background image

Effective: 

October

 2020

K-71-101

KS-PS Addressable   
SmartOne

® 

 Protocol

Photoelectric Smoke Detector 

FEATURES

• Multi-criteria optical smoke sensing technology

• Advanced data analysis reduces chance of

nuisance alarms

• Compatible with Kidde

®

, Fenwal

®

 

and Chemetron

®

intelligent control units

• Works with SmartOne

®

 

communication protocol

• Operates in conjunction with legacy SmartOne

DS, PSD, CPD and THD smoke and heat detectors

• Two-color (green/red) status LED

• Supports remote LED alarm indication

• Detector head and terminal base design (bases sold

 

separately)

• Low-profile design blends into ceiling

• Suitable for raised floor and plenum applications

• Attractive 6 in. diameter trim ring provided with bases

• Electronic addressing performed with SmartOne

 

Hand-Held Programmer

• FM Approved

• cULus Listed

 

to UL268, 7th edition

California State Fire Marshal Listed

DESCRIPTION

The KS-PS Photoelectric Smoke Detector

 is an intelligent

device that gathers analog information from multiple optical
sensors, converting this data into digital signals. Utilizing
dual optical wavelengths combined with multiple detection
angles, the 

KS-PS

 differentiates particles that are not repre-

sentative of actual smoke. Data is digitally filtered to
remove signal patterns that are typical of nuisance sources,
thus reducing unwanted alarms. To make an alarm deci-
sion, the detector’s on-board microprocessor measures
and analyzes all optical sensor readings and compares this
information to a preprogrammed setting.

ADDRESSING

KS-PS detectors feature electronic addressing. No addressing
switches are used.

PROTOCOL

This product will operate only on a Kidde Fire Systems fire alarm-
suppression control unit employing SmartOne communications
protocol.

STATUS LED

KS-PS detectors use an LED to indicate the detector’s condition.
In normal, standby condition, a green LED flashes at a 9 second
repetition rate. An alarm is indicated by a red flash at a 2.50 sec-
ond repetition rate.

REMOTE ALARM LED

An optional SIGA-LED Remote Indicator can be connected to the 
standard DS-SB base if the KS-PS detector status LED is in a 
location where it cannot be easily viewed.

INSTALLATION

A KS-PS detector mounts to North American 1-gang boxes, 3-1/2
inch or 4 inch octagon boxes, and to 4 inch square electrical
boxes 1-1/2 inches (38 mm) deep. 

EASY TWIST HEAD

A KS-PS detector head is installed onto its base by aligning arrow
marks and gently twisting the head clockwise until secure.
Removal is just as easy and is done by grasping the head and
gently pressing down while turning counter-clockwise. Removal
can be aided with the optional SIGA Removal Tool (P/N SIGA-
RTA). This tool can be attached to a telescoping pole to avoid the
use of ladders.

SENSITIVITY

The alarm sensitivity is the minimum obscuration level at which
the detector initiates an alarm condition and can be specified via
the control unit menus or the remote configuration software. The
control unit to which the detectors are connected is capable of
interrogating each detector to determine its sensitivity. 

Summary of Contents for SmartOne KS-PS

Page 1: ... readings and compares this information to a preprogrammed setting ADDRESSING KS PS detectors feature electronic addressing No addressing switches are used PROTOCOL This product will operate only on a Kidde Fire Systems fire alarm suppression control unit employing SmartOne communications protocol STATUS LED KS PS detectors use an LED to indicate the detector s condition In normal standby conditio...

Page 2: ...e 24 VDC nominal Current Normal Operating Alarm 150 µA 220 µA SLC Protocol SmartOne UL cUL smoke sensitivity range 0 5 to 3 50 ft 2 95 to 11 48 m obscuration Open Area Use Only NOTE Smoke sensitivity is selected at the control unit or with the remote configuration software Default values are 2 0 ft Alarm and 1 5 ft Pre Alarm Refer to the Installation Operation and Maintenance Manual or the Configu...

Page 3: ... wire loops will be wired as shown bringing loose end of loop back to the control unit COMPATIBLE CONTROL UNITS FACUs running software revision 82 4 are compatibility tested but not agency listed with the device s in this data sheet Fire Alarm Control Unit FACU Type Current Product Legacy Product Single Loop ARIES SLX ARIES FenwalNET 6000 MICRO SLX PEGAsys FenwalNET 2000 Multiple Loop ARIES MLX AR...

Page 4: ... Ashland MA 01721 USA Telephone 508 881 2000 K 71 101 Rev AA 2020 Carrier Kidde Fenwal Chemetron and SmartOne are registered trademarks of Kidde Fenwal Inc or its parents subsidiaries or affiliates SIGA LED Remote Indicator OPTIONAL NOTE Maximum wiring resistance to SIGA LED must not exceed 10 Ohms per wire To next detector From control unit or From previous detector DS SB Standard Base Shown with...

Reviews: