ILLUSION — 11.2 K-factor

Extra Large Orifice Concealed Pendent Sprinklers

Quick & Standard Response, Standard Coverage

Page 1 of 4 

AUGUST 2018 

TFP184

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO ILLUSION, 11.2 K-factor, 

Extra Large Orifice Concealed Pendent 

Sprinklers quick, response, standard 

coverage, are decorative, fast response 

solder type sprinklers featuring a flat 

cover plate designed to conceal the 

sprinkler. When limited water pressure 

is available and a higher applied water 

density is necessary, the ILLUSION 

is the best choice for architecturally 

sensitive areas such as casinos, hotel 

lobbies, office buildings, churches, and 

restaurants.
Each unit includes a Cover Plate 

Assembly that conceals the sprin-

kler operating components above 

the ceiling. The separable two-piece 

design of the Cover Plate and Support 

Cup Assemblies allows installation of 

the sprinklers and pressure testing 

of the fire protection system prior to 

installation of a suspended ceiling or 

application of the finish coating to a 

fixed ceiling. They also permit removal 

of suspended ceiling panels for access 

to building service equipment without 

having to first shut down the fire pro-

tection system and remove sprinklers.
Also, the separable two-piece design 

of the Sprinkler provides for 3/4 in.  

(19,1 mm) of vertical adjustment to 

provide a measure of flexibility with 

regard to which the length of fixed pipe 

drops to the sprinklers must be cut.
The ILLUSION Sprinklers are shipped 

with a Disposable Protective Cap. The 

Protective Cap is temporarily removed 

for installation, and it can be replaced 

to help protect the sprinkler while the 

ceiling is being installed or finished. The 

tip of the Protective Cap can also be 

used to mark the center of the ceiling 

hole into plaster board, ceiling tiles, etc. 

by gently pushing the ceiling product 

against the Protective Cap. When the 

ceiling installation is complete, the Pro-

tective Cap is re- moved and the Cover 

Plate Assembly installed.
As an option, the ILLUSION Pendent 

Sprinklers may be fitted with a silicone 

Air and Dust Seal (Ref. Figure 4). The 

Air and Dust Seal is intended for sensi-

tive areas where it is desirable to stop 

air and dust travel through the cover 

plate from the area above the ceiling.

NOTICE

The ILLUSION Concealed Pendent 

Sprinklers described herein must be 

installed and maintained in compli-

ance with this document and with the 

applicable standards of the National 

Fire Protection Association, in addition 

to the standards of any other authori-

ties having jurisdiction. Failure to do so 

may impair the performance of these 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number (SIN)

TY5521

Technical 

Data

Approvals

UL and C-UL Listed

(The listings apply only to the service 

conditions indicated in the Design Cri-

teria section.)

Approvals for Air & Dust Seal

UL and C-UL Listed for use with the 

ILLUSION (TY5521); however, use of 

the Air & Dust Seal changes the sprin-

kler response rating from quick to 

standard.

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficient

K = 11.2 GPM/psi

½

 (161,3 LPM/

bar

½

)

Temperature Ratings

160°F (71°C) Sprinkler/139°F (59°C) Plate

212°F (100°C) Sprinkler/165°F (74°C) Plate

Adjustment

3/4 in. (19,1 mm)

Finishes

Cover Plate: Refer to Ordering Proce-

dure section

Physical Characteristics

Body  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Saddle . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Sealing Assembly  . .Beryllium Nickel w/TEFLON 

Solder Link Halves  . . . . . . . . . . . . . . . . . .  Nickel

Lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Compression Screw . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . Bronze/Brass

Guide Pin Housing  . . . . . . . . . . . . . . . . . .Bronze

Guide Pins . . . . . . . . . . . . . . . . . .  Stainless Steel

Support Cup . . . . . . . . . . . . . . . . . . .Plated Steel

Cover Plate . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Retainer . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Cover Plate Ejection Spring . . . .  Stainless Steel

Summary of Contents for tyco ILLUSION

Page 1: ...rarily removed for installation and it can be replaced to help protect the sprinkler while the ceiling is being installed or finished The tip of the Protective Cap can also be used to mark the center of the ceiling hole into plaster board ceiling tiles etc by gently pushing the ceiling product against the Protective Cap When the ceiling installation is complete the Pro tective Cap is re moved and ...

Page 2: ...ler must only be installed in the pendent position and with the centerline of the sprinkler per pendicular to the mounting surface Step 2 Remove the Protective Cap Step 3 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 4 Wrench tighten the sprinkler using only the W Type 18 Sprinkler Wrench Ref Figure 3 The W Type 18 Sprinkler Wrench ...

Page 3: ...osition If the Cover Plate Retainer Assembly cannot be engaged with the Support Cup or the Cover Plate Retainer Assembly cannot be engaged sufficiently to contact the ceiling the Sprinkler Fitting must be repositioned 3 3 16 DIA 81 0 mm 2 1 2 DIA 63 5 mm MOUNTING SURFACE 3 16 4 8 mm FACE OF SPRINKLER FITTING DEFLECTOR IN OPERATED POSITION 3 4 19 1 mm THREADED ADJUSTMENT SPRINKLER SUPPORT CUP ASSEM...

Page 4: ...ged by dropping striking wrench twist slippage or the like must be replaced Also replace any sprin kler that has a cracked bulb or that has lost liquid from its bulb Ref Installa tion Section If a sprinkler must be removed do not reinstall it or a replacement without reinstalling the Cover Plate Assembly If a Cover Plate Assembly becomes dislodged during service replace it immediately The owner is...