manualshive.com logo in svg
background image

0       6      12     16     24

2

4

1

292555/00

Technical data

 

4126 31 

4126 32 

4126 33

 

047 61 

6047 60 

047 63

Supply voltage: 

230V 50/60Hz  120V 50/60Hz 

24V AC/DC 

Effective power consumption: Approx. 1 W 
Contact rating:  

1 changeover contact 16A 250V~µ cos 

ϕ

 = 1

Parallel compensation: 

600W max. 70µF

Accuracy:  

~ 0,1 s / day

  

single strand  

 

multi strand

Terminal capacity:

 

1,5...4 mm

2

  

 

1,5...2,5 mm

2

Programmes :  

56 

Battery reserve: 

5 years 

Storage ambient:  

-20°C to +60°C 

Working ambient:  

-20°C to +55°C

IP: 

20

General information

• Start-up: after applying the supply voltage, the time switch
  starts automatically with the last selected function. The relay 
  position is set by the current program.
• Battery backup
  - Backlighting not active
  - Data key READ/WRITE only via the menu

Set language

A

Day, Time, Date

Switch status

Function

Receptacle for 

data key

Overview of programmed 
switching times for the week. 
Resolution 0.5h

Select menu, back to main menu,
Hold down > 1s = operating display

Confirm selection or load parameters

 

Select menu options or set parameters

Overview

Time switch   
D21 - 1-channel
4 126 31 / 32 / 33 - 047 61 / 63 / 6047 60

®

!

  Safety notes

This  product  should  be  installed  in  line  with  installation  rules,  preferably  by  a  qualified  electrician.  Incorrect  installation  and  use  can  lead  to  risk 
of electric shock or fire. Before carrying out the installation read the instructions and take account of the product’s specific mounting location. Do not open 
up, dismantle, alter or modify the device except where specifically required to do so by the instructions. All Legrand products must be opened and repaired 
exclusively by personnel trained and approved by Legrand. Any unauthorised opening or repair completely cancels all liabilities and the rights to replacement 
and guarantees. Use only Legrand brand accessories.
The device contains a LiMnO

2

 primary cell. When the product reaches the end of its life, this cell must be correctly removed and disposed of in accordance with 

national legislation and the requirements of environmental protection.

GB

 
 

Operating principle: Typ 1.B. S. T. 
IEC/EN 60730-1, IEC/EN 60730-2-7 
Operation in a normal environment 
Montage: in distribution panel, Degree of contamination: 2 
Switch output, potential-free

a









d

c

b

g

This symbol indicates that the 
selection is active.

* Only available in EXPERT mode.

2000 W

1000 W

2000 VA

600 W   70µF

+

c

R

2000 W

+

2000 W

2000 W

+

3680 W

Содержание MicroRex D21 Plus

Страница 1: ... 6047 60 Safety notes This product should be installed in line with installation rules preferably by a qualified electrician Incorrect installation and use can lead to risk of electric shock or fire Before carrying out the installation read the instructions and take account of the product s specific mounting location Do not open up dismantle alter or modify the device except where specifically req...

Страница 2: ...ctory set SPECIAL The switchover to from summertime can be freely programmed by entering a start date and end date and is then executed each year on the same day of the week e g Sunday 3 Programming A program consists of an ON time OFF time and associated on and off days Programs with predefined on off days Mon to Sun Mon to Fri and Sat and Sun for these programs you only need to set the switching...

Страница 3: ...ive the programmed switching cycles are shifted at random within the range of 15 minutes Hour counter Displays the total relay ON time 0 to 65535 h and the date of the last reset Load the programs of the time switch on to a data key WRITE KEY Warning all programs stored on the data key will be overwritten or or Load the programs from the data key to the time switch READ KEY Warning all programs pr...

Страница 4: ...tching from ACTIVE to PASSIVE the additional menu items are hidden again and all the Expert mode settings are cancelled After re activating Expert mode will operate again with the basic settings Holiday After activation the holiday program is executed between 0 00h on the start date and 24 00h on the end date Constant ON OFF After the holi day program has run once it must be reactivated Activating...

Страница 5: ...econd increments If the switching time is shorter than the cycle duration the cycle will be shortened accordingly The ON time will remain unchanged If the switching time is actually shorter than the ON time the ON time will be shortened accordingly 0 10 00 0 10 00 0 10 00 0 04 00 0 04 00 0 04 00 15 00 00 15 10 00 15 20 00 15 30 00 15 32 00 Program 1 Relais Chanal 1 Program n min max Period 2s 2h P...

Отзывы: