manualshive.com logo in svg
background image

Series TY-L – 5.6 and 8.0 K-factor 

Upright, Pendent, and Recessed Pendent Sprinklers 

Standard Response, Standard Coverage

Page 1 of 6 

MAY 2020 

TFP110

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Series TY-L 5.6 and 

8.0 K-factor Upright, Pendent, 

and Recessed Pendent Sprin-

klers described herein are stan-

dard response, standard coverage, 

solder type spray sprinklers. They are 

designed for use in light, ordinary, and 

extra-hazard commercial occupan-

cies such as banks, hotels, shopping 

malls, factories, refineries, and chemi-

cal plants.
The Series TY-L Recessed Pendent 

Sprinkler, where applicable, is 

intended for use in areas with a fin-

ished ceiling. It uses a two-piece 

Style 20 (1/2 in. NPT) or Style 30 

(3/4 in. NPT) Recessed Escutcheon. 

The Recessed Escutcheon provides  

1/4 in. (6,4 mm) of recessed adjust-

ment or up to 1/2 in. (12,7 mm) of total 

adjustment from the flush pendent 

position. The adjustment provided by 

the Recessed Escutcheon reduces the 

accuracy to which the fixed pipe drops 

to the sprinklers must be cut.
Corrosion-resistant coatings, where 

applicable, are utilized to extend the 

life of copper alloy sprinklers beyond 

what would be obtained when exposed 

to corrosive atmospheres. Although 

corrosion-resistant coated sprinklers 

have passed the standard corrosion 

tests of the applicable approval agen-

cies, the testing is not representative 

of all possible corrosive atmospheres.  

Consequently, it is recommended 

that the end-user be consulted about 

the suitability of these coatings for 

any given corrosive environment. The 

effects of ambient temperature, con-

centration of chemicals, and gas/

chemical velocity, should be consid-

ered as a minimum, along with the cor-

rosive nature of the chemical to which 

the sprinklers will be exposed.
An intermediate level version of the 

Series TY-L Pendent Sprinkler can be 

obtained by utilizing the Series TY-L 

Pendent Sprinkler in combination with 

the Model S Shield.

NOTICE

The Series TY-L 5.6 and 8.0 K-fac-

tor Upright, Pendent, and Recessed 

Pendent Sprinklers described herein 

must be installed and maintained in 

compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION (NFPA), in addition to 

the standards of any other authorities 

having jurisdiction. Failure to do so 

may impair the performance of these 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.
NFPA 13 prohibits installation of 1/2 in. 

NPT sprinklers with K-factors greater 

than 5.6 in new construction. They are 

intended for retrofit in existing sprinkler 

systems only.

Sprinkler 

Identification 

Number (SIN)

TY3111  � � �  Upright 5�6K, 1/2 in� NPT
TY3211 � � �Pendent 5�6K, 1/2 in� NPT
TY4111  � � �  Upright 8�0K, 3/4 in� NPT
TY4211 � � �Pendent 8�0K, 3/4 in� NPT
TY4811 � � �  Upright 8�0K, 1/2 in� NPT
TY4911 � � �Pendent 8�0K, 1/2 in� NPT

TY3111 is a re-designation for S1800 and G3111
TY3211 is a re-designation for S1801 and G3112
TY4111 is a re-designation for S1810 and G3101
TY4211 is a re-designation for S1811 and G3102
TY4811 is a re-designation for S1805
TY4911 is a re-designation for S1806

Содержание tyco TY-L Series

Страница 1: ...ve passed the standard corrosion tests of the applicable approval agen cies the testing is not representative of all possible corrosive atmospheres Consequently it is recommended that the end user be consulted about the suitability of these coatings for any given corrosive environment The effects of ambient temperature con centration of chemicals and gas chemical velocity should be consid ered as ...

Страница 2: ...on Deflector 3 7 6 5 4 2 1 5 Strut Ejection 3 Frame 1 Element Fusible Sealing Button 2 Spring 4 Deflector 7 6 Hook 3 4 NPT 2 7 8 73 0 mm DIA 2 11 16 68 3 mm 2 11 16 68 3 mm 1 2 12 7 mm NOMINAL MAKE IN UPRIGHT PENDENT CROSS SECTION RECESSED PENDENT 2 5 8 66 7 mm 7 16 11 1 mm NOMINAL MAKE IN 2 5 8 66 7 mm 2 50 8 mm WRENCH FLANGES ESCUTCHEON PLATE SEATING SURFACE 2 7 8 73 0 mm DIA WRENCH AREA 3 STYLE...

Страница 3: ...nted 1 2 3 N A6 212 F 100 C White 1 2 3 NOTES 1 UL Listed 2 C UL Listed 3 FM Approved 4 FM Approved for maximum 150 F 68 C ambient temperatures 5 LPCB Approved LPCB Ref No 094a 03 6 Not Available N A K Factor Type Temperature Rating Frame Color Code Sprinkler Finish Natural Brass Chrome Plated Lead Coated Wax Coated Wax Over Lead Coated 8 0 3 4 in NPT Upright TY4111 165 F 74 C Unpainted 1 2 3 5 1 ...

Страница 4: ... 8 3 2 mm 2 7 8 DIA 73 0 mm 1 2 12 7 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING 7 16 1 8 11 1 3 2 mm 2 1 4 DIA 57 2 mm MOUNTING PLATE 1 8 3 2 mm 2 7 8 DIA 73 0 mm CLOSURE TY L 1 1 2 38 1 mm 1 3 4 44 5 mm 1 4 6 4 mm 1 2 12 7 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING 7 16 1 8 11 1 3 2 mm 2 1 4 DIA 57 2 mm MOUNTING PLATE 1 8 3 2 mm 2 7 8 DIA 73 0 mm CLOSURE 1 4 6 4 mm TY L 1 1 2 38 1 mm 1 3 4 ...

Страница 5: ...rdance with this section Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified Absence of an escutcheon which is used to cover a clearance hole may dela...

Страница 6: ...ching up to twenty five sprinklers The wax used for 280 F 138 C sprinklers isthesameasfor212 F 100 C sprinklers Therefore the 280 F 138 C sprinkler is limited to the same maximum ceiling temperatureasthe212 F 100 C sprinkler which is 150 F 65 C completed to verify the integrity of the corrosion resistant coating Thereafter annual inspections per NFPA 25 should suffice however instead of inspecting...

Отзывы: