background image

 

 

 

 

 

 

 
 
 
 

VECTOR INVERTER 

 

INSTRUCTION MANUAL 

Summary of Contents for HI RUN n 700

Page 1: ...VECTOR INVERTER INSTRUCTION MANUAL ...

Page 2: ... OF ELECTRICAL SHOCK z SHORT CIRCUIT RATING THIS INVERTER IS NOT SUITABLE FOR USE ON A CIRCUIT CAPABLE OF DELIVERING MORE THAN 5 000RMS SYMMETRICAL AMPERES 480 VOLTS AND 240 VOLTS MAXIMUM z OVER SPEED PROTECTION THIS INVERTER DOES NOT PROVIDE OVER SPEED PROTECTION z OVER LOAD PROTECTION THIS INVERTER PROVIDES MOTOR OVER LOAD PROTECTION z OVER LOAD PROTECTION LEVEL IS 50 200 OF FULL LOAD CURRENT TH...

Page 3: ...HICH IF NOT AVOIDED CAN RESULT IN SERIOUS INJURY OR DEATH CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED CAN RESULT IN MINOR TO MODERATE INJURY OR SERIOUS DAMAGE OF PRODUCT THE MATTERS DESCRIBED UNDER CAUTION MAY IF NOT AVOIDED LEAD TO SERIOUS RESULTS DEPENDING ON THE SITUATION IMPORTANT MATTERS ARE DESCRIBED IN CAUTION AS WELL AS WARNING SO BE SURE TO OBSERVE THEM NOTE N...

Page 4: ...F ELECTRIC SHOCK ENSURE PROPER EARTH CONNECTION BEFORE OPENING THE COVER WAIT AT LEAST 5 MINUTES UNTIL DC BUS CAPACITORS ARE DISCHARGE CAUTION HEAVY OBJECT TO AVOID MUSCLE STRAIN OR BACK INJURY USE LIFTING AIDS AND PROPER LIFTING TECHNIQUES WHEN REMOVING OR REPLACING CAUTION THESE INSTRUCTIONS SHOULD BE READ AND CLEARLY UNDERSTOOD BEFORE WORKING ON N700 SERIES EQUIPMENT CAUTION PROPER GROUNDS DISC...

Page 5: ...D WIRE SCREENED CABLE IS REQUIRED FOR MOTOR WIRING AND THE LENGTH MUST BE LESS THAN 20 METERS B THE CARRIER FREQUENCY SETTING MUST BE LESS THAN 5KHZ TO SATISFY EMC REQUIREMENTS C SEPARATE THE MAIN CIRCUIT FROM THE SIGNAL PROCESS CIRCUIT WIRING D IN CASE OF REMOTE OPERATING WITH CONNECTOR CABLE THE INVERTER DOES NOT CONFORM TO EMC 4 ENVIRONMENTAL CONDITIONS WHEN USING A FILTER FOLLOW THESE GUIDELIN...

Page 6: ... A CABINET OR BY ADDING COVERS AS FOLLOWS 1 CABINET AND COVER THE INVERTER MUST BE INSTALLED INTO A CABINET WHICH HAS THE PROTECTION DEGREE OF TYPE IP2X IN ADDITION THE TOP SURFACES OF CABINET ARE EASILY ACCESSIBLE SHALL MEET AT LEAST THE REQUIREMENTS OF THE PROTECTIVE TYPE IP4X OR WHICH IS CONSTRUCTED TO PREVENT SMALL OBJECTS FROM ENTERING INVERTER IP4X cabinet IP20 with louver Air Air FIG 1 INVE...

Page 7: ...USER 1 WIRING WARNINGS FOR ELECTRICAL PRACTICES AND WIRE SPECIFICATIONS WARNING USE COPPER CONDUCTOR ONLY 75 WITH A TORQUE RATING WARNING SUITABLE FOR USE ON A CIRCUIT CAPABLE OR DELIVERING NOT MORE THAN 5 000 RMS SYMMETRICAL AMPERES 240V MAXIMUM WARNING SUITABLE FOR USE ON A CIRCUIT CAPABLE OR DELIVERING NOT MORE THAN 5 000 RMS SYMMETRICAL AMPERES 480V MAXIMUM ...

Page 8: ...LB 53 06 IN LB 132 7 IN LB 132 7 IN LB 132 7 IN LB 265 5 IN LB 10 AWG 8 AWG 6 AWG 6 6 AWG 6 6 AWG 2 AWG 2 0 AWG 3 0 AWG 4 0 AWG 300 kcmil RECOMMENDED RING TERMINAL SIZE UL LISTED FOR 055LF 110LF MAXIMUM WIDE 12 mm MODEL NAME TIGHTENING TORQUE IN LB WIRE RANGE N700 055HF N700 075HF N700 110HF N700 150HF N700 185HF N700 220HF N700 300HF N700 370HF N700 450HF N700 550HF 26 5 IN LB 26 5 IN LB 26 5 IN ...

Page 9: ...TED BCP BRANCH CIRCUIT PROTECTION TYPE FUSE AS SHOWN IN THE TABLE BELOW MODEL NAME CIRCUIT BREAKER A FUSE A N700 055LF N700 075LF N700 110LF N700 150LF N700 185LF N700 220LF N700 300LF N700 370LF N700 450LF N700 550LF 30 40 60 80 100 125 150 200 250 300 30 40 60 80 100 125 150 200 250 300 MODEL NAME CIRCUIT BREAKER A FUSE A N700 055HF N700 075HF N700 110HF N700 150HF N700 185HF N700 220HF N700 300...

Page 10: ... FIELD WIRING CONNECTION MUST BE MADE BY AN UL LISTED AND CSA CERTIFIED CLOSED LOOP TERMINAL CONNECTOR SIZED FOR THE WIRE GAUGE INVOLVED CONNECTOR MUST BE FIXED USING THE CRIMP TOOL SPECIFIED BY THE CONNECTOR MANUFACTURER OR EQUIVALENT WORDING INCLUDED IN THE MANUAL ...

Page 11: ... POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED CAN RESULT IN SERIOUS INJURY OR DEATH INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED CAN RESULT IN MINOR TO MODERATE INJURY OR SERIOUS DAMAGE TO THE PRODUCT THE SITUATION DESCRIBED IN THE CAUTION MAY IF NOT AVOIDED LEAD TO SERIOUS RESULTS IMPORTANT SAFETY MEASURES ARE DESCRIBED IN CAUTION AS WELL AS DANGER SO BE SURE TO OBSERV...

Page 12: ...er in a place which can bear the weight according to the specifications in the text Chapter 6 Specifications Otherwise it may fall and there is a danger of injury z Be sure to install the unit on a perpendicular wall which is not subject to vibration Otherwise the inverter may fall and cause injury to personnel z Be sure not to install and operate an inverter which is damaged or has parts which ar...

Page 13: ...the input Otherwise there is a danger of fire z Be sure not to connect AC power supply to the output terminals U V W Otherwise there is a danger of injury and or fire and or damage to unit z Be sure not to connect a resistor to the DC terminals PD P and N directly Otherwise there is a danger of fire and or damage to unit z Be sure to install an earth leakage breaker or the fuse s which is are the ...

Page 14: ...ment restarts Otherwise there is a danger of injury z Be sure not to select retry mode for equipment running up and down or traversing because there is output free running mode in term of retry Otherwise there is a danger of injury and or machine breakage z Even if the power supply is cut for a short period of time the inverter may restart operation after the power supply is restored if the operat...

Page 15: ...g the test run Was the direction of the motor correct Did the inverter trip for on acceleration or deceleration Were the RPM and frequency motor correct Were there any abnormal motor vibrations or noises Otherwise there is a danger of machine breakage 4 Maintenance inspection and part replacement z After turning off the input power supply do not perform the maintenance and inspection for at least ...

Page 16: ...1 Operation setting and a frequency setting by the terminal control 21 3 1 2 Operation setting and frequency setting with the digital operator 21 3 1 3 Operation setting and frequency setting from both the digital operator and the terminal operator 21 3 2 Test Run 22 3 2 1 To input the operation setting and the frequency setting from the terminal control 22 3 2 2 Operation setting and the frequenc...

Page 17: ...5 12 Frequency conversion monitor d012 44 5 13 Accumulated time monitor during RUN d013 44 5 14 Accumulated time monitor during RUN d014 44 5 15 Power ON time monitor d015 44 5 16 Power ON time monitor d016 44 5 17 IGBT Power Module Temperature monitor d017 44 5 18 Trip count d018 44 5 19 Trip monitor 1 to 6 d019 d024 44 6 Explanation of F group 46 6 1 Output frequency setting F001 F201 46 6 2 Bas...

Page 18: ... 1 Operation limit b001 69 8 2 Starting method setting function b003 b004 69 8 3 Operation command selection b005 b007 70 8 4 AVR selection b008 71 8 5 Frequency conversion factor b009 71 8 6 Carrier frequency b010 71 8 7 Cooling fan operating selection b011 72 8 8 Ground Fault selection b013 72 8 9 Initialization selection b014 72 8 10 Country code for initialization b015 73 8 11 Automatic restar...

Page 19: ...order setting 104 9 3 1 O L terminal setting 104 9 3 2 OI L terminal setting 105 9 3 3 O2 L terminal setting 106 9 4 Other function 107 9 4 1 Analog input filter 107 10 Explanation of O group 108 10 1 Intelligent output terminal setting 108 10 1 1 Intelligent output terminal arrangement 108 10 1 2 Wiring intelligent output terminals 109 10 1 3 Output terminal function selection o001 o004 o031 o032...

Page 20: ...tor control method 134 12 2 Autotuning 135 12 2 1 Off line autotuning 135 12 2 2 ON LINE autotuning 138 12 3 Sensorless vector control SLV 138 12 4 Sensored vector control V2 0Hz Sensored vector control 0Hz V2 139 13 Communication function 140 13 1 Communication function 140 13 2 Communication protocol 142 13 2 1 Inverter read frame 142 13 2 2 Request frame for setting parameter 143 14 Protection ...

Page 21: ...ating Instructions and Parts Manual vi 16 Specification 155 16 1 Standard specification list 155 16 1 1 200V class 155 16 1 2 400V Class 155 16 1 3 Common specification for 200V 400V class 156 16 2 Dimension 158 ...

Page 22: ...the unit is damaged please contact HYUNDAI 1 Make sure that the package contains one operation manual for the inverter 2 Make sure that there was no damage broken parts in the body during transportation of the unit 3 Make sure that the product is the one you ordered by checking the label specification Fig 1 1 Outlook of N700 inverter Fig 1 2 Contents of specification label Inverter Model Maximum a...

Page 23: ...nty period of the unit is one year after the purchase date However the warranty will be void if the fault is due to Incorrect use as directed in this manual or attempted repair by unauthorized personnel Any damage sustained other than from transportation Which should be reported immediately Using the unit beyond the limits of the specifications Natural Disasters Earthquakes Lightning etc 2 The war...

Page 24: ... 1 3 Appearance from the front Fig 1 4 Front cover removed Note When you use cables for remote operation please remove the connector Bottom cover Digital Operator FAN cover Mounting plate Bolting hole Main circuit terminals Specification label Control circuit terminals Wiring blind cover ...

Page 25: ...nstall the inverter in a place which can bear the weight according to the specifications in the text Chapter 17 Specification Otherwise it may fall and result in possible injury z Be sure to install the unit on a perpendicular wall which is not subject to vibration Otherwise the inverter may fall and cause injury to personnel z Be sure not to install and operate an inverter which is damaged or par...

Page 26: ...e The ambient temperature surrounding the inverter should not exceed the allowable temperature range 14 to 122 F 10 to 50 The temperature should be measured in the air gap surrounding the inverter shown in the diagram above If the temperature exceeds the allowable temperature component life will become shortened especially in the case of the Capacitors 4 Operating Environment Humidity The humidity...

Page 27: ...reases and the temperature surrounding the inverter will rise So please make sure that the temperature around is within the limit of the allowable range Fig 2 3 Ventilation within an Enclosure 8 External cooling of inverter It is possible to install the inverter so that the heatsink is outside of the back of the enclosure This method has two advantages the cooling of the inverter is greatly increa...

Page 28: ...5550 6650 100 of rated output efficiency 95 4 96 3 96 1 96 0 96 0 96 4 Table 2 1 Approximate loss for each capacity 2 1 2 Blind cover of wiring parts 1 Cable entry through Rubber Bushings The wiring should be done after making a cut in the rubber bushings with nippers or cutters If you want to use the conduit after taking out the rubber bushings connect the conduit Fig 2 4 Cable entry through Rubb...

Page 29: ...not to power a three phase only inverter with single phase power Otherwise there is a danger of fire z Be sure not to connect AC power supply to the output terminals U V W Otherwise there is a danger of injury and or fire and or damage to unit z Be sure not to connect a resistor to the DC terminals PD P and N directly Otherwise there is a danger of fire and or damage to unit z Be sure to set a ear...

Page 30: ...N700 Operating Instructions and Parts Manual 2 Installation and Wiring 9 2 2 1 Terminal Connection Diagram sink type Fig 2 5 Terminal Connection Diagram sink type ...

Page 31: ...10V the maximum frequency goes with 10V Input Impedance 14 4k ohm Allowable maximum voltage DC 3 12V O2 Frequency command support voltage When inputting DC 0 10V this signal is added to frequency command of 0 or 0I terminal Input Impedance 13k ohm Allowable maximum voltage DC 0 12V Frequency setting OI Frequency command Terminal current When inputting 4 20mA 20mA is maximum frequency When only AT ...

Page 32: ...ge The voltage between input and PLC 27V 11 FA1 12 RUN 13 OL 14 OTQ Output intelligent Open collect output 4 terminal RUN Signal during run FA1 Frequency arrival type 1 signal FA2 Frequency arrival type 2 signal OL Overload advance notice signal OD Output deviation for PID control ALM Alarm signal FA3 Arrival signal for only setting frequency OTQ Over torque IP Instantaneous stop signal UV Under v...

Page 33: ...it is selected open phase protection is valid R phase S phase or T phase open phase condition It becomes single phase operation condition Trip operation such as a deficiency voltage or over current may occur z Don t use it under open phase condition A converter module may be damaged as a result of the following conditions Use caution when an unbalance of the power supply voltage is more than 3 Pow...

Page 34: ...l braking resistor to these terminals z When installing an external braking resistor make sure that the resistance is correctly rated to limit the current drawn through the BRD Regenerative breaking unit connection terminals P N z The Inverters rated more than 30 don t contain a BRD circuit If regenerative braking is required an external BRD circuit Option is required along with the resistor Optio...

Page 35: ...er are in the following pictures Wiring of terminals Corresponding type N700 055LF 075LF 110LF 055HF 075HF 110HF Screw size M5 N700 150LF 185LF 150HF 185HF 220HF Screw size M6 N700 220LF Screw size M8 N700 300LF 370LF 450LF 300HF 370HF 450HF 550HF 750HF 900HF Screw size M8 N700 550LF N700 1100HF 1320HF Screw size M10 Table 2 4 Wiring of main circuit terminals ...

Page 36: ...art reduces noise 3 Noise filter for Inverter This part reduces common noise generated between the power supply and the ground as well as normal noise Put it in the primary side of inverter 4 Input radio noise filter capacitor filter This part reduces radiation noise emitted from wire at the input 5 Direct reactor This part control harmonic from inverter 6 Breaking resistor Regenerative breaking u...

Page 37: ...0LF More than 35X2 M8 6 0 HBS400N 225A HiMC220 200V class 55 75 N700 550LF More than 70X2 M10 10 0 HBS400N 300A HiMC220 5 5 7 5 N700 055HF More than 4이상 4 M5 3 0 HBS30N 30A HiMC18 7 5 10 N700 075HF More than 4 4 M5 3 0 HBS30N 30A HiMC18 11 15 N700 110HF More than 6 6 M5 3 0 HBS60N 50A HiMC32 15 20 N700 150HF More than 10 10 M6 4 5 HBS100N 50A HiMC40 18 5 25 N700 185HF More than 16 10 M6 4 5 HBS100...

Page 38: ...h the CM1 and L terminals are insulated to both the common terminal of the input and output signals Do not short or connect to ground these common terminals Use twisted screened cable for the input and output wires of the control circuit terminals Connect the screened cable to the common terminal Limit the connection wires to 65 feet Separate the control circuit wiring from the main power and rela...

Page 39: ...nd separate them from the rest Limit the connection wires to 65 feet 3 Change of input logic type The logic type of intelligent input terminals is on the following list Factory Default N700 Inverter 5 5 132 Sink TYPE The input logic type can be changed by changing the Short bar connection of control terminal Sink type Between P24 and PLC on the control terminal Source type Between PLC and CM1 on t...

Page 40: ...2 4 Digital operator wiring For operating this inverter it can use digital operator OPE N7 For remote operation remove the digital operator from the inverter and use the optional connector cable ICS 1 3 2feet or ICS 3 10 feet to connect the digital operator cable When using connector cable be sure to use less than 10 feet long Otherwise there is a danger of malfunction ...

Page 41: ...erwise there is a danger of injury z Be sure not to select retry mode for up and down equipment or traveling equipment because there is an output free running mode in term of retry Otherwise there is a danger of injury and or machine breakage z Even if the power supply is cut for a short period of time the inverter may restart operation after the power supply is restored if the operation command i...

Page 42: ... which controls the inverter by connecting the control circuit terminals with signals from the outside the frequency setting the starting switch etc 2 The operation is started when the operation setting FW REV is turned ON while the input power is turned ON Note The methods of setting the frequency with the terminal are the voltage setting and the current setting Both are selective The control cir...

Page 43: ... Code values are shown Set 1 Terminal with key press the key once to set the frequency setting for the operator Indication code turns back to F010 4 Set terminal with the operation setting selection Set F011 as indication code press the key once Set 1 terminal with the key press the key once to set the frequency setting for the operator Indication code turns back to F011 5 Set Monitor mode When mo...

Page 44: ... operator with the operation setting selection Set F011 as the indication code press the key once Set 2 OPE with key press the key once to set the frequency setting for the operator Indication code turns back to F011 5 Set the output frequency Set F001 as indication code by pressing the key once Code values are shown Set to the desired output frequency with the key press the key once to store it 6...

Page 45: ... sure that the direction of the motor is correct Otherwise there is danger of injury or equipment damage z Make sure there is no abnormal noise and vibration Otherwise this is a danger of injury or equipment damage Make sure that the inverter does not trip during the acceleration and deceleration and check that the revolutions per minute and the frequency reading are correct When overcurrent tripp...

Page 46: ...is on RUN LED Running lamp RUN ON when the inverter output is on and the motor is developing torque and OFF when the inverter output is off STOP Mode PRG LED Programming lamp PRG This LED is ON when the inverter is ready for parameter editing Program mode It is normally OFF when the parameter display is monitoring data Monitor mode Monitor indicator Monitor lamp Hz A V Lamp that marks monitor depa...

Page 47: ...le the basic setting mode or the extension setting mode is displayed the display will be different from the above when the power is restored It is possible to shift to other extension function modes monitor modes and basic modes in A b I o C H P state Key explanation Function key This key is used to navigate through the lists of parameters and functions for setting and monitoring parameter values ...

Page 48: ...tely to move up or down the lists of parameters and functions shown in the display and increase decrease values Run key RUN Press this key to run the motor Parameter F009 determines the rotor direction of the motor FWD or REV Stop key STOP Press this key to stop the motor when it is running This key will also reset an alarm that has tripped keypad navigational map 2 Setting method of function and ...

Page 49: ...ligent output terminal monitor Display the state of the intelligent output terminals 43 d012 Frequency conversion monitor 0 00 99 99 100 0 400 0 d001xb009 0 00 44 d013 Accumulated time monitor during RUN Hr 0 9999 1000 6553 Hr 0 44 d014 Accumulated time monitor during RUN Min 0 59 Min 0 44 d015 Power on time monitor Hr 0 9999 1000 6553 Hr 0 44 d016 Power on time monitor Min 0 59 Min 0 44 Table 4 1...

Page 50: ...0 3600 sec 30 0 49 F008 Decelerating time setting 0 1 999 9 1000 3600 sec 30 0 49 F208 Decelerating time setting 2nd motor 0 1 999 9 1000 3600 sec 30 0 49 F009 Driving direction selection 0 FWD 1 REV 0 ⅹ 50 F010 Frequency source selection 0 OPE VOL 1 TERMINAL 2 OPE KEYPAD 3 COM 4 OPT1 5 OPT2 0 ⅹ 50 F011 RUN command source selection 1 TERMINAL 2 OPE 3 COM 4 OPT1 5 OPT2 2 ⅹ 51 F012 Motor control met...

Page 51: ...ttern 2nd motor 0 Line 1 S_Curve 2 U_Curve 3 RU_Curve 0 ⅹ 56 A002 Deceleration pattern 0 Line 1 S_Curve 2 U_Curve 3 RU_Curve 0 ⅹ 56 A202 Deceleration pattern 2nd motor 0 Line 1 S_Curve 2 U_Curve 3 RU_Curve 0 ⅹ 56 A003 Acceleration curvature 1 10 8 x 57 A004 Deceleration curvature 1 10 8 x 57 A005 Acceleration stop frequency 0 00 Max Frequency Hz 0 00 57 A006 Acceleration stop time 0 60 00 sec 0 00...

Page 52: ... frequency 4 0 00 99 99 100 0 400 0 Hz Start frequency Max frequency 0 00 60 A032 Multi speed frequency 5 0 00 99 99 100 0 400 0 Hz Start frequency Max frequency 0 00 60 A033 Multi speed frequency 6 0 00 99 99 100 0 400 0 Hz Start frequency Max frequency 0 00 60 A034 Multi speed frequency 7 0 00 99 99 100 0 400 0 Hz Start frequency Max frequency 0 00 60 A035 Multi speed frequency 8 0 00 99 99 100 ...

Page 53: ...1 999 9 1000 3600 sec 30 0 61 A053 Multi speed 6 acceleration time 0 1 999 9 1000 3600 sec 30 0 61 A054 Multi speed 6 deceleration time 0 1 999 9 1000 3600 sec 30 0 61 A055 Multi speed 7 acceleration time 0 1 999 9 1000 3600 sec 30 0 61 A056 Multi speed 7 deceleration time 0 1 999 9 1000 3600 sec 30 0 61 A059 Free V F frequency 1 0 99 99 100 0 400 0 Hz 0 00 ⅹ 61 A060 Free V F voltage 1 0 0 999 9 V...

Page 54: ...A081 DC braking selection 0 Disable 1 Enable 0 64 A082 DC braking frequency 0 00 60 00 Hz 0 50 64 A083 DC braking wait time 0 0 5 0 sec 0 0 64 A084 DC braking force 0 100 0 64 A085 DC braking time 0 00 60 00 sec 0 00 64 A086 DC braking edge level selection 0 Edge 1 Level 1 64 A087 DC braking force for starting 0 100 0 64 A088 DC braking time for starting 0 00 60 00 sec 0 00 64 A089 Acceleration De...

Page 55: ...re time 0 3 1 0 sec 1 0 73 b018 Retry wait time 0 3 100 0 sec 1 0 73 b019 Instantaneous power failure under voltage trip during stop 0 Invalid 1 Valid 2 ST DEC Dis 3 Always Invalid P N DC 0 73 b020 Frequency setting to match 0 99 99 100 0 400 0 Hz 0 00 74 b021 Non stop function section at Instantaneous power failure 0 invalid 1 valid 0 ⅹ 77 b022 Starting voltage of non stop function at Instantaneo...

Page 56: ...hermistor adjustment 0 0 999 9 105 0 81 b037 Data command selection 0 OPERATOR 1 RS485 2 OPT1 3 OPT2 4 RS232 0 ⅹ 82 b038 Communicating transmission speed 0 2400BPS 1 4800BPS 2 9600BPS 3 19200BPS 4 38400BPS 2 ⅹ 82 b039 Communication code 1 32 1 82 b040 Communication bit 7 BIT 8 BIT 8 82 b041 Communication parity 0 NO Parity 1 Even Parity 2 Odd Parity 0 82 b042 Communication stop bit 1 1Bit 2 2itT 1...

Page 57: ...put terminal selection 0 N O 1 N C 0 87 I018 O input span calibration 0 9999 Factory setting 104 I019 O input zero calibration 0 9999 Factory setting 104 I020 O start frequency 0 99 99 100 0 400 0 Hz 0 00 104 I021 O end frequency 0 99 99 100 0 400 0 Hz 0 00 104 I022 O start voltage 0 100 0 104 I023 O end voltage 0 100 100 104 I024 O start selection 0 EXT FREQ 1 ZERO HZ 1 104 I025 OI input span cal...

Page 58: ...3 setting 3 109 o004 Intelligent output 4 setting Intelligent output setting reference 7 109 o005 Intelligent output 1 selection 0 110 o006 Intelligent output 2 selection 0 110 o007 Intelligent output 3 selection 0 110 o008 Intelligent output 4 selection Intelligent output contact setting 0 N O 1 N C 0 110 o009 FM output selection 0 FREQ_OUT 1 CURR_OUT 2 TORQ_OUT 3 DFREQ_OUT 4 VOL_OUT 5 POW_IN 6 L...

Page 59: ...ection 2 nd motor 0 Manual 1 Automatic 0 ⅹ C004 Manual torque boost value 0 0 20 0 1 0 123 C204 Manual torque boost value 2 nd motor 0 0 20 0 1 0 92 C005 Manual torque boost break point 0 0 50 0 5 0 123 C205 Manual torque point boost frequency 2 nd motor 0 0 50 0 5 0 92 C006 Torque limit selection 0 4 Guad mode 1 TER OPR 2 Analog IN 3 OPT1 4 OPT2 0 125 C007 Torque limit 1 0 200 200 125 C008 Torque...

Page 60: ...e Initial data Change mode on run Page C025 PID D gain 0 0 100 0 sec 0 0 129 C026 PID Feedback gain 0 00 99 99 times 1 00 129 C027 PID Feedback selection 0 Current 1 Voltage 0 129 Table 4 9 Advanced control function setting C group LAD Linear Acceleration Deceleration BRD Regenerative Breaking Circuit ...

Page 61: ...07 2 nd motor constant J 0 00 99 99 100 0 655 3 kg m 2 Jstd ⅹ 132 H008 1 st motor constant L 0 00 99 99 100 0 999 9 mH Lstd ⅹ 132 H208 2 nd motor constant L 0 00 99 99 100 0 999 9 mH Lstd ⅹ 133 H009 1 st motor constant R1 Autotuning data 0 000 9 999 Ω R1std ⅹ 133 H209 2 nd motor constant R1 Autotuning data 0 000 9 999 Ω R1std ⅹ 133 H010 1 st motor constant R2 Autotuning data 0 000 9 999 Ω R2std ⅹ ...

Page 62: ...ation completion range setting 0 9999 5 P011 Orientation completion delay time setting 0 00 9 99 sec 0 00 P012 Electronic gear position selection 0 FEEDBACK 1 REFERENCE 0 P013 Electronic gear numerator of ratio setting 0 9999 1024 P014 Electronic gear denominator of ratio setting 0 9999 1024 P015 Position control feed forward gain setting 0 00 99 99 100 0 655 3 0 00 P016 Position control loop gain...

Page 63: ...d F Reverse r Stop o 2 On operating the inverter in case of CW FWD or CCW REV the RUN lamp will illuminate 5 3 Output current monitor d003 1 Indication code d003 displays the output current value 2 The data is displayed as follows 0 0 999 9 Display is in 0 1 A unit In case of displaying d003 the monitor lamp A is illuminated 3 The output current is displayed in RMS value according to the load curr...

Page 64: ...onitor d009 1 When you select PID function 01 in C022 the inverter displays the feedback value changed by C026 PID scale Display of monitor part Feedback quantity x PID scale frequency command value C026 0 00 99 99 Display is in 0 01 unit 100 0 999 9 Display is in 0 1 unit 1000 9999 Display is in 1 unit 5 10 Intelligent input terminal monitor d010 1 The LED display will monitor the state of the in...

Page 65: ...RUN d014 1 The operation time of inverter is accumulated and the value is displayed 2 0 59 Display is in 1 min Units 5 15 Power ON time monitor d015 1 This accumulates the time running to the inverter and displays the value 2 0 9999 Display is in 1 hour units When the value is more than 10 000 hours the last point added in the LED display 1000 6553 The maximum value is 6553 5 16 Power ON time moni...

Page 66: ...ctions and Parts Manual 5 Explanation of d Group Function 45 Output current on tripping A The direct voltage between P and N on tripping V Note Please refer to the protection function list for detailed Trip monitor display ...

Page 67: ...setting by 0 1Hz F201 Output frequency setting of 2nd motor 0 00 Hz 0 0 F004 F203 0 00 99 00 By 0 01Hz setting 100 0 400 0 setting by 0 1Hz Table 6 1 Output frequency setting F001 F201 6 2 Base frequency setting F002 F202 1 Base frequency and motor voltage On selection of base frequency and motor voltage set the output of the inverter frequency voltage to the motor rating Fig 6 2 Base frequency an...

Page 68: ...that the inverter will achieve when it receives top speed reference from the control terminals or the digital operator 3 The inverter output voltage from the base frequency to the maximum frequency is the same level as the voltage selected on the motor voltage selection Code Function name Initial value Unit Setting range Contents F003 Maximum frequency setting 60 00 Hz 30 00 400 0 30 00 99 00 Sett...

Page 69: ...function can set a upper and lower limit of the output frequency z Even if a frequency command exceeds the upper and lower limit the inverter will ignore this value and stop at the values set z Set first upper limit on setting z Be sure that the upper limit F005 lower limit F006 z The upper and lower limit will not operate if 0Hz is set Code Function name Initial value Unit Setting range Contents ...

Page 70: ...eleration time can be set Set a long time to accelerate or decelerate slowly or set a short time to accelerate or decelerate quickly 2 The time setting is the time it takes to accelerate from 0Hz to the maximum frequency F003 and to decelerate from the maximum frequency to 0Hz Code Function name Initial value Unit Setting range Contents F007 Acceleration time setting 30 0 Sec 0 01 3600 0 1 999 9 U...

Page 71: ... 7 Driving direction selection F009 6 8 Frequency source setting F010 1 Select the method of frequency command 2 When 10 0Vdc is inputted to the frequency command by 02 L terminal the operating direction of motor is reversed Code Function name Initial value Unit Setting range Contents 0 OPE VOL Potentiometer Setting frequency with the potentiometer the digital operator has 1 Ter Setting frequency ...

Page 72: ... setting 2 5 OPT2 Setting frequency with option board 2 Table 6 9 RUN command source setting F011 3 Operation command from the control terminals Terminal start stop by ON OFF of control terminals 4 Put 01 REV to an intelligent input terminal When using the FW terminal it is possible the change the contact from NO to NC by setting a or b respectively in I009 I017 Forward FW CM1 terminal Reverse REV...

Page 73: ...sensorless vector control 6 V2 Sensored vector control F012 Motor control method 5 7 0Hz V2 0Hz Sensored vector control 0 VC Constant torque characteristic 1 VP1 Reduced torque characteristic VP1 7 power 2 VP2 Reduced torque characteristic VP2 0 power 3 Free V f Free setting V f characteristic 4 SLV I Indirect sensorless vector control F212 Second Motor control method 5 5 SLV D Direct sensorless v...

Page 74: ...he revolution of motor and output torque are estimated by output current voltage of the inverter and motor constant of setting It is possible to operate with high starting torque and high accuracy at low frequency In the case of using this function please select the suitable motor constant of using the motor according to the parameter of selection of motor constant If this inverter operates less t...

Page 75: ...Initial value Unit Setting range Contents F015 Motor capacity selection motor rated capacity According to Inverter capacity 1 5 2 2 3 7 5 5 7 5 11 15 18 5 22 30 37 45 55 75 90 110 132 160 Setting according to the number of motor poles 200V class 400V class F215 2nd motor capacity selection According to Inverter capacity 1 5 2 2 3 7 5 5 7 5 11 15 18 5 22 30 37 45 55 75 90 110 132 160 Setting accord...

Page 76: ...ents 0 Speed control mode F018 Speed Torque mode selection 0 0 1 1 Torque control mode Table 6 16 Speed Torque mode selection F018 Please use a feedback option card for using this function Set the F012 to 6 or 7 Note This function is explained in the feedback option card manual 6 17 SLV control mode selection F019 Code Function name Initial value Unit Setting range Contents 0 Normal Operation F019...

Page 77: ...et acceleration and deceleration pattern of the 2nd motor setting in each A 201 A202 Set value 0 1 2 3 Curve Line S shape U shape Reverse U shape A001 Acceleration curve Selection A002 Deceleration curve selection Contents Accelerate and decelerate in line frequency set value linear with time Collapsing the cargo such as the going up and down machine conveyor it uses it for prevention Cutting the ...

Page 78: ...eration curvature function A003 A004 Fig 7 1 Acceleration and deceleration curvature 7 3 Acceleration stop function A005 A006 When the moment of inertia for the load is high this is the function to wait until the slip of the motor on starting becomes smaller Use when the over current trip occurs on starting Code Function name Initial value Unit Setting range Contents A005 Acceleration stop frequen...

Page 79: ...celeration and deceleration selection 0 1 Changing by two stage acceleration and deceleration frequency A 010 A11 Ex 2 A008 Acceleration time 2 30 0 Sec 0 1 3600 0 1 999 9 1000 3600 A009 Deceleration time 2 30 0 Sec 0 1 3600 0 1 999 9 1000 3600 A010 Acceleration Frequency 2 0 00 Hz 0 00 F003 0 00 99 99 100 0 400 0 It is valid when two stage acceleration and deceleration selection A007 is 01 Ex 2 A...

Page 80: ...ration and deceleration frequency A 015 A016 Ex 2 A013 Acceleration time 3 30 0 Sec 0 1 3600 0 1 999 9 1000 3600 A014 Deceleration time 3 30 0 Sec 0 1 3600 0 1 999 9 1000 3600 A015 Acceleration frequency 3 0 00 Hz 0 00 F003 0 00 99 99 100 0 400 0 It is valid when Three stage acceleration and deceleration selection A012 is 01 Ex 2 A016 Deceleration frequency 3 0 00 Hz 0 00 F003 0 00 99 99 100 0 400...

Page 81: ... 99 99 100 0 400 0 Multi Speed 9 setting A037 Multi Speed 10 0 00 Hz 0 00 F004 F003 0 00 99 99 100 0 400 0 Multi Speed 10 setting A038 Multi Speed 11 0 00 Hz 0 00 F004 F003 0 00 99 99 100 0 400 0 Multi Speed 11setting A039 Multi Speed 12 0 00 Hz 0 00 F004 F003 0 00 99 99 100 0 400 0 Multi Speed 12 setting A040 Multi Speed 13 0 00 Hz 0 00 F004 F003 0 00 99 99 100 0 400 0 Multi Speed 13 setting A041...

Page 82: ...frequency F002 maximum frequency F003 is invalid Free V f frequency 7 is same as the maximum frequency Code Function name Initial value Unit Setting range Contents A059 Free V F frequency 1 0 00 Hz 0 00 400 0 0 00 99 99 100 0 400 0 F1 frequency setting A060 Free V F voltage 1 0 0 V 0 0 999 9 Voltage of V1 setting A061 Free V F frequency 2 0 00 Hz 0 00 400 0 0 00 99 99 100 0 400 0 F2 frequency sett...

Page 83: ...l the jogging operation is started Code Function Initial value Unit Setting range Contents A073 Jogging frequency 0 00 Hz 0 00 Starting frequency 10 00 Jogging frequency Setting 0 FRS free run stop on jogging stop 1 DEC deceleration stop on jogging stop A074 Jogging stop selection 0 2 DCBR direct braking on jogging stop Table 7 9 Jog operation setting A073 A074 3 The jogging operation does not use...

Page 84: ... minium value cannot be set over the maxium value and the maximum value cannot be set under the minimum value 5 Please set the maimum frequency value before the initial frequency setting Code Function name Initial value Unit Setting range Contents A075 Jump frequency 1 lower limit 0 00 Hz 0 00 F003 0 00 99 99 100 0 400 0 Lower limit frequency setting with jump frequency 1 A076 Jump frequency 1 upp...

Page 85: ...king is started A084 DC braking force 0 0 100 Weak Zero current Strong Range is from 0 to 80 A085 DC braking time 0 00 Sec 0 00 60 00 The DC braking is stopped after this time delay has elapsed The time is started when the late time has elapsed 0 Edge movement A086 DC braking edge level selection 1 1 Level movement A087 DC braking force for starting 0 0 100 Weak Zero current Strong Range is from 0...

Page 86: ...er starts and stops it is possible to operate DC braking without terminal operation When using internal DC braking the DC braking selection A081 should be set 01 Set the starting frequency of the DC braking with A082 If DC braking late time A083 is set and the dc braking frequency is reached the operating command FW is switched OFF The inverter cuts the output and for the set time of A083 free run...

Page 87: ...rmal operation is restored Example 5 2 Example 6 2 1 Edge operation A086 0 2 Level operation A086 1 Example 4 1 When starting Example 4 2 When starting FW A088 DC braking Output frequency Example 5 1 When stopping Example 5 2 When stopping Example 6 1 When stopping Example 6 2 When stopping FW A085 A082 Output frequency Fig 7 11 Internal DC braking curve 7 12 Acceleration and deceleration referenc...

Page 88: ...ime to 30Hz becomes 15 seconds Fig 7 12 Acceleration and deceleration setting curve A089 0 2 in case of A089 1 The arrival time to setting value of output frequency is accelerating time regardless of maximum frequency That is if output frequency F001 is set to 30Hz when maximum frequency is 60Hz and accelerating time is 30 seconds the arrival time to 30Hz becomes 30 seconds But it is valid when th...

Page 89: ...can t reach the setting frequency in the acceleration deceleration time setting value make a value of the A090 and A092 lager and if a vibration is occured make a value of the A090 and A092 lager 4 A091 A093 If an over voltage or a speed over shoot is occurred make a value of the A091 and A093 smaller If you want to shot a deceleration time using the BRD make a value of the A091 and A093 lager 7 1...

Page 90: ... to raise the voltage slowly on motor starting In case of raising the motor torque on starting make the setting value low However the inverter has a tendency of tripping on over current protection by making this value lower because of almost direct starting F004 Output frequency Output voltage FW 0 1 6 Fig 8 1 Reduced voltage start selection curve Code Function name Initial value Unit Setting rang...

Page 91: ...digital operator or the control terminals Terminal you can select the stop after slowing down according to slowing down time or the free run stop When the DC braking A081 is selected DCBR is working during a deceleration stop Code Function name Initial value Unit Setting range Contents 0 Deceleration stop 1 FRS Free run stop b006 Stop mode selection 0 2 DCBR stop after DC Braking Table 8 5 Selecti...

Page 92: ...l output frequency to the FM terminal Code Function name Initial value Unit Setting range Contents b009 Frequency conversion factor 1 0 times 0 1 99 9 FM digital output frequency Output frequency x Frequency conversion factor Table 8 8 Frequency conversion factor b009 8 6 Carrier frequency b010 1 The carrier frequency of the PWM wave form output from the inverter is adjustable with b010 2 If the c...

Page 93: ... Only during run Table 8 11 Cooling fan operating selection b011 8 8 Ground Fault selection b013 1 This is the function to warn when ground fault is occurred 2 Note that if this code is 1 valid only the moment when the power is on the inverter checks out ground fault between the inverter output and the motor 3 If ground fault is detected while running inverter will stop with another error overcurr...

Page 94: ...ersion F002 F003 F010 F011 A073 F013 1 50 50 01 1 1 230 400 USA US version F002 F003 F010 F011 A073 F013 b015 Country code for initialization 0 2 60 60 0 2 0 230 460 Table 8 14 Country code for initialization b015 8 11 Automatic restart mode function b016 b025 1 Instantaneous power failure restart You can select whether the inverter trips or retries restart when an instantaneous power failure unde...

Page 95: ...his set frequency restart with 0Hz is caused Ex 3 4 Table 8 15 Instantaneous power failure restart b016 b020 Frequency matching start The inverter reads the motor RPM and direction and restarts the inverter to match these readings without motor stop NOTE 1 When trip of the over voltage or over current occurs in the deceleration time an instantaneous power failure E016 is displayed and the inverter...

Page 96: ...arm outputs at an instantaneous power failure and under voltage during stop is following When b016 is set to 0 Fig 8 3 The waveform of alarm outputs at instantaneous power failure under voltage alarm output during stop b016 0 It is possible to use an output by assigning the signal IP 08 during instantaneous stop by setting UV 09 during under voltage to an intelligent output terminal 11 14 o001 o00...

Page 97: ... than b017 second Fig 8 4The waveform of alarm outputs at instantaneous power failure under voltage alarm output during stop b016 1 or 2 When b016 is set to 1 or 2 and instantaneous power failure time is more than b017 second Fig 8 5 The waveform of alarm outputs at instantaneous power failure under voltage alarm output during stop b016 1 or 2 ...

Page 98: ...tage due to generating during deceleration more than non stop 0V LADSTOP level at instantaneous power failure b022 the condition would be in LAD stop until over voltage is released Code Function name Initial value Unit Setting range Contents 0 Non stop function at instantaneous power failure invalid b021 Non stop function selection at instantaneous power Failure 0 1 Non stop function at instantane...

Page 99: ...rding to motor rated current to protect the motor from overloading overheating and damage A warning signal can be generated before tripping an electronic thermal protection z The frequency characteristic is set in b028 1 Electronic thermal level Code Function name Initial value Unit Setting range Contents b027 Electronic thermal level Irate A 0 0 999 9 Please set value less than 2 times of motor r...

Page 100: ...put frequency 20Hz Fig 8 8 Reduced torque characteristic 200V class 15Hp Constant torque characteristic Set this characteristic in case of the use of a constant torque motor Ex 200V class 15Hp b027 46A output frequency 2 5Hz Fig 8 9 Constant torque characteristic 200V class 15Hp 2 Thermal warning A warning signal can be generated before overheat protection by the electronic thermal protection occu...

Page 101: ...sed with regenerative energy from the motor at automatic deceleration by this function When this function operates while accelerating the frequency will not reach the goal frequency the Inverter will adjust in the following way Make an acceleration time longer Raise a torque boost Raise a overload restriction level Code Function name Initial value Unit Setting range Contents 0 Invalid 1 Accelerati...

Page 102: ... 0 0 2 0 0 Rated current ⅹ2time As load reaches overload advance notice level OL2 signal is output Table 8 20 Overload advance notice o026 o027 Fig 8 11 The waveform for overload advance notice level 8 15 External thermistor b034 b036 1 Temperature protection of the external machine is possible by the use of a thermistor fitted to your motor 2 Wire the thermistor between control terminals TH and C...

Page 103: ...al value Unit Setting range Contents b037 Data command selection 0 0 3 0 Operator 1 RS485 RS485 2 OPT1 Profibus 3 OPT2 DeviceNet 4 RS232 RS232 b038 Communicating transmission speed 2 0 4 0 2 400bps 1 4 800bps 2 9 600bps 3 19 200bps 4 38 400bps b039 Communication code 1 1 32 b040 Communication bit 8 7 8 7 7bit 8 8bit b041 Communication parity 0 0 2 0 No parity 1 Even parity 2 Odd parity b042 Commun...

Page 104: ... O or OI terminal z Setting switching O2 terminal individually frequency order possible Analog control terminal Frequency setting input OI Frequency command Terminal 4 20mA z When inputting DC 4 20mA 20mA is maximum frequency z When AT terminal is ON OI signal is valid P24 Interface power z It is DC24V power for connection input signal When selecting source logic it s connection input common CM1 I...

Page 105: ...on level variable 0 9999Ω Table 9 1 List of control circuit terminal 9 1 2 Intelligent input terminal connection 1 Intelligent input terminal circuit can use 24V through the P24 terminal from the inside of the inverter 2 Input circuit is connected to PLC terminal Therefore in case of using an internal power short the circuit like the following In order to use external power remove the short line a...

Page 106: ...ion 3 If a function tries to be assigned to an intelligent input terminal where another terminal already has the function the new terminal will automatically be restored back to the previous setting code Function name Code value Contents Item 1 REV Reverse driving Operation command 2 CF1 Multi speed 1 binary operation 3 CF2 Multi speed 2 binary operation 4 CF3 Multi speed 3 binary operation 5 CF4 ...

Page 107: ...function Refer to feedback function 38 XT1 Multi step acceleration deceleration time 1 39 XT2 Multi step acceleration deceleration time 2 40 XT3 Multi step acceleration deceleration time 3 Multi step acceleration deceleration Time function Table 9 2 Input terminal function selection I001 I008 4 The initial function setting I001 I008 for the intelligent input terminal is like the following Code Fun...

Page 108: ...al value Unit Set range Contents 0 N O Normally Open a contact I009 I016 Intelligent input 1 8 a b ON NC selection 0 1 N C Normally Closed b contact I017 Input FW a b ON NC selection 0 0 1 a b contact setting of FW terminal Table 9 4 Input terminal a b NO NC selection I009 I016 a contact ON with Close OFF with open Normally open state b contact ON with Open OFF with close Normally closed state RES...

Page 109: ...put status Contents OFF Inverter is STOP mode Motor STOP 0 FWD Forward Run stop ON Inverter is forward operation mode Motor Forward run OFF Inverter is stop mode Motor Reverse run 1 REV Reverse Run stop ON Inverter is Reverse operation mode Motor Reverse run Table 9 5 Driving command FWD REV Forward Reverse Ex The setting method of run command through control terminals The setting method of run co...

Page 110: ...ol terminals Setting by F011 1 Ter I001 2 CF1 I002 3 CF2 I003 4 CF3 I004 5 CF4 Multi speed1 15 is set with A028 A042 Fig 9 9 Multi speed operation function CF1 CF4 in the control terminal Signal Input for the terminal Setting Frequency Multi speed CF4 CF3 CF2 CF1 Function Code Setting Value 0 speed OFF OFF OFF OFF A027 0 Hz 1 speed OFF OFF OFF ON A028 5 Hz 2 speed OFF OFF ON OFF A029 10 Hz 3 speed...

Page 111: ...OG Jogging driving ON Jogging operation at jogging frequency A073 Table 9 6 Jogging driving JOG Jogging Operation Note When the Jogging frequency is set to the start frequency F004 or 0Hz jogging operation is not valid When using JOG function confirm whether the motor stops Code Function name Initial value Unit Setting range Contents A073 Jogging frequency 0 00 Hz 0 00 10 00 Jogging frequency sett...

Page 112: ...rent braking DB External DC Braking 1 Please set 7 DB to an Intelligent input terminal 2 DC braking is then switched by ON OFF of DB terminal irrespective of DC braking selection A081 3 Set DC braking force with A084 4 If DC braking time A083 is set the Inverter output is cut off for this time period the motor will be free running After the setting time passes DC braking is started 5 Please set DC...

Page 113: ...frequency b027 b227 1ST 2nd Motor electronic thermal level b Group b028 b228 1ST 2nd Motor electronic thermal characteristic C003 C203 1ST 2nd Motor torque boost selection C004 C204 1ST 2nd Motor passivity torque boost amount C Group C005 C205 1ST 2nd Motor passivity torque boost frequency H002 H202 1ST 2nd Motor constant selection H003 H203 1ST 2nd Motor stator resistance H004 H204 1ST 2nd Motor ...

Page 114: ...uency setting value of A010 A011 Fig 9 14 In case of setting 2 step acceleration deceleration function to 9 for the input terminal 1 I001 9 2 7 Three Stages acceleration deceleration 3CH 1 In case of changing by intelligent input terminal assign 10 3CH to an Intelligent input terminal By setting this function it is possible to change the rate of acceleration and deceleration 2 As methods to change...

Page 115: ... it is possible to select 0Hz start or matching frequency start as output methods with the free run stop selection b007 Example 1 Example 2 11 When you set the frequency setting to match b007 and the frequency detected is under this setting 12 when the free run stop is released the inverter is restarted from 0Hz 13 The setting of this function is valid for selection b006 on stopping Code Function ...

Page 116: ...trips E12 EXTERNAL and the outputs switched OFF 3 Assign 12 EXT to an intelligent input terminal 4 The trip will not be canceled when the terminal is turned OFF 5 To cancel the trip the reset signal must be applied or the Inverter switched OFF and ON again at the supply Operation command FW REV EXT terminal Number of Motor revolution time RS terminal Alarm output terminal Free run Fig 9 17 In case...

Page 117: ...USP error occurs the inverter will restart automatically Please take care Example 2 9 2 11 Software lock mode selection SFT Software Lock 1 It is selectable whether the data in a code is changeable in this function 2 This function is used to prevent changing data by mistake 3 When you want to use an intelligent input terminal 1 8 I001 I008 assign 15 SFT Code Function name Initial value Unit Settin...

Page 118: ...n by AT terminal selection AT terminal by electric current input 4 20 mA of OI L terminal and O2 voltage input 0 10V of L terminal do ON analog outside input switching According to AT terminal selection I049 s command I can choose input of O OI O2 Note that the value of 02 selection I038 is 0 singleness Code Function name Initial value Unit Setting range Contents 0 O OI O OI switching by AT termin...

Page 119: ... L No No 0 1 ON O2 L Yes OFF O L Yes 0 ON OI L Yes OFF O L Yes 1 1 ON O2 L No OFF O L Yes 0 ON OI L Yes OFF O L Yes Intelligent Input Terminal on Assigning AT 2 1 ON O2 L Yes 0 O2 L Yes 1 Adding O L and OI L Yes No Intelligent Input Terminal when don t assign AT 2 Adding O L and OI L Yes Yes Table 9 12 Analog external signal selection by association of AT terminal selection I049 and 02 selections ...

Page 120: ...ing ex 2 I050 Reset selection 0 2 At ON cancellation when is normal trip when is normal nullity trip cancellation 0 0Hz 0Hz start I051 Reset frequency matching selection 0 1 Fmat Frequency matching start ex 3 Table 9 13 Reset selection 5 Use the RESET terminal as the a contact Normally open If the RESET terminal is set to b contact the inverter is always RESET 1 Example RS Alarm Alarm 2 Example RS...

Page 121: ...lity of overcurrent trip 6 Turn ON PIDC terminal after turning OFF PID action Note Please refer to PID control part for details 9 2 16 UP DOWN function UP DOWN UDC 1 The Inverter output frequency can be changed with the UP and DWN intelligent input terminals 2 Assign 24 UP and 25 DWN 26 UDC to two of the intelligent input terminals 1 8 3 This function is valid only when the frequency command selec...

Page 122: ...ed by UP DOWN is remembered After power cycle it keep last frequency adjusted by UP DOWN Table 9 14 UP DOWN function UP DOWN UDC Code Function Output state Contents OFF Motor output acts normally 24 UP Remote control UP ON Accelerating motor from present frequency Output frequency increases OFF Motor output acts normally 25 DOWN Remote control Down ON Decelerating motor from present frequency Outp...

Page 123: ...et 1 input terminal to torque limit function C006 This mode sets torque limit in 4 zones forward driving and regenerating reverse driving and regenerating Limits for each quadrant are set with C007 C010 individually By use of torque limit cutting terminal 1 and 2 this mode changes and uses torque limit 1 4 set in C007 C010 3 When this function set a torque an existence and nonexistence function TL...

Page 124: ...eration deceleration time setting function selection 코드 기능명칭 XT3 XT2 XT1 초기값 A043 1st acceleration time 0 0 1 30 0 A044 1st deceleration time 0 0 1 30 0 A045 2nd acceleration time 0 1 0 30 0 A046 2nd deceleration time 0 1 0 30 0 A047 3rd acceleration time 0 1 1 30 0 A048 3rd deceleration time 0 1 1 30 0 A049 4th acceleration time 1 0 0 30 0 A050 4th deceleration time 1 0 0 30 0 A051 5th accelerati...

Page 125: ...I020 O Start frequency 0 00 Hz 0 00 400 0 Start frequency setting I021 O End frequency 0 00 Hz 0 00 400 0 End frequency setting I022 O Start voltage 0 0 100 Starting point for the voltage input 0V I023 O End voltage 100 0 100 Ending point for the voltage input 10V 0 external frequency 0 I022 output frequency to I020 output I024 O Start selection 1 1 0Hz 0 I022 value of output frequency to 0Hz is o...

Page 126: ...ency 0 00 Hz 0 00 400 0 Start frequency setting I028 OI End frequency 0 00 Hz 0 00 400 0 End frequency setting I029 OI Start voltage 0 0 100 Starting point for the voltage input 4mA I030 OI End voltage 100 0 100 Ending point for the voltage input 20mA 0 external frequency 0 I029 output frequency to I027 output I031 OI Start selection 1 1 0Hz 0 I029 value of output frequency to 0Hz is output Table ...

Page 127: ...e irreversible I038 O2 Start selection 0 2 Assistance Table 9 19 O2 L terminal setting 2 10V ratio of 10V is as following 3 Setting O2 starts selection I038 by 0 singleness O2 to use L signal individually and AT function does not allocate Please take care Intelligent input terminal function I002 s initial value was set by 16 AT 4 Or I038 if input AT signal after set I049 by 1 O O2 by 0 O2 L Simple...

Page 128: ...e or electric current input from outside in this function 2 The frequency setting circuit is valid to noise removal 3 Please adjust output frequency setting value higher or lower in case there is a frequency issue affecting the drive stability due to noise influence Code Function Initial value Unit Setting range Contents I046 Analog input filter factor 8 1 30 Setting by 1 unit Table 9 20 Analog in...

Page 129: ... rotor termination z It is rotor termination of output terminal AM AMI Note Don t earth P24 Interface power z It is DC24V power for connection input signal When selecting source logic it s connection input common CM1 Interface power Common z This is common for DC 24V terminal for interface thermister input TH Digital monitor FM z When sink logic is selected it is a common point of contact Digital ...

Page 130: ...ssigned to the intelligent output terminals 11 14 o001 o004 and relay output terminals AL RN o031 o032 Function code Function name Code value Contents Reference item 0 RUN Signal during run Signal during run 1 FA1 Constant speed arrival signal 2 FA2 Over setting frequency Frequency arrival signal 3 OL Overload advance notice signal overload limit 4 OD Output deviation for PID control PID function ...

Page 131: ...s changeable individually 2 The intelligent output terminals 11 14 are the Open Collector output and the alarm relay AL RN are all relay outputs Code Function name Initial value Unit Setting range Contents 0 N O Normally Open a contact o005 o008 Intelligent 1 4 Output setting 0 1 N C Normally Closed b contact FW terminal input setting 0 0 1 Setting a b contact of FW terminal Table 10 3 Intelligent...

Page 132: ...ll relay if you need output current greater than 50mA To reduce the spike voltage across the relay at turn off use a diode on both end of a relay coil or use a solid state relay instead of a mechanical relay 4 Specification of Intelligent output terminals AL 0 AL 1 AL 2 RN 0 RN 1 RN 2 Relay output C contact 5 The specifications of the alarm relay AL0 AL1 AL2 and RUN relay is c contact The method f...

Page 133: ...n AL1 AL0 AL2 AL0 ON Normal Open Closed ON Normal Closed Open ON Trip Closed Open ON Trip Open Closed a contact N O OFF Open Closed b contact N C OFF Open Closed Fig 10 6 Example on using as alarm Point of contact specification Point of contact Division Resistor load Inductive load Maximum contact capacity AC250V 2A DC30V 8A AC250V 0 2A DC30V 0 6A AL1 AL0 RN1 RN0 Minimum contact capacity AC100V 10...

Page 134: ...cy 2 20 FA5 only setting frequency 2 to an intelligent output terminals 11 14 Code value Function name Output state Contents OFF When output frequency doesn t reach the frequency set in F001 1 FA1 Constant speed arrival signal ON When output frequency reaches the frequency set in F001 OFF When output frequency reaches below the arrival frequency during the deceleration which is set in o019 2 FA2 O...

Page 135: ...arrival setting for deceleration 2 0 00 Hz 0 00 400 0 0 00 99 99 100 0 400 0 Table 10 7 Frequency setting during the acceleration and deceleration 4 The hysteresis frequency for the arrival signal is the following ON Setting frequency 1 of maximum frequency Hz OFF Setting frequency 2 of maximum frequency Hz 5 However in set 06 FA3 20 FA5 case when inverter accelerates ON Setting frequency 1 of max...

Page 136: ... the amount of a load is high it is possible to adjust the gain by outputting an overload advance notice It is used to prevent damage to the machine from too much load i e baggage on a conveyor the Inverter overload protection will operate 3 Assign 03 OL or 21 OL2 to an intelligent output terminal 11 14 Code value Function name Output state Contents OFF In case output current is smaller than value...

Page 137: ...eviation Level OD 1 It is possible to establish the maximum deviation level o029 on PID control When the PID deviation amount reaches the set level o029 it is possible to output OD PID Max deviation in an intelligent output 2 o029 can be set from 0 to 100 0 and corresponds with the command from 0 to maximum value Code Function name Initial value Unit Setting range Contents o029 PID deviation setti...

Page 138: ...e page from108 to 111 Specification of the intelligent output terminals 1 4 Specification of Intelligent output terminals AL 0 AL 1 AL 2 RN 0 RN 1 RN 2 for details 10 2 6 Over torque signal OTQ 1 This function can detect that estimated value of output torque of motor increase more than optional level and outputs 2 When an over torque signal 7 OTQ is selected in intelligent output terminal 11 14 th...

Page 139: ...Code Function name Initial value Unit Setting range Contents o028 RUN ON time over level 0 Hour 0 9999 Over time level setting Table 10 14 RUN ON time over level 1 RUN time over RNT Assign 11 RNT to an intelligent output terminal 11 14 Set ON time level with o028 2 Power ON time over ONT Assign 12 ONT to an intelligent output terminal 11 14 Set ON time level with o028 10 2 10 Thermal warning signa...

Page 140: ...details 10 2 12 Zero speed detect signal ZS 1 Please set 16 ZS to an intelligent output terminal 11 14 and a relay output terminal By selecting zero speed signal in an intelligent output selection this function comes into effect 2 This function detects that the output of the rotation speed of a motor or the output of LAD fell off from the zero speed detection level o030 and outputs the ZS signal 3...

Page 141: ...ermal load 0 100 o009 FM output Selection 0 7 Flad LAD frequency 0 Maximum frequency Hz Table 10 17 FM output Selection o009 Note o009 2 output torque is only outputted when control mode is SLV SLV2 V2 0Hz V2 display 3 PWM signal type o009 0 1 2 4 5 6 7 PWM Pulse Width Modulation signal is used to run a moving coil type indicator PWM signal is expressed by analog value that is AUTO meaning value b...

Page 142: ...orm of FM signal o009 3 5 FM adjustment It is used to reform a meter that is connected to FM terminal Code Function name Initial value Unit Setting range Contents o010 FM offset 3 00 3 00 10 00 Offset setting o011 FM adjustment 80 0 0 0 255 0 Gain setting Table 10 18 FM offset and adjustment Adjusting method Connect an input meter for DC 0 10 V to FM CM1 terminal Adjust FM to read the same meter a...

Page 143: ...tput Selection 0 6 Flad LAD frequency 0 Maximum frequency Hz 0 Fo Output frequency 0 Maximum frequency Hz 1 Io Output current 0 200 2 To Output torque 0 200 3 Vo Output voltage 0 100 4 Pin Input electric power 0 200 5 Load Thermal load ratio 0 100 o015 AMI Output Selection 0 6 Flad LAD frequency 0 Maximum frequency Hz Table 10 19 AM AMI output signals selection Note Display o012 o015 2 output torq...

Page 144: ... gain F014 Function name Code Setting range Unit Contents Output voltage gain F014 20 100 Decrease the value of F014 in case of motor hunting Carrier frequency b010 0 5 10 0 kHz Decrease the value of b010 in case of motor hunting V f stability adjust C002 0 0 300 0 Adjust the value of C002 in case of motor hunting Table 11 2 Motor hunting control function F014 b010 C002 11 2 Torque boost function ...

Page 145: ...ge start selection b003 to 0 In case of C003 0 C004 10 0 C005 5 0 In case of C003 0 C004 5 0 C005 10 0 Fig 11 1 The graph for Manual torque boost 11 2 2 Automatic torque boost 1 The output voltage is adjusted automatically by condition of the load 2 When using automatic torque boost it important that the following two parameters are set correctly 3 In case of adding over current protection at dece...

Page 146: ...o not work and torque limits change to 200 Option 1 Option 2 Reserved Code Function name Initial value Unit Setting range Contents 0 Individual setting 1 Terminal 2 Analog input 3 OPT1 Reserved C006 Torque limit selection 0 4 OPT2 Reserved C007 Torque limit 1 200 0 200 In the case of 4 upper limits individuation setting forward driving C008 Torque limit 2 200 0 200 In the case of 4 upper limits in...

Page 147: ...D 0 TRQ1 30 CM1 P24 PLC TRQ2 31 Fig 11 3 Torque limit setting in intelligent input terminal 8 When using torque limit function at low speed level use overload restriction together 11 4 External braking control function C012 C018 1 This is a function that the inverter controls external braking used in systems like elevators By braking control function selection C012 is set to valid 01 this function...

Page 148: ...ting time for braking confirmation the inverter will output braking error signal BER and the trip will occur If braking confirmation signal is not set to intelligent input braking terminal the waiting time for braking confirmation will be invalid and after the inverter will output braking releasing signal proceed to After braking confirmation signal turns off after braking releasing signal turns o...

Page 149: ...re that the motor will slip down easily if setting current is low Table 11 6 Braking control function selection 4 ln the following case the inverter trip occurs and outputs braking error signal BER Braking error ln the case that output current is less than releasing current after waiting time for braking releasing confirmation When braking confirmation signal is used in the case that braking confi...

Page 150: ...or fan and pump applications z When using this function set C022 to 01 or 02 Turn off the terminal in the case that you validate this function or turn on the terminals in the case that you invalidate this function after assigned 21 PID valid invalid to intelligent input terminals in the case of switching valid invalid of this function with the outside signal Code Function name Initial value Unit S...

Page 151: ...c block diagram of PID control 3 Components of PID P action This is the action that the manipulated variable is in proportion to the command Fig 11 7 Components of PID P action I action This is the action that the manipulated variable increases with time in a straight lime Fig 11 8 Components of PID I action D action This is the action that the manipulated variable in proportion to the changing ra...

Page 152: ...n 5 The Maximum PID Deviation Level Output It is possible to establish the maximum deviation level o029 on PID control When the PID deviation amount reaches the set level o029 it is possible to set an intelligent output o029 can be set from 0 to 100 0 and corresponds with the command from 0 to maximum Assign 04 OD to an intelligent output terminal 1 4 o001 o004 6 Feedback monitor of PID Feedback s...

Page 153: ...uning data H002 Motor constant selection 1 0 2 2 AT ONLINE DATA On line autotuning valid 0 MOTOR DATA General purpose motor 1 AT DATA Autotuning data H202 Motor constant Selection 2nd motor 1 0 2 2 AT ONLINE DATA On line autotuning valid H003 Motor constant R1 R1std Ω 0 000 9 999 Hyundai standard motor data H203 2nd Motor constant R1 R1std Ω 0 000 9 999 Hyundai standard motor data H004 Motor const...

Page 154: ...ning data Llstd mH 0 00 99 99 Autotuning motor data H012 Motor constant Io Autotuning data Istd A 0 0 999 9 Autotuning motor data H212 2nd Motor constant Io Autotuning data Istd A 0 0 999 9 Autotuning motor data H013 Motor constant J Autotuning data Jstd kg m 2 0 00 99 99 100 0 655 3 Autotuning motor data H213 2nd Motor constant J Autotuning data Jstd kg m 2 0 00 99 99 100 0 655 3 Autotuning motor...

Page 155: ... vector control F013 Motor voltage selection 220 440 V 200 240 380 480 200 215 220 230 240 200V class setting 380 400 415 440 460 480 400V class setting F015 Motor capacity Factory setting 1 5 75 1 5 2 2 3 7 5 5 7 5 11 15 18 5 22 30 37 45 55 75 F215 Second motor capacity Factory setting 1 5 75 1 5 2 2 3 7 5 5 7 5 11 15 18 5 22 30 37 45 55 75 F016 Motor pole selection 4 pole 2 12 2 4 6 8 10 12 F216...

Page 156: ...alid 1 VALID NOT ROT Valid the motor does not rotate H001 Autotunig selection 0 0 2 2 VALID IN ROT Valid the motor rotates 0 MOTOR DATA General purpose motor 1 AT DATA Autotuning data H002 Motor constant selection 1 0 2 2 AT ONLINE DATA On line autotuning valid H009 Motor constant R1 Autotuning data R1std Ω 0 000 9 999 Stator resistor H010 Motor constant R2 Autotuning data R2std Ω 0 000 9 999 Roto...

Page 157: ...d and excute autotuning by itself In this case as inertia motor J is motor itself add the motor shaft converting value to inertia motor z In the machine restricted the motor shaft revolution permit elevator ball screw and so on the mode H001 1 VALID NOT ROT should be selected in which operates autotuning without rotating Sometimes the motor can rotate in spite of selecting 1 VALID NOT ROT in H001 ...

Page 158: ...rred during the autotuning the autotuning is forced to terminate Abnormal termination is not displayed The display of a trip has priority After eliminating the cause of the trip execute the autotuning again If the autotuning is interrupted by power off with the stop key or turning the run command off the constant for autotuning may be stored After making an initialization and reset the setting ran...

Page 159: ... is executed after DC braking operation terminates 4 Setting method Set the motor constant selection H002 H202 to the data of autotuning that is valid 2 AT ONLINE DATA online tuning Give the autotuning selection H001 as the ineffectiveness 0 Input the run command 12 3 Sensorless vector control SLV 1 This function is the method that the revolution of motor and output torque are estimated by output ...

Page 160: ...07 H207 H013 H213 At deceleration Unstable of motor rotation Set Motor constant J smaller for preset constant H007 H207 H013 H213 During torque limit Insufficient torque during torque limit at low speed Set overload restriction level lower than torque limit level b031 C007 C010 At low frequency operation Irregular of rotation Set Motor constant J bigger for preset constant H007 H207 H013 H213 NOTE...

Page 161: ...t using RS232 485 protocol 1 1 Fig 13 2 RS485 port specification Control terminal PCB Abbreviation name Description Abbreviation name Description RXP Transmission and Reception side for RS485 232 JP1 Terminal resistance valid invalid CAN communication RXN Transmission and Reception side for RS485 232 JP2 Terminal resistance valid invalid RS485 232 communication X1 Transmission and Reception side f...

Page 162: ...hod RS485 communication requires a termination resistor The N700 has built in terminal resistor that by shorting JP2 jumper the termination resistor of the control terminal is valid and enables to control the reflection of a signal Refer to clause 13 1 Communication function on page 139 The following setting are required to operate RS485 communication Note If the data commend setting is communicat...

Page 163: ...esponse Cycle method is used in the communication The communication network is controlled by the master equipment and it is operated by the method that the slave equipment reply from the transmission request of the master equipment ModBUS communication frame type and form is as follows 13 2 1 Inverter read frame It requires 1 8 parameters of Inverter 1 External controller transmit frame Communicat...

Page 164: ...r 8bit of 16bit CRC Table 13 5 Inverter response frame Frame size 5byte Communication number Command Request Byte CRC H CRC L Request parameter number ⅹ2byte Data1 Data2 Data N 13 2 2 Request frame for setting parameter Setting 1 parameter and command note3 of Inverter 1 External transmit frame Communication number Order Parameter Data CRC Hi CRC Lo Clause Description Data size Specifications Comm...

Page 165: ...ponse frame 3 Parameter setting Basic parameter 1st byte Each group is setting Group 1st byte Group 1st byte D 0x01 O 0x07 F 0x02 C 0x08 U 0x03 H 0x09 A 0x04 P 0x0a B 0x05 I 0x06 Table 13 8 Basic parameters 1st byte 2nd byte Parameter number setting Ex The case of A60 parameter reading or writing 1st byte 0x04 2nd byte 0x3C Trip information Trip information is 4 parameters output frequency output ...

Page 166: ...stor error 9 Under voltage 25 Abnormal brake 10 26 Communication error 11 27 Over time of reset input 12 External trip 28 IGBT protection U phase 13 USP error 29 IGBT protection V phase 14 Ground fault voltage 30 IGBT protection W phase 15 31 Option 1 2 error 16 Temporary power loss protection 32 Over speed error Table 13 10 Trip information items 4 Data value setting Data value is transmitted exc...

Page 167: ...Ex The case of output frequency command is 60 Hz Data 6000 transmit 1st byte 0x17 2nd byte 0x70 Note Response frame when you send a command for setting a parameter When the data cannot be stored due to the attempt to store data while the unit is running the setting data will not be stored and the original data will be responded 16bit CRC generation The step of CRC 16 generation is as follows z All...

Page 168: ...1 1111 1111 1111 1 Polynomial 1010 0000 0000 0001 1001 1111 1111 1110 Shift3 0100 1111 1111 1111 Shift4 0010 0111 1111 1111 Polynomial 1010 0000 0000 0001 1000 0111 1111 1110 Shift5 0100 0011 1111 1111 Shift6 0010 0001 1111 1111 1 Polynomial 1010 0000 0000 0001 1000 0001 1111 1110 Shift7 0100 0000 1111 1111 Shift8 0010 0000 0111 1111 1 Polynomial 1010 0000 0000 0001 1000 0000 0111 1110 Byte1 6 CRC...

Page 169: ...d when the inverter power is restored while running Valid when the USP function is selected E13 USP ERR Ground fault protection When power is turned ON this detects ground faults between the inverter output and the motor E14 GND FLT Temporary power loss protection When an instantaneous power failure occurs for more than 15ms the inverter output is switched off Once the instantaneous power failure ...

Page 170: ...devices output phase W E30 WIGBT ERR Option error These indicate the error of option PCB 1 2 You can refer to the details of option PCB s instruction manual E31 OPT ERR Over speed error This is displayed when the motor rotation speed exceeds E32 RESVD Table 14 1 Protection function List Note When a trip occurs please proceed with reset operation after that you first find the cause of the fault 14 ...

Page 171: ...eling of paint Never clean the display part of the digital operator with detergent on alcohol 15 1 3 Regular inspection Inspections should be regularly carried out on the parts that can t be inspected while the inverter is running 1 Is there any trouble with the cooling system Cleaning of air filter etc 2 Check that all screw terminals and fixings are tight as they may loosen due to vibration or t...

Page 172: ...B and earth terminal with megger 2 Incremental clamping 3 Watch 1 To be over 5M ohm 2 3 No abnormality DC500V class megger Connection conductor electric line 1 Is there warp in conductor 2 Is there any damage of coating of wires O O 1 2 By watching 1 2 No abnormality Terminals Is there any damage O By watching No abnormality Inverter parts converter parts Resistance check between each terminal O T...

Page 173: ...ing smooth 2 No abnormality Display 1 Is the LED lamp illuminated 2 Cleaning O 1 Lamp indicates lamp on operator 2 Cleaning with cloth 1 Confirm light Display Meter Is direction value Normal O O Confirm indication value of board meter Satisfy normal value control value Voltage meter current meter Whole 1 Is there abnormal signal abnormal sound 2 Is there any abnormal occur O O 1 By hearing feeling...

Page 174: ...mmended to be replaced every 5 years And if the inverter is used in a worse condition this recommended replacing period is reduced 15 5 Megger test 1 When executing a megger test on the inverter remover all wires to R S T PD N RB U V and W 2 Do not use a megger or buzzer on the control circuit only use a digital multi meter Megger Voltage 500V DC 3 Execute megger test is complete reconnect the J61...

Page 175: ...s Note 2 Almost infinite value is indicated on no conducting With the effect of the smoothing capacitor the inverter conducts instantly and an infinite value isn t indicated Ohm number 10 ohms is indicated on conducting The values indicated will not be exactly the same for each terminal however they will be very close together If there is a significant difference a problem may exist Pole of tester...

Page 176: ...0 ⅹ250 400ⅹ610ⅹ260 440ⅹ650 ⅹ271 Table 16 1 Standard specification list 200V class 16 1 2 400V Class INVERTER MODEL N700 055HF N700 075HF N700 110HF N700 150HF N700 185HF N700 220HF N700 300HF N700 370HF N700 450HF N700 550HF N700 750HF N700 900HF N700 1100H F N700 1320H F Max Applicable Motor 4P 5 5 7 5 11 15 18 5 22 30 37 45 55 75 90 110 132 400V 8 3 11 0 15 9 22 1 26 3 33 2 41 9 50 2 63 0 76 2 1...

Page 177: ... Input current 4 20mA Input impedance 180Ω Operator Run Stop key Forward Reverse function mode Extend signal Forward run stop 1a connect 1b selection possibility 3wire input possibility Run Stop Extend port Setting with RS485 communication Intelligent input terminal FW and 8 terminal selection REV Reverse CF1 CF4 Multi speed bit 1 4 JG jogging DB External dc braking SET2 2nd control 2CH 2nd accele...

Page 178: ...g point Analog meter adjustment Starting frequency Carrier frequency adjustment Electronic thermal Free setting External start end frequency rate Analog input selection Trip retry Reduced voltage start Overload restriction Restarting after an instantaneous power failure Various kinds signal output Initialization value setting Automatic deceleration at the time of the power supply block AVR functio...

Page 179: ...ion 1 Model N700 055LF 055HF N700 075LF 075HF N700 110LF 110HF Fig 16 1 Dimension of model N700 055LF 055HF N700 075LF 075HF N700 110LF 110HF 2 Model N700 150LF 150HF N700 185LF 185HF N700 220LF 220HF Fig 16 2 Dimension of model N700 150LF 150HF N700 185LF 185HF N700 220LF 220HF ...

Page 180: ...ructions and Parts Manual 16 Specification 159 3 Model N700 300LF 300HF Fig 16 3 Dimension of model N700 300LF 300HF 4 Model N700 370LF 370HF N700 450LF 450HF Fig 16 4 Dimension of model N700 370LF 370HF N700 450LF 450HF ...

Page 181: ...00 Operating Instructions and Parts Manual 16 Specification 160 5 Model N700 550LF 550HF Fig 16 5 Dimension of model N700 550LF 550HF 6 Model N700 750HF 900HF Fig 16 6 Dimension of model N700 750HF 900HF ...

Page 182: ...N700 Operating Instructions and Parts Manual 16 Specification 161 7 Model N700 1100HF 1320HF Fig 16 7 Dimension of model N700 1100HF 1320HF ...

Page 183: ......

Page 184: ...REVISION HISTORY FOR N700 OPERATING INSTRUCTIONS AND PARTS MANUAL No Revision contents Date of issue Version No 1 Initial release of manual OCT 2008 HHIS WZ PE 070 00 ...

Page 185: ......

Page 186: ...DON 2ND FLOOR THE TRIANGLE 5 17 HAMMERSMITH GROVE LONDON W6 OLG U K TEL 44 20 8600 7127 FAX 44 20 8741 5620 4571 TOKYO 8TH FL YURAKU CHO DENKI BLDG 1 7 1 YURAKU CHO CHIYODA GU TOKYO JAPAN 100 0006 TEL 81 3 3212 2076 3215 7159 FAX 81 3 3211 2093 3216 0728 CAIRO APARTMENT NO 503 5TH FL BUILDING NO 7 BLOCK 2 9TH DIVISION EL NASR ROAD NEW MAADI CAIRO EGYPT TEL 20 2 520 0148 9 FAX 20 2 754 7528 SOFIA 4...

Reviews: