Installation Instructions

Optical Smoke Switch ORS 142

 1 Safety instructions

Smoke Switches are used for fire safety and must be 
tested for correct operation after installation. If they 
are not correctly installed, proper operation cannot 
be guaranteed.
Any special national or regional regulations must be 
observed.
The sensing chamber of the Smoke Switch must not 
be opened.

2 Application

The Optical Smoke Switch ORS 142 detects both 
smouldering and open fires with smoke emission. 
An additional temperature sensor reacts at a tem-
perature of about 70°C. In the event of an alarm, a 
fault, or a power failure, a relay contact opens. The 
accessories include a mains unit NG 519 and control 
unit NAG 03 for power supply and additional control 
tasks (see Section 8 “Ordering data”).

  In places with background interference such 

as steam, dust, dew formation, or smoke 
from a production process, we recommend 
use of our Heat Switch TDS 247 (see Section 
8 “Ordering data”).

3 Additional functions

In addition, the evaluation electronics of the ORS 
142 monitor the sensing chamber of the detector 
for slight contamination, heavy contamination, and 
faults. The ORS 142 provides visual indication of 
its status. By means of a communication interface, 
the various operating conditions can be read out 
and individually processed using the status indica-
tor RZA 142. An auto drift compensation ensures a 
constant  difference between the base signal and 
the alarm threshold.

4 Mounting and electrical connections

The Smoke Switch ORS 142 must be mounted as 
shown in the following illustrations. It must only be 
mounted on a horizontal surface.

4.1 Mounting dimensions

Dimensions of Smoke Switch ORS 142 without base:

4.2 Electrical connections

Any commercially-available cable can be used. For 
installations in which severe electromagnetic inter-
ference is to be expected, we recommend the use of 
screened cables.
Recommended conductor cross-section: 0.6 ... 0.8 
mm
Terminal assignment in base for ORS 142:

1

18 V DC to 28 V DC

2

GND

3

Communication interface

4

Relay contact

5

Relay contact

6

free

Ø 80 mm

33

m