Digital Protector

Voltage – Current

         and 

Frequency control

0 -100A

ke-DP01-100A

Phase Sequence Control

Under Voltage Protection

Unbalanced Voltage  
Protection

Over Frequency 
Protection

Under Frequency 
Protection

TRUE  RMS

Latch Function

V

L1

,

V

L2,

V

L3

V

L12,

V

L23,

V

L13

I

L1,

I

L2,

I

L3

Hz

General:

In three phase systems, it measures RMS values of AC voltages,
currents and system frequency sensitively. Using up direction button 
(Select) phase-neutral voltages and phase-phase voltages monitor 
sequentially.
ke-DP01 has many  features. 
Those are;
- Phase Failure

(seq)

- Phase Sequence 

(seq)

- Over Voltage Protection

(o - U)

- Under Voltage Protection

(u - U)

- Voltage Unbalance (asymmetry) Protection

(unb)

- Over Current Protection

(o - C)

- Under Current Protection

(u - C)

- Current Unbalance (asymmetry) Protection

(ubC)

- Over Frequency  Protection

(o - F)

- Under Frequency  Protection

(u - F)

When device is turn on if its adjusted voltages and frequency in its 
interval and if phase sequence is correct relay  switch on.
If any of error occurred ( except phase failure and phase sequence ) 
at the end of adjusted time relay switch off its contact. When system
return normal  values, at the end of time out relay switch on.

L1

L2

L3

Re

< t-1

t-1

Phase Failure:  (u-U)

Before starting system , it controls phase absence then if all phases  
exits Normal LED turn on and relay  contact  switch on. In case of 
missing of any L1,L2,L3 phases , Normal LED turn off  and relay  
switch  off its contact .In this case 

u-U 

warn appears

 

on display.

V

L1

Special Buttons:

L1

L2

L3

V

L2

V

L3

L1

L2

L3

V

L12

L1

L2

L3

V

L23

L1

L2

L3

V

L13

Select: 

(Up direction) 

when pressing continuously, 
screen displays  frequency of 
system. When button release 
device continue to show voltage. 

Reset: 

If error case although disappeared 
then device is not return to normal, 
latch-function occurred and it 
makes locked device. 
Or Lock-function (only for currents) 
may be occured.
After checking error in system then 
 restart device with pushing reset 
button.

Voltage Unbalanced:  (unb)

The phase-phase voltage unbalance limit can be adjusted  
between(5% - 20%) . When it exceeds the adjusted limit , the device 
switched off its out contact at the end of  t-1 delay. In this case  

unb

 

warn  appears on the screen. For the returning normal state, 
asymmetry values should under  20% (hysteresis value). In this case 
at the end of t3 time Normal LED turned on and output contact switch 
on. If the phase-phase voltage  unbalance, return adjusted value 
shorter than  t-1 time, output relay does not release its contact. 
Hysteresis is 20 %.

unb

 = 000(oFF) protection is disable .

Example:

 Let's say that asymmetry value is set to %15 for a 

3 x 380VAC. 
In this case, relay contact switch off  at (380-(380x0.15))=323 V.
Switch on the contact is performed at 323+(380x%15x%20)= 334V. 
(%20 is the hysteresis).

Re

L1,L2,L3

L2,L3

L1
L2
L3

Phase Sequetion:  (Seq)

In case of wrong phase order , Normal LED turned off and relay 
contact is not switch  on. In this case 

seq

  warn appears on the 

screen. If  phase order is corrected , Normal LED turned on and out 
relay switch on.

hys

+ % unb

V

nom

hys

Level

Re

- % unb

t-1

< t-1

t-1

L1,L3,L2

L1,L2,L3

r-t

r-t

Over Voltage Protection

Under Current Protection

Unbalanced Current  
Protection

Over Current Protection

L1

L2

L3

L1

L2

L3

Display Functions:

    (V

max 

- V

min

 % unb  =

            x 100      Hys = 380 x (% Asm) x (% 20)

         380

AREAS OF OPERATION:
 

■  In-Elevator motors protection
■  on submersible pump and electric motors protection 
■  Resistance in oven with

IMPORTANT:

  L1 - N  is device supply inputs. Thus,the applied L1 – N 

voltage must be rated voltage of  system . Otherwise normal led makes 
flash and the device switched off its output contact.
The measured frequency also  must the  frequency  of the system.

®

Summary of Contents for ke-DP01-100A

Page 1: ...gh disappeared then device is not return to normal latch function occurred and it makes locked device Or Lock function only for currents may be occured After checking error in system then restart device with pushing reset button Voltage Unbalanced unb The phase phase voltage unbalance limit can be adjusted between 5 20 When it exceeds the adjusted limit the device switched off its out contact at t...

Page 2: ...evice will wait to switch on its output relay when failure ends after a switch off It can be set between 0 5 and 99 9 seconds Very Over Current Coefficient VOC Current Very Sudden Switch Off Protection It can be set by the user between 2 1 and 6 When the current value exceeds the adjusted value within the start delay time the device switches off its output contact immediately Very Over Current val...

Page 3: ...ge t 1 00 1 99 9 sec Delay Time for Frequency t 2 00 1 99 9 sec Over Frequency o F u F 0 4 70 Hz oFF function is disabled Under Frequency u F 40 Hz o F 0 4 oFF function is disabled Accessing Voltage Parameter Accessing Current Parameter Over Current o C oFF function is disabled Hysteresis Value hYS 00 3 3 0 50 50 Delay Time for Current d t 0 1 60 sec Start Delay Time Sdt 0 1 60 sec oFF function is...

Page 4: ...rrent Transformer Ratio X 5A Current Measurement Range 0 100 Amp AC Voltage Measurement Range Phase Phase 10 500 Vac 45 65Hz Phase Neutral 10 300 Vac 45 65Hz For power supply L1 N 176V 242V Voltage Measurement Power Consumption 1VA for one phase Measurement Sensitivity 1 1 digit Contact Current Max 3A 240Vac Device Protection Class IP 20 Connector Protection Class IP 00 Temperature 5 C 50 C Connec...

Reviews: