NETCOM6P-Encrypted Installation Guide  

This guide outlines how to install and program the NETCOM6P—serial to Ethernet 
converter—for network communication. As the NETCOM6P can be configured to operate 
with a CIM or directly from a PC109x or later control board, this guide is divided into the 
following 2 separate installation sections:  

 

NETCOM6P/CIM Installation—page 2 

 

NETCOM6P/ACU Control Board Installation (PC109x or later)—page 11 

Please refer to the appropriate installation instructions and diagrams. Installation 
procedures are different for each type of configuration.   

Important 

Installing the NETCOM6P involves 2 wiring procedures: temporary serial programming 
connections and permanent operation connections. This applies to both types of 
installations. Please be sure to review the relevant diagrams for programming and 
operating connections. 

Before You Start 

 

Verify that you have all the parts as outlined below. 

 

Obtain a static IP address, Subnet Mask, and, if applicable, a Gateway from the 
network administrator for each NETCOM6P. Space for recording addresses is provided 
at the back. 

 

Ensure that you install the latest Keyscan NETCOM Program Tool utility, which is on 
the enclosed CD, on a laptop or PC that can be serially connected to program the 
NETCOM6P. 

About the Reset Function 

During the NETCOM6P programming procedures, you are prompted to reset the device, 
which is a soft re-boot. This is equivalent to a power cycle. 

Contents 

 

 

NETCOM6P/CIM Installation 

 

NETCOM6P/ACU Installation 

12 

 

Specifications 

20 

 

 

 

 

Parts List 

 

NETCOM6P 

 

Serial Data Cable 

 

Utilities & Drivers CD 

 

 

 

 

 

 

 

 

Summary of Contents for Keyscan NETCOM6P

Page 1: ...ent operation connections This applies to both types of installations Please be sure to review the relevant diagrams for programming and operating connections Before You Start Verify that you have all the parts as outlined below Obtain a static IP address Subnet Mask and if applicable a Gateway from the network administrator for each NETCOM6P Space for recording addresses is provided at the back E...

Page 2: ... screen select Communication Setup Follow the on screen prompts 3 Open Explorer navigate to the Program Files folder Keyscan7folder For Vantage open the Keyscan Vantage folder 4 Open the Keyscan7Settings Encryption application For Vantage open the KeyscanVantageSettingsEncryption application 5 Click OK for English or select a language then click OK 6 Create an encryption key and record it It is re...

Page 3: ... circuit board Do not change the orientation of the standoffs TD1 RD1 TD2 RD2 GND RTS CTS GND RTS CTS B3 B2 B1 B0 Diag J2 RESET CAN2 EGND CAN1 GND V 12V SCKT1 PC106x J1 J7 J8 J6 J5 CAN2 CAN1 1 2 1 2 1 2 1 2 Rx COM COM CAN CAN Tx J3 J4 J9 J12 Power Good COM1 COM2 HDR1 J10 J11 Fault Flashing RJ45 Terminal Jack RESET NETCOMP Standoffs NETCOMP CIM Standoff correct mounting orientation Standoff Program...

Page 4: ...elect the port on the laptop or PC with the serial connection to the CIM in order to program the device 13 Select the baud rate that corresponds to the J16 or S2 communication settings depending on the version of PC109x control board 14 Leave Ethernet Connection Type on Automatic negotiation unless the IT administrator gives a specific setting If the NETCOM device experiences network communication...

Page 5: ...has been programmed and momentarily short the RESET jumper on the NETCOM6P 21 Remove the jumper from J12 on the CIM circuit board 22 Place a jumper ON J4 on the CIM unit to enable the board for network communication This designates it as CIM 0 23 Momentarily place a jumper on the CIM board s J1 RESET pins to initiate the jumper change in the preceding step 24 Connect an Ethernet cable from the RJ4...

Page 6: ... mA 290 mA CIM 0 TD1 RD1 TD2 RD2 GND RTS1 CTS1 GND RTS2 CTS2 B3 B2 B1 B0 Diag J2 RESET CAN2 EGND CAN1 GND V 12V SCKT1 Tx Data PC106x J1 J7 J8 J6 J5 CAN2 CAN1 Rx Data 1 2 1 2 1 2 1 2 COM COM CAN CAN J3 J4 J9 J12 Power Good Fault COM2 HDR1 J10 J11 RJ45 Terminal Jack RESET U2 NETCOMP Standoffs To program NETCOM2P 6P jumper ON J12 KI 00465E 04 13 COM1 Control Board PC 109x Common AUX Inputs E 24 23 22...

Page 7: ...ly Current Draw CIM 150 mA NETCOMP 140 mA 290 mA CIM 0 TD1 RD1 TD2 RD2 GND RTS1 CTS1 GND RTS2 CTS2 B3 B2 B1 B0 Diag J2 RESET CAN2 EGND CAN1 GND V 12V SCKT1 Tx Data PC106x J1 J7 J8 J6 J5 CAN2 CAN1 Rx Data 1 2 1 2 1 2 1 2 COM COM CAN CAN J3 J4 J9 J12 Power Good Fault COM2 HDR1 J10 J11 RJ45 Terminal Jack RESET U2 NETCOMP Standoffs To program NETCOM2P 6P jumper ON J12 KI 00257E 04 13 COM1 Temporary co...

Page 8: ...AN2 CAN1 Rx Data 1 2 1 2 1 2 1 2 COM COM CAN CAN J3 J4 J9 J12 Power Good Fault COM2 HDR1 J10 J11 RJ45 Terminal Jack RESET NETCOMP Standoffs To program NETCOM2P 6P jumper ON J12 KI 00467E 04 13 COM1 BRN WHT GRN WHT TX RX 485 OUT 485 IN Connect ribbon cable from HDR1 on CIM 0 to H2 on control board Control board requires power from DPS 15 Place a jumper on J12 to set the CIM for Program mode After p...

Page 9: ... USB cable to 12VDC power supply Current Draw CIM 150mA NETCOMP 140mA 290mA CIM 0 TD1 RD1 TD2 RD2 GND RTS1 CTS1 GND RTS2 CTS2 B3 B2 B1 B0 Diag J2 RESET CAN2 EGND CAN1 GND V 12V SCKT1 Tx Data PC106x J1 J7 J8 J6 J5 CAN2 CAN1 Rx Data 1 2 1 2 1 2 1 2 COM COM CAN CAN J3 J4 J9 J12 Power Good Fault COM2 HDR1 J10 J11 RJ45 Terminal Jack RESET NETCOMP Standoffs To program NETCOM2P 6P jumper ON J12 KI 00258E...

Page 10: ... board Jumper ON J4 TD1 RD1 TD2 RD2 GND RTS CTS GND RTS CTS B3 B2 B1 B0 Diag J2 RESET CAN2 EGND CAN1 GND V 12V SCKT1 PC106x J1 J7 J8 J6 J5 CAN2 CAN1 1 2 1 2 1 2 1 2 Rx COM COM CAN CAN Tx J3 J4 J9 J12 Power Good Fault COM1 COM2 HDR1 J10 J11 Control Board PC 109x Common AUX Inputs E 24 23 22 21 20 19 18 17 H1 H2 RJ45 Terminal Jack J1 U2 NETCOMP Standoffs CIM 0 NETCOMP CIM Standoff correct mounting o...

Page 11: ...2 1 2 Rx COM COM CAN CAN Tx J3 J4 J9 J12 Power Good Fault HDR1 J10 J11 CIM 0 CIM 1 CIM n Slave Global Master Termination Jumpers ON J5 J6 J7 J8 first last CIM Connect EGND terminal on all CIMs to ground lugs in ACU metal enclosures Global Master Jumper ON J3 CAT 5 CANBUS Slave Jumper OFF J3 H2 H2 KI 00471E 07 13 CAT 5 CANBUS Termination Jumpers ON J5 J6 J7 J8 first last CIM Slave H1 Slave Jumper O...

Page 12: ...ect Communication Setup Follow the on screen prompts 3 Open Explorer navigate to the Program Files folder Keyscan7 folder For Vantage open the Keyscan Vantage folder 4 Open the KeyscanSettingsEncryption application For Vantage open the KeyscanVantageSettingsEncryption application 5 Click OK for English or select a language then click OK 6 Create an encryption key and record it It is required to pr...

Page 13: ...s configuration only supports a single panel communication loop For programming the NETCOM6P required use a direct serial connection via the RS 232 COM4 terminal block on the ACU control board as instructed 1 Touch the earth ground lug in the ACU metal enclosure to discharge body static 2 Power down the ACU control board 3 Using a 4 Phillips screwdriver unfasten the 6 screws holding the ACU protec...

Page 14: ... speed duplex setting Set the NETCOM so it matches the network equipment setting If the network equipment was on an automatic setting then reconfigure both the network equipment which may include routers or switches and the NETCOM to a matching fixed speed and duplex setting As an example NETCOM 100 Mbit Half Duplex Network equipment 100Mbit Half Duplex 16 Click on a radio button that corresponds ...

Page 15: ...tions for permanent operation re locate to a PC connected to the network and PING the NETCOM2 s IP address using the Command Prompt The Average Round Trip Times should be less than 100 milliseconds and the Packets Sent should equal the Packets Received with 0 loss Continue at step 29 28 Wait for the PING Status result message IP Success indicates the NETCOM6P has network communication IP Timed Out...

Page 16: ... shown in Figure 8 Figure 7 Serial Programming Connections RJ45 Terminal Jack NETCOMP RESET Control Board PC 109x Cut view with ACU protective cover removed Common AUX Inputs E CPB CB MODULE COM4 AUX Inputs D Common IOCB COM1 NETCOMP plugs into M1 on control board For programming a NETCOM2P or NETCOM6P J16 jumpers F G ON Or S2 DIP switches 7 8 ON RS 232 COM4 GND TD RD DCD DTR CTS PC or laptop with...

Page 17: ...COMP RESET Control Board PC 109x Cut view with ACU protective cover removed Common AUX Inputs E CPB CB MODULE COM4 AUX Inputs D Common IOCB COM1 NETCOMP plugs into M1 on control board RS 232 COM4 GND TD RD DCD DTR CTS PC or laptop with Keyscan NETCOM Program Tool Utility TAMPER TB3 SWITCH KI 00254E 08 13 For programming a NETCOM2P or NETCOM6P J16 jumpers F G ON Or S2 DIP switches 7 8 ON ...

Page 18: ... WAN Keyscan requires a point to point private network where NETCOMs are used on a LAN WAN TCP IP that integrates building to building communication Figure 9 NETCOM2P PC109x or higher Control Board Connections PC 10 100 Base T Cable Control Board NETCOM2P or NETCOM6P to network Host PC with Communication Manager Parts List to network 10 or 100 Base T Current Draw ACU NETCOMP 270 mA RJ45 Terminal J...

Page 19: ...NETCOM6P Installation Guide 19 This page is intentionally blank ...

Page 20: ...AES Rijndael encryption For more information on encryption visit http www bis doc gov encryption default htm http www bis doc gov policiesandregulations regionalconsiderations htm RJ45 Ethernet Xport LED States The RJ45 Ethernet terminal has two bi colour LEDs Link LED left side Activity LED right side Amber flashing 10 Mbps Amber flashing Half duplex Green flashing 100 Mbps Green flashing Full du...