thermostat.

5.   Refer to the “Configuration” steps under the wiring diagram for the respective HVAC system type.
6.   If the thermostat or HVAC system does not perform as stated in the “Power Up” steps under the wiring 

diagram for the respective HVAC system, recheck all wiring - See Troubleshooting Tips.

7.   For HVAC systems with separate heating and cooling transformers, the metal jumper between 

Terminal 1 (RC) and Terminal 2 (RH) on the left terminal strip must be removed – 

See Figure 5.

UP

24VAC Common

24VAC Cool "HOT"

24VAC

COOL

TRANSFORMER

24VAC Heat "HOT"

24VAC

HEAT

TRANSFORMER

REMOVE

JUMPER

THERMOSTAT

(C)

(RH)
(RC)

3

1

2

 

For HVAC systems with separate heating and cooling transformers, the metal jumper between  

Terminal 1 (RC) and Terminal 2 (RH) on the left terminal strip must be removed. 

Figure 5 – Connections for heat and cool transformers - applies to all systems

 

SINGLE STAGE CONVENTIONAL FOR ZONE CONTROL SYSTEMS

(W2)

4

(Y2)

(G)

(Y1)

(W1)

(C)

(RC)

10

1

3

8

6

7

ZONE CONTROLLER

THERMOSTAT

System Cool Mode

Fan Relay
Zone Cool
Zone Heat

System Heat Mode

24VAC

CONTROL

TRANSFORMER

Fan
Cool

Cool Mode

24VAC "HOT"

24VAC Common

Heat Mode

Heat

UP

 

 

Figure 7 – Connections for single stage thermostat for zone control systems

 

CONFIGURATION
•     The “System Type” for this thermostat must be set to “Zone Control” under “System Options”.
The two additional outputs (W2 and Y2) are used with zoned heating and cooling systems. The W2 and 

Y2 terminals control the mode of operation (heating or cooling) of the zone control panel. The zone control 

panel will recognize calls for heat (W) from the individual zones when the W2 terminal is energized, and 

calls for cool (Y) when the Y2 terminal is energized. Neither W2 nor Y2 is energized when the mode is set 

to “OFF”. Therefore, the RC-1500 can act as a Master to set the operating mode of the entire system.

POWER UP
1.  Double check wiring, be sure that there are no stray wires or wire strands at the connections.
2.  Connect power to the transformer and system. The display will show the current thermostat settings.
3.  Press [FAN] and select “On”. The fan should come on. 
4.  Press [FAN] and select “Auto”. The fan should go off.
5.   Set the Mode to “Heat”. Raise the desired heat setting above the current temperature. Ensure that the 

heating unit comes on. Set the mode to “Off”. Ensure that the heating unit goes off.

6.   Set the Mode to “Cool”. Lower the desired cool setting below the current temperature. Ensure that the 

cooling unit comes on. Set the mode to “Off”. Ensure that the cooling unit goes off.

TWO STAGE CONVENTIONAL (2 STAGE HEAT / 2 STAGE COOL)

UP

Heat 1

Heat 2
24VAC Common*

24VAC "HOT"

Cool 2

Cool 1

Fan

24VAC

CONTROL

TRANSFORMER

Heat 2 Relay

Heat 1 Relay

Cool 1 Relay

Fan Relay

Cool 2 Relay

THERMOSTAT

HVAC SYSTEM

7

6

8

3

1

10

(RC)

(C)

(W1)

(Y1)

(G)

(Y2)

4

(W2)

 

 

Figure 8 – Connections for two stage conventional thermostat

 

CONFIGURATION
•   The “System Type” for this thermostat must be set to “Conventional” under “System Options”.
•    In the default configuration, this thermostat does not turn the fan on with a call for heat. If the furnace does 

not turn the fan on with a call for heat, the thermostat must be configured to do so under “System Options”. 

•   The “Cool Stages” and “Heat Stages” settings must be configured under “Stage Settings”.

POWER UP
1.  Double check wiring, be sure that there are no stray wires or wire strands at the connections.
2.  Connect power to the transformer and system. The display will show the current thermostat settings.
3.  Press [FAN] and select “On”. The fan should come on. 
4.  Press [FAN] and select “Auto”. The fan should go off.
5.  Press [HOLD] and select “On” to override Energy Efficient Control. 
6.   Set the Mode to “Heat”. Raise the desired heat setting 1° above the current temperature. Ensure that Stage 

1 heat comes on. After a few minutes, raise the desired heat setting 3°s above the current temperature. 

Stage 2 heat should come on. Set the mode to “Off”. Ensure that the heating unit goes off.

7.   Set the Mode to “Cool”. Lower the desired cool setting 1° below the current temperature. Ensure that Stage 

1 cool comes on. After a few minutes, lower the desired cool setting 3°s below the current temperature. 

Stage 2 cool should come on. Set the mode to “Off”. Ensure that the cooling unit goes off. 

8.  Press [HOLD] and select “Off” to enable Energy Efficient Control.

ABOUT HEAT PUMP SYSTEMS
1.  Terminal 5 (O) is energized for cooling, Terminal 6 (B) is energized for heating.

 In most applications, the reversing valve is energized for cooling and should be connected to the 

“O” terminal. If the heat pump requires the reversing valve to be energized for heating, connect the 

reversing valve to the “B” terminal.

2.   With a call for Stage 2 on a two speed heat pump, both compressor outputs Y1 and Y2 are energized. 

When 2 stages of cooling and 2 stages of heating are configured for a heat pump, Stage 2 is 

considered high speed on the heat pump and not auxiliary heat. If auxiliary heat (or emergency heat) is 

needed, configure 3 stages of heating on the heat pump.

3.   To temporarily disable Energy Efficient Control and heat as quickly as possible, press [HOLD] and 

select “On”. The RC-1500 will use the Auxiliary Heat as needed to reach the heat setting.

4.   Terminal 9 (L) is used to indicate a fault with the heat pump compressor. When there is a compressor 

fault, the display will flash red and the “Heat Pump Fault” error message is shown.

5.   The Emergency Heat Relay (E Terminal) and outdoor thermostats (usually accessories to a heat 

pump), are not used. The RC-1500 automatically controls auxiliary heat efficiently. If the heat pump is 

equipped with an outdoor thermostat, it should be removed from the auxiliary heat circuit.

ABOUT DUAL FUEL HEAT PUMP SYSTEMS
A dual fuel heat pump typically has a gas furnace combined with a heat pump. The gas furnace is used 

as auxiliary heat unless the outdoor temperature is very low, in which case it is used as the primary heat 

source.
1.   When used with dual fuel heat pumps, the RC-1500 requires a method for obtaining the outdoor 

temperature. A temperature sensor can be physically connected to the “Remote Temp. Sensor” 

terminals on the thermostat or the RC-1500 can obtain the outdoor temperature from a remote system.
 If the RC-1500 cannot obtain the outdoor temperature, the heat pump compressor will not operate and 

the thermostat will only call for the auxiliary heat until the problem is resolved. When this occurs, the 

display will flash red and the “Problem With Outdoor Temperature Sensor. Some Heat Stages May Be 

Disabled” error message is displayed. After the error has been acknowledged, “Outdoor Sensor Fault” 

will be displayed in the Message Bar until the problem is resolved.

2.  Balance Setpoint Limits:

•    If the outdoor temperature is above the “Upper Balance Setpoint” (45°F by default), the heat pump 

is used exclusively. 

•    If the outdoor temperature falls below the “Upper Balance Setpoint” but is above the “Lower Balance 

Setpoint” (35°F by default) and if the heat pump is unable to heat at a rate of 5°s per hour or better, 

the heat pump will turn off and auxiliary heat will be used until the call for heat has been satisfied. 

•    If the outdoor temperature falls below the “Lower Balance Setpoint”, the heat pump will turn off and 

the auxiliary heat will be used until the call for heat has been satisfied.

•    The Balance Setpoint Limits can be adjusted according to the manufacturer’s specifications under 

“Balance Setpoint” – See Installation Settings.

3.   When the RC-1500 makes a call for auxiliary heat, the heat pump compressor is turned off and the 

auxiliary heat is used exclusively.

HEAT PUMP (2 STAGE HEAT / 1 STAGE COOL)

 

24VAC Common*

24VAC "HOT"

Auxilirary Heat

Compressor

Ground Fault
Fan

Compressor Relay

Aux Heat Relay

Fan Relay

Fault Relay

Reversing Valve

Energized in Cool

Energized in Heat

24VAC

CONTROL

TRANSFORMER

THERMOSTAT

UP

HVAC SYSTEM

7

6

8

3

1

(G)

(Y1)

(B)

(C)

(RC)

4

5

9

(O)

(W2)

(L)

 

Figure 9 – Connections for heat pump thermostat

 

CONFIGURATION
•   The “System Type” for this thermostat must be set to “Heat Pump” under “System Options”.
•    The “System Type” for this thermostat must be set to “Dual Fuel Heat Pump” for a dual fuel system 

(Terminal “W2” is connected to the “W” or “W1” on the furnace).

POWER UP
1.  Double check wiring, be sure that there are no stray wires or wire strands at the connections.
2.  Connect power to the transformer and system. The display will show all of the thermostat settings.
3.  Press [FAN] and select “On”. The fan should come on. 
4.  Press [FAN] and select “Auto”. The fan should go off.
5.  Press [HOLD] and select “On” to override Energy Efficient Control.
6.   Set the Mode to “Heat”. Raise the desired heat setting 1° above the current temperature. Ensure that 

the heat pump comes on, in heating mode. After a few minutes, raise the desired heat setting 3°s 

above the current temperature. Auxiliary heat should come on. After a few minutes, set the mode to 

“EM Heat”. The heat pump should stop but the auxiliary heat should remain on. Set the mode to “Off”. 

Ensure that both the heat pump and auxiliary heat go off.

7.   Set the Mode to “Cool”. Lower the desired cool setting below the current temperature. Ensure that the 

heat pump comes on, in cooling mode. Set the mode to “Off”. Ensure that the cooling unit goes off.

8.   Press [HOLD] and select “Off” to enable Energy Efficient Control.

24VAC "HOT"

Heat

24VAC Common*

Fan
Cool

UP

24VAC

CONTROL

TRANSFORMER

Fan Relay
Cool Relay
Heat Relay

HVAC SYSTEM

THERMOSTAT

(RC)

(C)

(Y1)

(G)

(W1)

1

3

8

6

7

 

*   Common wire is required in “heat only” or “cool only” applications.  Also use a common if heat, cool,  

  or fan relay cannot supply 15mA to power thermostat, without activating. 

Figure 6 – Connections for single stage heat/cool thermostat

 

CONFIGURATION
•   From the factory, the RC-1500 is configured as a single stage conventional heat/cool thermostat. 
•    In the default configuration, this thermostat does not turn the fan on with a call for heat. If the furnace does 

not turn the fan on with a call for heat, the thermostat must be configured to do so under “System Options”.

POWER UP 
1.  Double check wiring, be sure that there are no stray wires or wire strands at the connections.
2.  Connect power to the transformer and system. The display will show the current thermostat settings.
3.  Press [FAN] and select “On”. The fan should come on. 
4.  Press [FAN] and select “Auto”. The fan should go off.
5.   Set the Mode to “Heat”. Raise the desired heat setting above the current temperature. Ensure that the 

heating unit comes on. Set the mode to “Off”. Ensure that the heating unit goes off.

6.   Set the Mode to “Cool”. Lower the desired cool setting below the current temperature. Ensure that the 

cooling unit comes on. Set the mode to “Off”. Ensure that the cooling unit goes off.

The RC-1500 thermostat is designed to work with most single state conventional 4-wire HVAC systems (without 

a transformer common). However, if the RC-1500 “resets” when calling for heat or cool, or if the heat, cool, or 

fan relay cannot supply 15mA to power thermostat without the relay activating, the transformer common wire or 

the LEVITON Thermostat Power Supply Module (Part Number: 30A00-1) is required.

SINGLE STAGE CONVENTIONAL

Comp Stage 2 Relay

Comp Stage 1 Relay

Compressor Stage 2

9

5

4

1

3

8

6

7

(L)

(G)

(Y1)

(B)

(O)

(W2)

(C)

(RC)

UP

HVAC SYSTEM

THERMOSTAT

24VAC

CONTROL

TRANSFORMER

Ground Fault
Fan
Compressor Stage 1
Energized in Heat
Energized in Cool
Auxilirary Heat
24VAC Common*

24VAC "HOT"

Aux Heat Relay

Reversing Valve

Fan Relay

Fault Relay

(Y2)

10

 

Figure 10 – Connections for two speed heat pump thermostat 

CONFIGURATION
•   The “System Type” for this thermostat must be set to “Heat Pump” under “System Options”.
•   The “Cool Stages” and “Heat Stages” settings must be configured under “Stage Settings”.

POWER UP
1.    Double check wiring, be sure that there are no stray wires or wire strands at the connections.
2.    Connect power to the transformer and system. The display will show the current thermostat settings.
3.    Press [FAN] and select “On”. The fan should come on. 
4.    Press [FAN] and select “Auto”. The fan should go off.
5.      Set the Mode to “Heat”. Raise the desired heat setting 1° above the current temperature. Ensure that 

the heat pump comes on, in heating mode. Press [HOLD] and select “On” to override Energy Efficient 

Control. Stage 2 heat should come on. 

6.      Raise the desired heat setting 3°s above the current temperature. Auxiliary heat should come on. 
7.      After a few minutes, set the mode to “EM Heat”. Both stages of the heat pump should stop but the 

auxiliary heat should remain on. Set the mode to “Off”. Ensure that the auxiliary heat goes off.

8.      Press [HOLD] and select “Off” to enable Energy Efficient Control. Set the Mode to “Cool”. Lower 

the desired cool setting 1° below the current temperature. Ensure that the heat pump comes on, in 

cooling mode. Press [HOLD] and select “On”. Stage 2 cool should come on.

9.     Set the mode to “Off”. Ensure that both stages of the cooling unit go off.
10.  Press [HOLD] and select “Off” to enable Energy Efficient Control.

TWO SPEED HEAT PUMP (3 STAGE HEAT / 2 STAGE COOL)

WARNINGS AND CAUTIONS
•    

WARNING: TO AVOID FIRE, SHOCK OR DEATH, turn off power at circuit 

breaker or fuse and test that the power is off before wiring!

•    

WARNING: TO AVOID SERIOUS PERSONAL INJURY OR DEATH, never touch uninsulated wires or 

terminals unless the wiring has been disconnected at the network interface.

•    Read and understand all instructions. Follow all warnings and instructions marked on the product.

•    Do not use this product near water – e.g., near a tub, wash basin, kitchen sink or laundry tub, in a wet 

basement, or near a swimming pool.

•    Never push objects of any kind into this product through openings, as they may touch dangerous voltages.

•    Never install communications wiring or components during a lightning storm.

•    Never install communications components in wet locations unless the components are designed 

specifically for use in wet locations.

•    Use caution when installing or modifying communications wiring or components.

•    SAVE THESE INSTRUCTIONS.

WEB 

VERSION

Reviews: