www.ismacontrolli.com

DMP262en | 1st Issue rev. 8 | 05/2022

iSMA-B-MINI/MIX

User Manual

Modbus

 

 

Summary of Contents for 4I4O-H

Page 1: ...www ismacontrolli com DMP262en 1st Issue rev 8 05 2022 iSMA B MINI MIX User Manual Modbus ...

Page 2: ...ions 17 4 2 Power Supply Connection 18 4 3 LED Indicators 18 4 3 1 MIX Series Front Panels 18 4 3 2 MINI Series Front Panels 19 4 4 RS485 Port 22 4 4 1 RS485 Communication Bus Connection 22 4 4 2 RS485 Network Termination 22 4 5 Setting Module Address 22 4 6 Baud Rate 23 4 7 Protocol 23 4 8 Default Settings 23 4 8 1 Restoring Default Settings 25 5 Inputs and Outputs 26 5 1 Local I O 26 5 2 Univers...

Page 3: ...08 35 6 7 Up Time 30012 35 6 8 Hardware Version 30130 35 6 9 MAC Address 30131 35 6 10 Device Actions 40001 35 6 11 Baud Rate 40136 35 6 12 Stop Bits 40137 35 6 13 Data Bits 40138 36 6 14 Parity Bit 40139 36 6 15 Response Delay Time 40140 37 6 16 Watchdog Time 40141 37 7 LocalIO Registers 38 7 1 Universal Input Registers 38 7 1 1 Status of Universal Inputs Working as Digital Inputs 30017 38 7 1 2 ...

Page 4: ... 44 7 4 3 Hand Control Status of Digital Outputs 30015 44 7 5 Triac Output Registers 45 7 5 1 State of Triac Outputs 40018 45 7 5 2 Default State of Triac Outputs 40143 45 7 5 3 Value of 1 4 Triac PWM Outputs 40121 40124 46 7 5 4 Default State of 1 4 Triac PWM Outputs 40145 40148 46 7 5 5 Configuration Mode of 1 4 Triac Outputs 40168 40171 46 7 5 6 Hand Control Status of the Triac Outputs 30015 46...

Page 5: ...ntrolli com DMP262en 1st Issue rev 8 05 2022 page 5 of 107 8 3 4 Analog Outputs 58 8 4 RS485 Configuration 59 8 5 IP Configuration 59 8 6 Device Management 60 8 7 Contact 61 9 List of Modbus Registers 62 10 List of Supported Temperature Sensors 73 ...

Page 6: ... most popular open communication protocols Modbus ASCII RTU TCP IP and BACnet MS TP IP which are selected using DIP switches Rotary switches are used to set the module address which facilitates and accelerates the process of commissioning the system Built in mini USB allows for the initial configuration of the unit without external power supply Built in Modbus Gateway TCP IP to Modbus ASCII RTU en...

Page 7: ...put mode added for 4U4O Ordinary IO Monostable Relay Bistable Relay Time Relay NO and NC ms Time Relay NO and NC in seconds Input Forwarding Heating Cooling with corresponding BACnet objects and Modbus registers Output for resetting to default added after input mode change in 4U4O and 4I4O Improved BACnet COV Increment now can have values with the resolution of 0 1 BACnet COV Increment access read...

Page 8: ...temperature sensors implemented in Celsius and Fahrenheit degrees New Modbus function 0x17 Read Write Multiple registers New Modbus function 0x2B to read the VENDOR_NAME MODEL_NAME FW_VERSION HOMEPAGE Supporting Modbus address 0xFF for communication with the gateway IP module Improved filtering on UI Fixed one record in sensor 30k6A1 table resistance 60713 to 80713 5 C 1 7 13 Oct 2020 Introduced a...

Page 9: ...ent phenomena like surges and bursts to devices They also isolate products from inductive phenomena from other transformers and loads Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges Avoid powering the product and its controlled monitored devices especially high power and inductive loads from a single power source...

Page 10: ...ose to the coil as possible 2 2 EN 60730 1 Power Supply Considerations Electrical safety in the building automation and control systems is essentially based on the use of extra low voltage which is strictly separated from the mains voltage This low voltage is either SELV or PELV according to EN 60730 1 Protection against electric shock is ensured by the following measures Limitation of voltage low...

Page 11: ... be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio ...

Page 12: ...O H 1 2 W 1 8 VA 4U4O H IP 2 2 W 3 3 VA 4U4A H 2 2 W 3 3 VA 4U4A H IP 3 2 W 4 8 VA 4O H 1 6 W 2 4 VA 4O H IP 2 6 W 3 9 VA 4TO H 1 0 W 1 5 VA 4TO H IP 2 0 W 3 0 VA MIX18 3 0 W 4 5 VA MIX18 IP 4 4 W 6 6 VA MIX38 5 0 W 7 5 VA MIX38 IP 7 4 W 11 1 VA Universal Inputs Temperature input Measurement with RTDS attached Accuracy 0 1 C For PT1000 and NI1000 sensors use 16 bit resolution Voltage input Voltage...

Page 13: ...A Measurement resolution 12 bit default or 16 bits Processing time 10 ms channel at 12 bits 140 ms channel at 16 bits Digital Inputs Type Dry contact Max input frequency 100 Hz saved in EEPROM memory Analog Outputs Voltage range 0 10 V DC Max load current 20 mA total 60 mA load current for all outputs for MIX18 MIX18 IP MIX38 MIX38 IP modules Resolution 12 bit Accuracy 0 5 Digital Outputs relays C...

Page 14: ...Continuous load per channel 0 5 A at 20 V AC up to max 250 V AC Peak load per channel 1 5 A at 20 V AC up to max 250 V AC 30s Gate Control Zero crossing turn ON Frequency Range 47 to 63 Hz Snubber Snubberless triac RS485 Interface RS485 Up to 128 devices Communication protocols Modbus RTU Modbus ASCII or BACnet set by switch Baud rate From 2400 to 115200 set by switch Address 0 to 99 set by switch...

Page 15: ...th 110 mm 4 331 in Length 88 mm 3 4646 in Height 62 mm 2 441 in MIX38 MIX38 IP Width 110 mm 4 331 in Length 160 mm 6 2993 in Height 62 mm 2 441 in MINI Series Width 110 mm 4 331 in Length 37 mm 1 457 in Height 62 mm 2 441 in Table 2 Technical specification 3 1 Summary Table for All Modules Module Type UI DI A O DO T O Modbus RTU ASCII Modbus TCP IP BACnet MS TP BACnet IP 4I4O H 4 4 4I4O H IP 4 4 4...

Page 16: ...4O H IP 4 4 8I 8 8I IP 8 8U 8 8U IP 8 4TO H 4 4TO H IP 4 MIX18 5 5 4 4 MIX18 IP 5 5 4 4 MIX38 8 12 6 12 MIX38 IP 8 12 6 12 RS485 slave Modbus gateway IP RS485 works only as a master on RS485 network RS485 master slave Modbus gateway IP RS485 works only as a master on RS485 network Table 3 Summary table for all modules ...

Page 17: ...ssue rev 8 05 2022 page 17 of 107 4 Hardware Specification 4 1 Dimensions 4 1 1 MINI Series Dimensions Figure 2 The MINI series dimensions 4 1 2 MIX18 Series Dimensions Figure 3 The MIX18 series dimensions 4 1 3 MIX38 Series Dimensions Figure 4 The MIX38 series dimensions ...

Page 18: ... 1st Issue rev 8 05 2022 page 18 of 107 4 2 Power Supply Connection Figure 5 AC power supply connection Figure 6 DC power supply connection 4 3 LED Indicators 4 3 1 MIX Series Front Panels MIX18 Top Panels Figure 7 The MIX18 top panel Figure 8 The MIX18 IP top panel ...

Page 19: ...ge 19 of 107 MIX38 Top Panels Figure 9 The MIX38 top panel Figure 10 The MIX38 IP top panel 4 3 2 MINI Series Front Panels MINI 8I and 8I IP Top Panels Figure 11 The 8I top panel Figure 12 The 8I IP top panel MINI 8U and 8U IP Top Panels Figure 13 The 8U top panel Figure 14 The 8U IP top panel ...

Page 20: ... MINI 4I4O H and 4I4O H IP Top Panels Figure 15 The 4I4O H top panel Figure 16 The 4I4O H IP top panel MINI 4U4O H and 4U4O H IP Top Panels Figure 17 The 4U4O H top panel Figure 18 The 4U4O H IP top panel MINI 4U4A H and 4U4A H IP Top Panels Figure 19 The 4U4A H top panel Figure 20 The 4U4A H IP top panel ...

Page 21: ... If the module receives sends a lot of messages the LED can be lit continuously LEDs indicating the status of the universal inputs U1 Un are lit when the resistance connected to the input is less than 5 kΩ dry contact input is active LEDs indicating the status of the digital inputs I1 In are lit when the input is active LEDs indicating the status of the analog outputs A1 An are lit when the output...

Page 22: ...e must be terminated at both ends with a resistor across the line adequate to its characteristic impedance Both ends must be terminated since the propagation is bidirectional In case of an RS485 twisted pair cable this termination is typically 120 Ω 4 5 Setting Module Address To determine the address on the Modbus network the module is equipped with two rotary switches S1 and S2 located on the top...

Page 23: ...the register Off 0 Off 0 On 1 76800 Off 0 On 1 Off 0 4800 Off 0 On 1 On 1 9600 On 1 Off 0 Off 0 19200 On 1 Off 0 On 1 38400 On 1 On 1 Off 0 57600 On 1 On 1 On 1 115200 Table 4 Baud rate selection 4 7 Protocol The protocol is selected with sections 4 and 5 of the S3 switch according to the table 4 5 Protocol Off 0 Off 0 Modbus RTU Off 0 On 1 Modbus ASCII On 1 Off 0 BACnet master On 1 On 1 BACnet sl...

Page 24: ...START 0 STATE OF THE ANALOG OUTPUTS AFTER START 0 UNIVERSAL INPUT CONFIGURATION 1 INPUT FILTER TIME CONSTANT 2 UNIVERSAL INPUT RESOLUTION 0 ANALOG OUTPUT CONFIGURATION 0 Only for IP modules USERNAME platform PASSWORD 1000 IP ADDRESS 192 168 1 123 MASK 255 255 255 0 GATEWAY 192 168 1 1 HTTP PORT 80 MODBUS TCP PORT 502 MODBUS TCP TIMEOUT 60s RS485 TIMEOUT 1000ms RS485 BIASING RESISTORS MINI only DIS...

Page 25: ... default configuration of all registers follow the steps below turn off the power supply set section 6 of the S3 switch to on turn on the power supply the power LED will start blinking switch section 6 of the S3 switch to off to restore the default settings To cancel the reset turn off the power and switch section 6 of the S3 switch to the off position ...

Page 26: ...their quantities differ between the modules types according to the table Module Type UI DI AO DO TO 4I4O H 4 4 4I4O H IP 4 4 4O H 4 NC NO 8A 4O H IP 4 NC NO 8A 4U4A H 4 4 4U4A H IP 4 4 4U4O H 4 4 4U4O H IP 4 4 8I 8 8I IP 8 8U 8 8U IP 8 4TO H 4 4TO H IP 4 MIX18 5 5 4 4 MIX18 IP 5 5 4 4 MIX38 8 12 6 12 MIX38 IP 8 12 6 12 Table 7 Inputs and outputs in MINI MIX modules 5 2 Universal Inputs Universal i...

Page 27: ... Ω resistance According to Ohm s law the current is directly proportional to the voltage and the resistance is the constant of proportionality I U R According to the Ohm s law equation for 20 mA current with 200 Ω resistance the output voltage is 4 V It means that the 4 V voltage measured on the universal input corresponds to 20 mA current The result is expressed in millivolts 5 2 1 Universal Inpu...

Page 28: ...niversal Input Resistance Connection Figure 29 A universal input resistance connection 5 2 4 Universal Input Dry Contact Connection Figure 30 A universal input dry contact connection 5 3 Digital Inputs Digital inputs operate as standard dry contact inputs and additionally as high speed pulse counters up to 100 Hz ...

Page 29: ...ct pulses up to 100 Hz The connection is identical as in case of the dry contact input 5 4 Analog Outputs Analog outputs provide a 0 10 V DC output with maximum load up to 20 mA They support three types of output signals voltage 0 10 V DC with maximum load up to 20 mA digital Pulse Width Modulation PWM 0 01 Hz 0 1 Hz 1 Hz 10 Hz 100 Hz 5 4 1 Analog Output Voltage Connection Figure 32 An analog outp...

Page 30: ...y Connection Figure 33 An analog output relay connection 5 4 3 Analog Output Actuator Connection Figure 34 An analog output actuator connection 5 5 Digital Outputs Digital outputs operate as relay outputs with maximum loads of resistive load 3 A at 230 V AC and 3 A at 30 V DC inductive load 75 VA for 230 V AC and 30 W for 24 V DC ...

Page 31: ...107 5 5 1 Digital Output Solenoid Valve Connection Figure 35 A digital output solenoid valve connection 5 5 2 Digital Output Resistive Load Connection Figure 36 A digital output resistive load connection 5 5 3 Digital Output Inductive Load Connection Figure 37 A digital output inductive load connection ...

Page 32: ...l www ismacontrolli com DMP262en 1st Issue rev 8 05 2022 page 32 of 107 5 6 Triac Outputs Triac outputs work as typical binary outputs or in Pulse Width Modulation PWM mode 0 01 Hz 0 1 Hz 1 Hz 10 Hz Figure 38 A triac output connection ...

Page 33: ...16 8I 9110 0x5B16 8I IP 8410 0x5416 8U 9410 0x5E16 8U IP 8310 0x5316 4I4O H 9310 0x5D16 4I4O H IP 8510 0x5516 4U4O H 9510 0x5F16 4U4O H IP 8610 0x5616 4U4A H 9610 0x6016 4U4A H IP 8210 0x5216 4O H 9210 0x5C16 4O H IP 8710 0x5716 4TO H 9710 0x6116 4TO H IP 5010 0x3216 MIX18 5110 0x3316 MIX38 5210 0x3416 MIX18 IP 5310 0x3516 MIX38 IP Table 8 Firmware version and module type WARNING Changing the conf...

Page 34: ...low This register reflects the state of S3 switch Baud rate Protocol Bit 0 Bit 1 Bit 2 Baud rate Bit 3 Bit 4 Protocol 0 0 0 User defined 0 0 Modbus RTU 0 0 1 76800 0 1 Modbus ASCII 0 1 0 4800 1 0 BACnet Master 0 1 1 9600 1 1 BACnet Slave 1 0 0 19200 1 0 1 38400 1 1 0 57600 1 1 1 115200 Table 9 Baud rate and protocol 6 4 Counter of Received Messages 30004 The 32 bit register with the number of vali...

Page 35: ...6 9 MAC Address 30131 This 32 bit register contains MAC address information of the module 6 10 Device Actions 40001 Setting the 40001 register according to the table below enables 1 of 4 available actions module reset reloading the settings setting to default and entering the bootloader Value Action 511 Reset 767 Reload settings 1023 Set to default 1279 Enter bootloader Table 10 Device actions 6 1...

Page 36: ...th the same RS485 bus and communication errors appear on the network Figure 39 Modbus frame 6 13 Data Bits 40138 The number of data bits transmitted in a single byte is determined according to the following table Value No of Data Bits 7 7 8 default 8 Table 12 Data bits 6 14 Parity Bit 40139 Every byte of data being transferred may have additional protection in the form of a parity bit added before...

Page 37: ...haracter required by the protocol Modbus RTU 6 16 Watchdog Time 40141 This 16 bit register specifies the time expressed in seconds to watchdog reset If the module does not receive any valid message within that time all digital and analog outputs will be set to the default state This feature is useful in case of an interruption in data transmission and if for security reasons output states must be ...

Page 38: ... following table No of Bit in Register No of Universal Input 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 Table 14 UI register operating DI for MIX38 and MIX38 IP 7 1 2 Universal Input Voltage Current Measure 1 8 30071 30073 30075 30077 30079 30087 30089 30091 These 16 bit registers contain the results of measuring the voltage for each input The result is expressed in millivolts The results of measuring the cu...

Page 39: ...ith the following table Register Value Description 0 Off resistance measurement only measuring the voltage dry contact off 1 default Temperature sensor 10K3A1 NTC B 3975K ºC 2 Temperature sensor 10K4A1 NTC B 3695K ºC 3 Temperature sensor 10K NTC B 3435K Carel ºC 4 Temperature sensor 20K6A1 NTC B 4262K ºC 5 Temperature sensor 2 2K3A1 NTC B 3975K ºC 6 Temperature sensor 3K3A1 NTC B 3975K ºC 7 Temper...

Page 40: ...UI shortcut or open loop the filter is reset and the UI value filtering is stopped 7 1 7 Resolution of the Universal Inputs 40167 This register is used to determine the bit resolution for each of the universal inputs Setting the bit to 0 sets the resolution of the converter to 12 bit Setting the bit to 1 sets the resolution of the converter to 16 bit Each input can be configured separately in acco...

Page 41: ... for each digital input The register with a lower number contains a lower byte of the counter and in the register with a higher number is stored in the higher byte of the counter In order to change the value of the register write any value called preset for pulse counting registers In special cases the counter can be reset by entering 0 Resetting the counter is also possible with the 40022 registe...

Page 42: ...s No of Bit in the Register No of Analog Output 0 1 1 2 2 3 3 4 4 5 5 6 Table 19 AO operating as DO for MIX38 and MIX38 IP 7 3 2 Value of 1 6 Analog Outputs 40121 40126 These 16 bit registers contain the value of analog output voltage in mV 7 3 3 Default State of the Analog Outputs Digital 40144 Setting a true value of a particular bit of this 16 bits register sets the maximum voltage 10 V on the ...

Page 43: ...0 V 1 PWM 1Hz 2 PWM 10Hz 3 PWM 100Hz 4 PWM 0 1Hz 5 PWM 0 01Hz Table 21 AO type settings 7 3 6 Hand Control Status of Analog Outputs 30015 This register is available only for modules with the manual control of analog outputs No of Bit in Register Description 0 1 Hand status of outputs 1 2 3 Hand status of outputs 2 4 5 Hand status of outputs 3 6 7 Hand status of outputs 4 Table 22 AO hand status bi...

Page 44: ...4 5 5 6 Table 24 State of DO for MIX38 and MIX38 IP 7 4 2 Default State of Digital Outputs 40143 This 16 bit register contains the default state of the digital output device after the start or watchdog reset Register bits correspond to the digital outputs according to the following table No of Bit in the Register No of Digital Output 0 1 1 2 2 3 3 4 4 5 5 6 Table 25 Default state of DO for MIX38 a...

Page 45: ...Outputs 40018 This 16 bit register contains the state of triac outputs in digital mode Setting a particular bit in the register activates the corresponding triac output according to the following table No of Bit in the Register No of Triac Output 0 1 1 2 2 3 3 4 Table 28 State of TO for 4TO H and 4TO H IP 7 5 2 Default State of Triac Outputs 40143 This 16 bit register contains the default state of...

Page 46: ...egisters contain the value of the duty that appears on the analog output expressed in percents after turning the power on or resetting the watchdog 7 5 5 Configuration Mode of 1 4 Triac Outputs 40168 40171 These 16 bit registers contain information about the mode of triac outputs according to the following table Register Value Description 0 default Digital Output 1 PWM 1Hz 2 PWM 10Hz 3 Not support...

Page 47: ...ding to the signals from the digital input The relation between inputs and outputs is shown in the table below and it cannot be changed Digital Input Digital Output DI1 DO1 DI2 DO2 DI3 DO3 DI4 DO4 Table 33 Built in application determining relations between inputs and outputs The digital inputs in 4I4O H 4I4O H IP 4U4O H 4U4O H IP modules can be set to work in different modes There are dedicated re...

Page 48: ...H and 4U4O H IP only 40187 DI3 DIFFERENTIAL 4U4O H and 4U4O H IP only 40188 DI4 OPERATION MODE 40189 DI4 TIME VALUE 40190 DI4 SETPOINT 4U4O H and 4U4O H IP only 40191 DI4 DIFFERENTIAL 4U4O H and 4U4O H IP only Table 34 List of registers dedicated for special application mode 7 6 2 Operation Mode Registers 40176 40180 40184 and 40188 This register contains information about the module working mode ...

Page 49: ...tate The action of a monostable relay can be executed remotely by changing the state of bit from false to true in the COMMAND register 40020 Outputs can by also overwritten with the DIGITAL OUTPUT register 40018 which allows remote control from BMS Bistable Relay In this mode only the rising edge of the digital input changes the output state The action of a bistable relay can be executed remotely ...

Page 50: ...ol from BMS Time Relay NC s In this mode if the output value is false the falling edge of the digital input sets the output to a true value Every rising edge on the digital input starts the counter from the beginning so that the output stays in true value for a time defined in the TIME VALUE register expressed in seconds counting from the last rising edge of the digital input The action of time re...

Page 51: ...al works in 2 states low and high If the control value is lower or equal with the difference between the Setpoint register and the Differential register the output is in the low state If the control value is higher or equal with the sum of the Setpoint register and Differential register the output is in the high state Output in the low state Control value Setpoint Differential Output in the high s...

Page 52: ...IR The action is executed by changing the state of the relevant bit changing from false to true All special application modes can be executed except for Input Forwarding Heating and Cooling modes No of Bit in the Register 40020 Command Input Number 0 1 1 2 2 3 3 4 Table 36 Command register for special application modes 7 6 5 Block Inputs Register 40021 The Block Inputs register is used to block th...

Page 53: ...oling modes 4U4O H and 4U4O H IP only as the setpoints for heating cooling control algorithm The default Setpoint value is 21 The register stores the setpoint multiplied by 10 7 6 7 Differential Registers 40179 40183 40187 40191 The Differential registers contain values which are used in heating cooling modes 4U4O H and 4U4O H IP only as the differential for heating cooling control algorithm Setpo...

Page 54: ...s 192 168 1 123 Please use the following default credentials Username platform Password 1000 by default Note The web server can be disabled by setting the HTTP port to 0 This option is available for firmware versions 6 5 and up 8 2 Device Page This page contains information about the device and its technical specification Basic Information section includes information about the type of the module ...

Page 55: ... for setting a different type of sensor Resolution read write resolution measurement 12 bit 16 bit for PT1000 and NI1000 sensors please use 16 bit resolution UI Flag read only the status of UI configured as dry contact input Disable Voltage Measurement read write disables voltage measuring resistance measurement only L P Filter Constant read write the value of the time constant for low pass filter...

Page 56: ...ns the following fields Block Input read write allows for blocking a particular input except for heating cooling modes Input Mode read write allows for selecting the Special Application Mode for a particular input Ordinary IO in default Command read write execution of the Special Application Modes except for input forwarding heating cooling modes Mode Time read write time base for time relay appli...

Page 57: ...ields State read only actual input state Reset Flag read write reset of pulses value leaving reset active will reset the value of the pulses Counter State read only the actual value of pulses saved in EEPROM Counter State To Set read write allows for setting the value of the counter 8 3 3 Digital Outputs This page allows for entering the configuration parameters and showing the actual value of the...

Page 58: ...guration parameters and showing the actual value of the analog outputs To open this page please navigate to the Local I O tab and choose the Analog Outputs from the submenu Figure 49 The 4U4A H IP Analog Outputs page The Analog Outputs table contains the following fields Value read write the actual value of the analog output in millivolts mV Type read write the analog output operating mode voltage...

Page 59: ...ASCII Stop Bits read write number of stop bits 1 or 2 Data Bits read write number of data bits transmitted in a single byte 7 or 8 Parity Bits read write transmission protection as a parity bit added before the stop bit bits RS485 Biasing Resistors activation of the biasing resistors for MINI IP modules only with a hardware version 2 0 MIX IP modules with hardware version 3 0 and up have a hardwar...

Page 60: ... port number default 502 Modbus Address read only the Modbus device address set by rotary switches Modbus TCP Communication Timeout read write the timeout value for TCP IP messages RS485 Timeout read write the timeout value for Modbus RTU ASCII messages Send Modbus Errors read only enable disable sending Modbus error messages BACnet ID read write BACnet ID set by rotary switches this value can be ...

Page 61: ...evice password in the New Device Password field enter the new device password again in the Confirm New Device Password field to confirm the password change please click the Submit button please log out and log in again using the new password 8 7 Contact This page displays information about Manufacturer s web page address and the e mail address to technical support Figure 53 Contact page view WARNI...

Page 62: ...at the unit start and change of transmission parameters 30008 7 0x07 COUNTER OF SENT FRAMES 32 bits Read only Default state is 0 Reset at the unit start and change of transmission parameters 30012 11 0x0B UP TIME Read only This 32 bit register contains module counting time in seconds from the last powering up or module reset 30015 14 0x0E STATUS OF MANUAL OPERATION Read only Status of manual opera...

Page 63: ...he corresponding counter 40023 22 0x16 COUNTER 1 LSB Read write Memory 32 bit counters for each of the digital input counting pulses 40024 23 0x17 COUNTER 1 MSB 40025 24 0x18 COUNTER 2 LSB Read write Memory 40026 25 0x19 COUNTER 2 MSB 40027 26 0x1A COUNTER 3 LSB Read write Memory 40028 27 0x1B COUNTER 3 MSB 40029 28 0x1C COUNTER 4 LSB Read write Memory 40030 29 0x1D COUNTER 4 MSB 40031 30 0x1E COU...

Page 64: ... 10 For a result divide the register value by 10 Selection of the type sensor is completed UNIVERSAL INPUT CONFIGURATION register from 40151 to 40158 for each input separately 30072 71 0x47 UIVERSAL INPUT TEMPERATURE 1 Read only 30073 72 0x48 UIVERSAL INPUT VOLTAGE 2 Read only 30074 73 0x49 UIVERSAL INPUT TEMPERATURE 2 Read only 30075 74 0x4A UIVERSAL INPUT VOLTAGE 3 Read only 30076 75 0x4B UIVERS...

Page 65: ...SAL INPUT VOLTAGE 4 Read only 30091 90 0x5A UIVERSAL INPUT VOLTAGE 5 Read only 30092 91 0x5B UIVERSAL INPUT VOLTAGE 6 Read only 30093 92 0x5C UIVERSAL INPUT VOLTAGE 7 Read only 30094 93 0x5D UIVERSAL INPUT VOLTAGE 8 Read only 30095 94 0x5E UIVERSAL INPUT TEMPERATURE 1 Read only 30096 95 0x5F UIVERSAL INPUT TEMPERATURE 2 Read only 30097 96 0x60 UIVERSAL INPUT TEMPERATURE 3 Read only 30098 97 0x61 U...

Page 66: ...SISTIVE INPUT 3 MSB Read only 30109 108 0x6C RESISTIVE INPUT 4 LSB Read only 30110 109 0x6D RESISTIVE INPUT 4 MSB Read only 30111 110 0x6E RESISTIVE INPUT 5 LSB Read only 30112 111 0x6F RESISTIVE INPUT 5 MSB Read only 30113 112 0x70 RESISTIVE INPUT 6 LSB Read only 30114 113 0x71 RESISTIVE INPUT 6 MSB Read only 30115 114 0x72 RESISTIVE INPUT 7 LSB Read only 30116 115 0x73 RESISTIVE INPUT 7 MSB Read...

Page 67: ... only 30127 126 0x7E HAND STATUS VALUE 3 Read only 30128 127 0x7F HAND STATUS VALUE 4 Read only 30130 129 0x81 HARDWARE_VERSIO N Read only The current hardware version of a device 30131 130 0x82 MAC_ADDRESS 32 bits Read only The MAC address of a device 40136 135 0x87 BAUD RATE Read write Memory Transmission speed The value is considered only when sections 1 2 and 3 of S3 switch are in the OFF posi...

Page 68: ...ITAL OUTPUTS Read write Memory State of digital outputs assigned at the start of the module and watchdog reset The default value is 0 40144 143 0x8F DEFAULT STATE OF ANALOG OUTPUTS DIGITAL Read write Memory State of analog outputs assigned at the start of the module and watchdog reset The default value is 0 40145 144 0x90 DEFAULT STATE OF ANALOG OUTPUT 1 Read write Memory In the registers is store...

Page 69: ...0K6A1 NTC 8 SIE1 9 TAC1 10 SAT1 16 Pt1000 17 Ni1000 128 Voltage measurement off 40152 151 0x97 UNIVERSAL INPUT CONFIGURATION 2 Read write Memory 40153 152 0x98 UNIVERSAL INPUT CONFIGURATION 3 Read write Memory 40154 153 0x99 UNIVERSAL INPUT CONFIGURATION 4 Read write Memory 40155 154 0x9A UNIVERSAL INPUT CONFIGURATION 5 Read write Memory 40156 155 0x9B UNIVERSAL INPUT CONFIGURATION 6 Read write Me...

Page 70: ...ERSAL INPUT 5 Read write Memory 40164 163 0xA3 FILTER TIME CONSTANT OF THE UNIVERSAL INPUT 6 Read write Memory 40165 164 0xA4 FILTER TIME CONSTANT OF THE UNIVERSAL INPUT 7 Read write Memory 40166 165 0xA5 FILTER TIME CONSTANT OF THE UNIVERSAL INPUT 8 Read write Memory 40167 166 0xA6 RESOLUTION OF THE UNIVERSAL INPUTS Read write Memory Resolution of the analog inputs When a bit is set the measureme...

Page 71: ...170 169 0xA9 ANALOG OUTPUT CONFIGURATION 3 Read write Memory 40171 170 0xAA ANALOG OUTPUT CONFIGURATION 4 Read write Memory 40172 171 0xAB ANALOG OUTPUT CONFIGURATION 5 Read write Memory 40173 172 0xAC ANALOG OUTPUT CONFIGURATION 6 Read write Memory 40176 175 0xAF DIGITAL INPUT 1 CONFIGURATION MODE Read write Memory Digital input configuration mode table Valu e OPERATING MODE 0 Ordinary IO def 1 M...

Page 72: ...mory 40180 179 0xB3 DIGITAL INPUT 2 CONFIGURATION MODE Read write Memory 40181 180 0xB4 DIGITAL INPUT 2 TIME VALUE Read write Memory 40182 181 0xB5 DIGITAL INPUT 2 SETPOINT Read write Memory 40183 182 0xB6 DIGITAL INPUT 2 DIFFERENTIAL Read write Memory 40184 183 0xB7 DIGITAL INPUT 3 CONFIGURATION MODE Read write Memory 40185 184 0XB8 DIGITAL INPUT 3 TIME VALUE Read write Memory 40186 185 0xB9 DIGI...

Page 73: ...el 20K6A1 2 2K3A1 3K3A1 30K6A1 SIE1 TAC1 SAT1 PT1000 NI1000 NI1000 21C ºC NI1000 LG ºC 10K Type II NTC 10K Type III NTC 20K NTC 3K NTC NI1000 32F ºF NI1000 70F ºF PT1000 ºF No 1 Sensor 10K3A1 β coefficient 3975K Manufacturers Aquatrol Cylon Honeywell Johnson Satchwell Seachange C Ω 50 667828 45 491749 40 335671 35 241840 30 176683 25 131251 20 96974 15 72895 10 55298 ...

Page 74: ...P262en 1st Issue rev 8 05 2022 page 74 of 107 No 1 5 42314 0 32650 5 25396 10 19904 15 15714 20 12494 25 10000 30 8056 35 6530 40 5325 45 4367 50 3601 55 2985 60 2487 65 2082 70 1751 75 1480 80 1256 85 1070 90 916 95 787 100 678 105 587 110 510 115 444 120 388 ...

Page 75: ...e 75 of 107 No 1 125 340 No 2 Sensor 10K4A1 β coefficient 3695K Manufacturers Andover Delta Controls Siebe York C Ω 50 441667 45 330749 40 239831 35 181532 30 135233 25 105081 20 78930 15 61030 10 47549 5 37316 0 29490 5 23462 10 18787 15 15136 20 12268 25 10000 30 8197 35 6754 40 5594 45 4656 ...

Page 76: ...Issue rev 8 05 2022 page 76 of 107 No 2 50 3893 55 3271 60 2760 65 2339 70 1990 75 1700 80 1458 85 1255 90 1084 95 939 100 817 105 713 110 624 115 547 120 482 125 426 No 3 Sensor 10K Carel β coefficient 3435K C Ω 50 329500 45 247700 40 188500 35 144100 30 111300 25 86430 ...

Page 77: ...62en 1st Issue rev 8 05 2022 page 77 of 107 No 3 20 67770 15 53410 10 42470 5 33900 0 27280 5 22050 10 17960 15 14690 20 12090 25 10000 30 8313 35 6940 40 5827 45 4912 50 4161 55 3536 60 3020 65 2588 70 2228 75 1924 80 1668 85 1451 90 1266 95 1108 100 973 105 857 ...

Page 78: ...e rev 8 05 2022 page 78 of 107 No 3 110 758 115 672 120 597 125 531 No 4 Sensor 20K6A1 β coefficient 4262K C Ω 40 806800 35 574400 30 413400 25 300400 20 220600 15 163480 10 122260 5 92220 0 70140 5 53780 10 41540 15 32340 20 25340 25 20000 30 15886 35 12698 40 10212 45 8260 ...

Page 79: ...v 8 05 2022 page 79 of 107 No 4 50 6718 55 5494 60 4518 65 3732 70 3098 75 2586 80 2166 85 1823 90 1541 95 1308 100 1114 105 953 110 818 115 704 120 609 125 528 115 444 120 388 125 340 No 5 Sensor 2 2K3A1 β coefficient 3975K Manufacturers Ambiflex Johnson C Ω 50 150395 45 112994 ...

Page 80: ...m DMP262en 1st Issue rev 8 05 2022 page 80 of 107 No 5 40 75593 35 57691 30 39789 25 30814 20 21839 15 16416 10 12453 5 9529 0 7353 5 5719 10 4482 15 3539 20 2814 25 2252 30 1814 35 1471 40 1199 45 983 50 810 55 672 60 560 65 468 70 394 75 333 80 282 85 241 ...

Page 81: ...ue rev 8 05 2022 page 81 of 107 No 5 90 206 95 177 100 152 105 132 110 114 115 100 120 88 125 77 No 6 Sensor 3K3A1 β coefficient 3975K Manufacturers Alerton C Ω 50 200348 45 150524 40 100701 35 76853 30 53005 25 41048 20 29092 15 21868 10 16589 5 12694 0 9795 5 7619 10 5971 ...

Page 82: ...macontrolli com DMP262en 1st Issue rev 8 05 2022 page 82 of 107 No 6 15 4714 20 3748 25 3000 30 2417 35 1959 40 1598 45 1310 50 1080 55 896 60 746 65 625 70 526 75 444 80 377 85 321 90 275 95 236 100 204 105 176 110 153 115 133 120 117 125 102 ...

Page 83: ...05 2022 page 83 of 107 No 7 Sensor 30K6A1 β coefficient 4262K Manufacturers Drayton C Ω 30 622911 25 477393 20 331876 15 245785 10 183697 5 138502 0 105305 5 80713 10 62347 15 48511 20 38019 25 30000 30 23828 35 19046 40 15317 45 12390 50 10079 55 8243 60 6777 65 5600 70 4650 75 3879 ...

Page 84: ...sue rev 8 05 2022 page 84 of 107 No 7 80 3251 85 2737 90 2313 95 1963 100 1672 105 1430 110 1228 115 1058 120 915 125 793 No 8 Sensor SIE1 Manufacturers Barber Colman Siebe C Ω 50 10732 45 10624 40 10517 35 10344 30 10172 25 9913 20 9654 15 9320 10 8933 5 8496 0 8044 5 7489 ...

Page 85: ...lli com DMP262en 1st Issue rev 8 05 2022 page 85 of 107 No 8 10 6938 15 6370 20 5798 25 5238 30 4696 35 4185 40 3707 45 3271 50 2875 55 2521 60 2206 65 1929 70 1685 75 1472 80 1287 85 1127 90 986 95 866 100 760 105 670 110 590 115 522 120 462 125 410 ...

Page 86: ...t Issue rev 8 05 2022 page 86 of 107 No 9 Sensor TAC1 β coefficient 3500K Manufacturers TAC C Ω 40 39024 35 29358 30 22284 25 17073 20 13192 15 10276 10 8068 5 6382 0 5085 5 4078 10 3294 15 2676 20 2188 25 1800 30 1488 35 1237 40 1034 45 869 50 733 55 622 60 529 65 453 ...

Page 87: ...62en 1st Issue rev 8 05 2022 page 87 of 107 No 9 70 389 75 335 80 290 85 252 90 220 95 192 100 169 105 149 110 131 115 116 120 103 125 92 No 10 Sensor SAT1 Manufacturers Satchwell C Ω 50 9719 45 9652 40 9584 35 9467 30 9349 25 9159 20 8968 15 8708 10 8396 5 8031 ...

Page 88: ... DMP262en 1st Issue rev 8 05 2022 page 88 of 107 No 10 0 7614 5 7150 10 6649 15 6121 20 5580 25 5039 30 4513 35 4012 40 3545 45 3117 50 2730 55 2386 60 2082 65 1816 70 1585 75 1385 80 1213 85 1064 90 937 95 828 100 734 105 654 110 585 115 525 120 474 125 429 ...

Page 89: ... No 11 Sensor PT1000 Manufacturers Honeywell Sauter Serck Siebe Cylon C Ω 50 803 1 40 842 7 30 882 2 20 921 6 10 960 9 0 1000 0 10 1039 0 20 1077 9 30 1116 7 40 1155 4 50 1194 0 60 1232 4 70 1270 8 80 1309 0 90 1347 1 100 1385 1 110 1422 9 120 1460 7 130 1498 3 140 1535 8 150 1573 3 160 1610 5 170 1647 7 ...

Page 90: ...107 No 11 180 1684 8 190 1721 7 200 1758 6 210 1795 3 220 1831 9 230 1868 4 240 1904 7 250 1941 0 260 1977 1 270 2013 1 280 2049 0 290 2084 8 300 2120 5 310 2156 1 320 2191 5 330 2226 8 340 2262 1 350 2297 2 360 2332 1 370 2367 0 380 2401 8 390 2436 4 400 2470 9 No 12 Sensor NI1000 Manufacturers Sauter ...

Page 91: ...2 page 91 of 107 No 12 C Ω 50 742 6 40 791 3 30 841 5 20 893 0 10 945 8 0 1000 0 10 1055 5 20 1112 4 30 1170 6 40 1230 1 50 1291 1 60 1353 4 70 1417 2 80 1482 5 90 1549 4 100 1617 8 110 1687 9 120 1759 8 130 1833 4 140 1909 0 150 1986 6 No 13 Sensor NI1000 21C ºC Manufacturers Distech C Ω ...

Page 92: ...05 2022 page 92 of 107 No 13 40 699 3 30 745 5 20 792 8 10 841 2 0 891 0 10 942 0 20 994 3 30 1047 8 40 1102 6 50 1158 5 60 1215 8 70 1274 3 80 1334 4 90 1407 8 100 1473 1 110 1524 0 No 14 Sensor NI1000 LG ºC Manufacturers LG C Ω 50 790 9 40 830 8 30 871 7 20 913 5 10 956 2 0 1000 0 ...

Page 93: ... 107 No 14 10 1044 8 20 1090 7 30 1137 6 40 1185 7 50 1235 0 60 1285 4 70 1337 1 80 1390 1 90 1444 4 100 1500 0 110 1557 0 120 1615 4 130 1675 2 140 1736 5 150 1799 3 No 15 Sensor 10K Type II NTC β coefficient 3975K Manufacturers Alerton F Ω 40 336095 35 279921 30 233942 25 196184 20 165062 15 139324 ...

Page 94: ... Issue rev 8 05 2022 page 94 of 107 No 15 10 117968 5 100192 0 85346 5 72910 10 62464 15 53660 20 46222 25 39919 30 34563 35 30001 40 26104 45 22767 50 19903 55 17439 60 15313 65 13476 70 11884 75 10501 80 9298 85 8249 90 7333 95 6530 100 5826 105 5208 110 4663 115 4182 ...

Page 95: ... 1st Issue rev 8 05 2022 page 95 of 107 No 15 120 3757 125 3381 130 3047 135 2751 140 2487 145 2252 150 2042 155 1855 160 1687 165 1536 170 1401 175 1279 180 1169 185 1070 190 981 195 901 200 827 205 761 210 701 215 646 220 597 225 551 230 510 235 472 240 438 245 406 ...

Page 96: ...2 page 96 of 107 No 15 250 377 No 16 Sensor 10K Type III NTC β coefficient 3695K Manufacturers Andowver F Ω 40 239831 35 203801 30 173631 25 148378 20 127139 15 109226 10 94078 5 81235 0 70317 5 61012 10 53063 15 46255 20 40411 25 35382 30 31046 35 27298 40 24051 45 21234 50 18782 55 16646 ...

Page 97: ... Issue rev 8 05 2022 page 97 of 107 No 16 60 14780 65 13148 70 11717 75 10459 80 9353 85 8378 90 7517 95 6755 100 6080 105 5481 110 4948 115 4474 120 4051 125 3673 130 3335 135 3032 140 2761 145 2517 150 2297 155 2100 160 1921 165 1760 170 1615 175 1453 180 1363 185 1255 ...

Page 98: ... 05 2022 page 98 of 107 No 16 190 1156 195 1066 200 985 205 910 210 842 215 780 220 723 225 671 230 623 235 580 240 540 245 503 250 469 No 17 Sensor 20K NTC β coefficient 4262K Manufacturers Honeywell F Ω 40 817605 35 674624 30 558679 25 464299 20 387186 15 323956 10 271927 5 228972 ...

Page 99: ...ue rev 8 05 2022 page 99 of 107 No 17 0 193390 5 163823 10 139177 15 118571 20 101293 25 86764 30 74511 35 64152 40 55369 45 47904 50 41543 55 36109 60 31457 65 27464 70 24029 75 21068 80 18509 85 16294 90 14372 95 12700 100 11244 105 9974 110 8862 115 7888 120 7034 125 6282 ...

Page 100: ...n 1st Issue rev 8 05 2022 page 100 of 107 No 17 130 5620 135 5036 140 4519 145 4062 150 3657 155 3297 160 2976 165 2691 170 2436 175 2209 180 2005 185 1823 190 1659 195 1512 200 1379 205 1260 210 1153 215 1055 220 967 225 888 230 816 235 750 240 691 245 637 250 588 ...

Page 101: ...sue rev 8 05 2022 page 101 of 107 No 18 Sensor 3K NTC β coefficient 3975K F Ω 40 100618 35 83827 30 70079 25 58783 20 49468 15 41763 10 35367 5 30042 0 25593 5 21866 10 18735 15 16096 20 13865 25 11975 30 10369 35 9000 40 7831 45 6830 50 5971 55 5232 60 4594 65 4043 70 3565 ...

Page 102: ...2en 1st Issue rev 8 05 2022 page 102 of 107 No 18 75 3150 80 2789 85 2475 90 2200 95 1959 100 1748 105 1562 110 1399 115 1254 120 1127 125 1014 130 914 135 825 140 746 145 676 150 613 155 556 160 506 165 461 170 420 175 384 180 351 185 321 190 294 195 270 200 248 ...

Page 103: ...ev 8 05 2022 page 103 of 107 No 18 205 228 210 210 215 194 220 179 225 165 230 153 235 142 240 131 245 122 250 113 No 19 Sensor NI1000 32F ºF Manufacturers Distech F Ω 40 791 3 30 818 9 20 847 1 10 875 6 0 904 6 10 933 9 20 963 7 30 993 9 40 1024 5 50 1055 5 60 1086 9 70 1118 7 ...

Page 104: ...4 of 107 No 19 80 1151 0 90 1183 6 100 1216 7 110 1250 2 120 1284 1 130 1318 5 140 1353 4 150 1388 5 160 1424 2 170 1460 3 180 1497 0 190 1534 1 200 1571 7 210 1609 8 220 1648 4 230 1687 9 240 1727 3 250 1767 6 No 20 Sensor NI1000 70F ºF Manufacturers Distech F Ω 40 699 3 30 724 8 20 750 7 10 776 9 ...

Page 105: ... page 105 of 107 No 20 0 803 4 10 830 3 20 857 7 30 885 4 40 913 5 50 942 0 60 970 9 70 1000 2 80 1029 9 90 1059 9 100 1090 3 110 1121 1 120 1152 2 130 1183 8 140 1215 8 150 1248 1 160 1280 9 170 1314 2 180 1347 9 190 1382 0 200 1417 0 210 1452 0 220 1487 0 230 1524 0 240 1560 0 250 1597 0 ...

Page 106: ...age 106 of 107 No 21 Sensor PT1000 ºF Manufacturers Distech F Ω 40 842 7 30 864 7 20 886 6 10 908 5 0 930 3 10 952 2 20 973 9 30 995 7 40 1017 4 50 1039 0 60 1060 7 70 1082 2 80 1103 8 90 1125 3 100 1146 8 110 1168 3 120 1189 7 130 1211 1 140 1232 4 150 1253 7 160 1275 0 170 1296 2 180 1317 4 ...

Page 107: ...iSMA B MINI MIX Modbus User Manual www ismacontrolli com DMP262en 1st Issue rev 8 05 2022 page 107 of 107 No 21 190 1338 6 200 1359 7 210 1380 8 220 1401 8 230 1422 9 240 1443 8 250 1464 8 ...