•  Disconnect power at the circuit breaker(s) or disconnect switch(es) before beginning 

installation or servicing.

•  More than one circuit breaker or disconnect switch may be required to de-energize the 

equipment before servicing.

•  Do not use the manual off position of the timer for equipment servicing. Always discon-

nect the power at the circuit breaker(s) or disconnect switch(es).

•  Use COPPER conductors ONLY.

•  For 40 amp loads, use #8 AWG wire, rated 90˚C min.

•  Wire in accordance with national and local electrical code requirements. 

DTMV40 Series

  

Time Initiated, Temperature, 

Pressure or Time Terminated Multi-Voltage 

40A Defrost Timers

        WARNING

Risk of Fire or Electric Shock

•  Rotate timer dial clockwise only.

        CAUTION

Risk of Damage to Timer

1

Paragon

Precision

TIME INITIATED, TIME TERMINATED

Grasslin

Mode Selection Wiring Diag.

TIME INITIATED, PRESSURE TERMINATED

(Separate Pressure Switch Required (see instructions)

TIME INITIATED, REMOTE TEMPERATURE OR

PRESSURE TERMINATED

STARTUP PROCEDURE

1. Determine model to be replaced (Grasslin or Competitors)

from table below.

2. Set Mode Selection (S1 BLUE DIP Switch

– Fig. A) See table below and instructions
on page 5. 

3. Apply corresponding Terminal

Identification and Door labels –see retrofit
kit instructions.

4. Set correct input voltage (S2 RED DIP

Switch – Fig. B).

5. Follow installation and programming instructions.

The DTMV40 can be configured for
either 120 or 208/240VAC. Locate RED
DIP Switch to the right of timer module.
For:
• 120VAC slide DIP switch UP
• 208/240VAC slide DIP switch DOWN

TImer Mechanism

Step 2

Interior

Protective

Cover

Step 1

Ground Lug

2-1/2”

6-1/8”

INSTALLATION

Note: For outdoor locations, raintight, or wet location conduit
hubs that comply with requirements of UL 514B (standard for
fittings for conduit and outlet boxes) are to be used.
1. Open  door  and  then  remove  interior  protective  cover  by

releasing spring clip on bottom.

2. Remove timer mechanism by releasing spring clip on bot-

tom.

3. Select knockouts to be used. Remove inner 1/2” knockout

by inserting a screwdriver in the slot and carefully punch
knockout loose. Remove slug. If 3/4” knockout is required,
remove  the  outer  ring  with  pliers  after  removing  the  1/2”
knockout. Smooth edges with knife if necessary.

4. Place enclosure in desired mounting location and mark the

three  mounting  holes  (refer  to  diagram below).  Start  by 
placing set  screw  on  top  and  attaching  enclosure  over 
keyhole: then screw in remaining two screws on bottom.

5. Connect  conduit  hubs  to  conduit  before  connecting  the

hubs to the enclosure. After inserting hubs into enclosure,
carefully tighten hub lock nut. Do not over-torque.

6.

Verify voltage selection. 120VAC – position switch UP;
208/240VAC – position switch DOWN (refer to Fig. B)

.

7. Wire in accordance with National and Local Codes.
8. Grounding:  Terminate  all  ground  wires  to  ground  lug  on

bottom of enclosure.

9. Replace  interior  pro-

tective cover. 

UL TYPE 3R Enclosure

Bracket Mount

Input Voltage Switch (S2)

Mode Selection Switch (S1)