TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions

1

Applications

The TEC2101-3 Thermostat is an N2 networked device 
that provides control of single-stage heating/cooling 
equipment. The technologically advanced TEC2101-3 
Thermostat features a Building Automation System 
(BAS) N2 Bus communication capability that enables 
remote monitoring and programmability for efficient 
space temperature control. 

North American Emissions Compliance

United States

This equipment has been tested and found to comply 
with the limits for a Class A digital device pursuant to 
Part 15 of the FCC Rules. These limits are designed to 
provide reasonable protection against harmful 
interference when this equipment is operated in a 
commercial environment. This equipment generates, 
uses, and can radiate radio frequency energy and, if 
not installed and used in accordance with the 
instruction manual, may cause harmful interference to 
radio communications. Operation of this equipment in a 
residential area is likely to cause harmful interference, 
in which case the user is required to correct the 
interference at his/her own expense.

Canada

This Class (A) digital apparatus meets all the 
requirements of the Canadian Interference-Causing 
Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte 
toutes les exigences du Règlement sur le matériel 
brouilleur du Canada.

Installation

Location Considerations

Locate the TEC2101-3 Thermostat:

on a partitioning wall, approximately 5 ft (1.5 m) 
above the floor in a location of average 
temperature

away from direct sunlight, radiant heat, outside 
walls, behind doors, air discharge grills, stairwells, 
or outside doors

away from steam or water pipes, warm air stacks, 
unconditioned areas (not heated or cooled), or 
sources of electrical interference

Note:

Allow for vertical air circulation to the 

TEC2101-3 Thermostat.

IMPORTANT:

The TEC2101-3 Thermostat is 

intended to provide an input to equipment under 
normal operating conditions. Where failure or 
malfunction of the thermostat could lead to personal 
injury or property damage to the controlled 
equipment or other property, additional precautions 
must be designed into the control system. 
Incorporate and maintain other devices such as 
supervisory or alarm systems or safety or limit 
controls intended to warn of, or protect against, 
failure or malfunction of the thermostat. 

TEC2101-3 N2 Networked Single-Stage Thermostat

Installation Instructions

Part No. 24-9890-420, Rev. —

Issued September 14, 2006

Summary of Contents for TEC2101-3 N2

Page 1: ...Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada Installation Location Considerations Locate the TEC2101 3 Thermostat on a partitioning wall approximately 5 ft 1 5 m above the floor in a location of average temperature ...

Page 2: ...hermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors included with the thermostat flush to the wall surface 7 Position the thermostat mounting base on the wall and use the two mounting screws included with the thermostat to secure the base to the surface as ill...

Page 3: ...ing all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the TEC2101 3 Thermostat Figure 5 Wiring the TEC2101 3 Thermostat If using the same power source for the thermostat and heating loads install ...

Page 4: ...ontroller commands an override of an analog or binary object all local changes attempted through the thermostat keypad for that object are ignored until the override is released For example if the supervisory controller sends an override message to turn System Mode Off and then the user selects System Mode On at the thermostat keypad the thermostat keeps the System Mode Off When an override is rel...

Page 5: ...6 7 BI 1 N2 BI CSBI 0 Off 1 On Temp Alarm6 BI 2 N2 BI CSBI 0 Normal 1 Alarm DI26 7 BI 3 N2 BI CSBI 0 Off 1 On 1 Commandable 2 The Heating and Cooling Setpoint SP cannot be overridden simultaneously this also applies to the Setback Heating SP and Setback Cooling SP The overridden setpoint must be released prior to overriding the other setpoint Additionally if one setpoint is overridden the other se...

Page 6: ...nt is overridden the TEC if necessary adjusts the other setpoint to maintain the minimum 2 F deadband between the setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2 F apart Failure to stay within the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2101 3 thermostat Overrides take precedence over any local adjustment or comma...

Page 7: ...cy Status Occupied Unoccupied Override Outdoor Temperature An outdoor air temperature sensor must be connected Applicable Alarms The backlight lights up as an alarm condition is displayed Note Press the YES SCROLL key to temporarily stop this menu from scrolling The Main User Menu is used to access and change the basic operating parameters of the thermostat Access this menu by pressing the MENU ke...

Page 8: ...ayed on the thermostat when the input is energized This input can be tied into the air conditioning unit control card which provides an alarm should there be a malfunction Filter A Filter alarm is displayed This alarm can be connected to a differential pressure switch that monitors a filter RemOVR Temporary occupancy request via a remote input This override function is controlled by a manual remot...

Page 9: ...3 0 or 4 0 cycles per hour Deadband Sets the minimum deadband between the heating and cooling setpoints Default 2 0F 1 0C Range 2 0F 1 0C to 4 0F 2 0C adjustable in 1 0F 0 5C increments Fan cont Determines how the fan is activated in response to a call for heating Fan cont applies to W1 and Fan Mode auto only Fan cont does not affect fan operation on a call for cooling Y1 Default on off The thermo...

Page 10: ...tdoor air temperature Requires that an outdoor air temperature sensor be installed and connected Default 120 F 49 C Range 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Discontinues cooling operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed and connected Default 40 F 40 C Range 40 F 40 C to 95 F 35 C adjustable in 5F 5C ...

Page 11: ...nly appears when the thermostat is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied override state this is the first prompt 2 Press the YES key to resume the programmed schedule The thermostat returns to the Status Display Menu Entering Permanent Tempe...

Page 12: ... the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu Selecting the Fan Mode The thermostat has three fan mode settings On Fan Mode on Energizes the fan all the time for both occupied and unoccupied states even if the system mode is set to off Automatic Fan Mode auto Energizes the fan ...

Page 13: ...ition Possible Cause Solution Thermostat Cycles Online and Offline Two or more controllers have the same address Change each duplicate address to a unique number There are Y or T taps on the N2 Bus or the repeater has lost power or is wired incorrectly Refer to the N2 Communications Bus Technical Bulletin LIT 636018 Thermostat Does Not Come Online Two or more controllers have the same address Chan...

Page 14: ... Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95 RH Maximum Noncondensing Storage 22 to 122 F 30 to 50 C 95 RH Maximum Noncondensing Compliance United States UL Listed File E27734 CCN XAPX Under UL 873 Temperature Indicating and...

Reviews: