Klaxon Intrinsically Safe Sounder Range

S00608KL, Issue 6, 12/10/2018

AUDIBLE SIGNALLING DEVICES

APPROVALS

 

AND CONFORMITIES

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание TCC-0001

Страница 1: ...L INFORMATION PLEASE READ PRIOR TO INSTALLATION Klaxon Intrinsically Safe Sounder Range S00608KL Issue 6 12 10 2018 AUDIBLE SIGNALLING DEVICES APPROVALS AND CONFORMITIES www acornfiresecurity com www...

Страница 2: ...ible 2 0 Intrinsically Safe Labelling The product will have an individual serial number printed onto the head base plate an example of the sounder label is shown below These products have been tested...

Страница 3: ...ur and if it does it will only exist for a short time Zone 20 Explosive dust air mixture is continuously present Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosiv...

Страница 4: ...side cutters or a similar tool To open a locked head remove the small rubber bung from the hole on the side of the sounder insert a tool into the hole and depress the clip whilst twisting the head An...

Страница 5: ...lockwise until it comes free Remove the appropriate fixing hole and conduit knockouts from the back box The back box provides IP66 protection For this to be maintained suitably rated minimum IP66 M20...

Страница 6: ...nder head unit onto the installed base the alarm tone must be set see page 5 To control the Sounder use either a switch in the safe area on either the positive or negative lines into the Barrier or by...

Страница 7: ...pin to 0v as detailed in the table on page 5 For this application a barrier with 2 Diode return paths is required as shown in the diagram below Switching between return paths for the 2 stage system wi...

Страница 8: ...section of the installation sheet The Sounder can be turned on and off either by using a suitably placed switch in the positive or negative rails switch must be of suitable ratings if installed in th...

Страница 9: ...ity monitoring to take place and a fire panel compatible with Intrinsically Safe products must also be used If required an external switch can be wired in series with the 1 and or 2 connections to giv...

Страница 10: ...mal operation The enclosure is non conducting and may generate an ignition capable level of electrostatic charge under certain extreme conditions It is the responsibility of the user to ensure that th...

Страница 11: ...rectly rated barrier could damage these products and so void any protection ratings Specific Conditions of Use 1 Clean equipment regularly to prevent dust build up with a damp or anti static cloth onl...

Страница 12: ...15 550Hz 0 7s 1000Hz 0 33s O I I I O O 1 93 16 1500Hz 2700Hz 3Hz O I I I I O 1 98 17 750Hz I O O O O O 1 93 18 2400Hz I O O O I O 1 105 19 660Hz I O O I O O 18 93 20 660Hz 1 8s ON 1 8s OFF I O O I I...