 Safety instructions 

This product should be installed in compliance with installation rules, preferably by a qualified electrician.

Incorrect installation and use can lead to risk of electric shock or fire.

Before carrying out the installation, read the instructions and take account of the product’s specific mounting location.

Do not open up, dismantle, alter or modify the device except where specifically required to do so by the instructions.

All Legrand products must be opened and repaired exclusively by personnel trained and approved by Legrand.

Any unauthorised opening or repair completely cancels all liabilities and the rights to replacement and guarantees.

Use only Legrand brand accessories.

 

LED  D1  D0    -      +

 

 C     T     R

        

BP1

        

BP2

        

Centralised keypad

5 722 54

Operation :  

Operating mode: connect the reader to manager 0 767 04 and in the manager software, select reader model 0 767 01. 

 

Use: to access the site, enter your code on the keypad, then press #. 

 

 

Entry accepted:    green ind long beep.

 

 

Entry refused:     3 red f 3 short beeps.

Factory settings : 

~

C

T

R

 

Buzzer enable 

 

~

C

T

R

 Wiegand 34 bit 

Master code: 1111 

  Site code: no code

Configuration :  

- Wiegand Mode: Within 30 seconds after power-up, enter the code ‘1111’ twice, press the # key to confirm, and then enter the confirmation code: ‘0’ for 34 bits (by default), ‘1’ for 26 bits, ‘2’ for 4 bits. Exit programming mode by pressing #.

 

- Changing the master code: enter the master code twice (default 1111), confirm by pressing #, the red and green indicators flash,

 

press 1 *,

 

enter the new master code (4 to 8 numbers), confirm by pressing #. A long confirmation beep sounds. Exit by pressing #.

  

Exp:  : 1111  1111  # 1  *  123456  #  #

 

 

- Loading the site code: enter the master code twice, confirm by pressing #,

 

the red and green indicators flash, press 2 *,

 

enter the site code from 001 to 255, confirm by pressing #. A long confirmation beep sounds. Exit programming mode by pressing #.

  

Exp:  : 123456  123456  # 2  *  012  #  #

 

 

- Disabling/enabling the buzzer: enter the master code twice, confirm by pressing #, the red and green indicators flash, press 4 *, enter 0 for disabled or for enabled , confirm by pressing #. A long confirmation beep confirms the modification. Exit programming mode by pressing #

  

Exp:  : 123456  123456  # 2  *  012  #  #

 

 

 

  

   

 Automatic exit from settings if no key is depressed for 60 seconds.

 

- Restore factory settings: keep pushbutton 1 and pushbutton 2 depressed, release pushbutton 2, wait 10 seconds for the long double confirmation beep, then release pushbutton 1 

  

 

 .

 