Standby Power Rating                                                                       Prime Power Rating

350 KW 60 Hz                                                                                     280 KW  60 Hz

n

 

The  Generac Modular Paralleling system utilizes
multiple small generators in a side by side parallel
arrangement to achieve a larger combined power
output.

n

 

The proven 13.3 liter  Generac generators can be
combined up to 10 units to provide from 300 kW to 1
megawatts of reliable power.

n

 

Paralleling System Features.  The paralleling function is
controlled by  Generac’s field proven Power Manager
Control utilizing contractor switching technology
resulting in cost effective reliable paralleling.  The MPS
control system provides automatic synchronization,
adjustable load sharing between generators, reverse
power protection and load shedding contacts.

n

 

The optional cable interconnect cabinet is furnished with
bus bar and lugs to allow easy cabling between the
multiple gensets. Recommended for 3 or more gensets.

n

 

The  Generac “Power Manger Generator controller”
provides complete engine monitoring and control along

       with alarm function and communication ability via a
       RS232 with  a modem link to Generac’s Genlink
       software or Modbus control.   A RS485 link is also
       available.

n

 

Flexibility.  The Modular Power systems flexibility allows
for a wide variety of configurations, including single or
multiple automatic transfer switch arrangements roof
application where better weight distribution is required
and areas with specific height or depth limitations.
Since MPS gensets need not be located together, space
can be utilized wherever it is available.  Smaller units
are also easier to transport and place on the jobsite.

n

 

Redundancy. N+1 means greater reliability with MPS.
Backup power during scheduled maintenance.
Simplified service which reduces maintenance costs.

n

 

Single source service response from Generac’s dealer
network provides parts and service support for the entire
unit.  You are never on your own when you own a
Generac Power System

GEN

Diesel Generator

Circuit
Breaker

Contactor

Contactor

Diesel Generator

Circuit
Breaker

GEN

Transfer Sw

W/ Integral

Control

UTILITY

Distribution
Cab

Contactor

Diesel Generator

Contactor

Circuit
Breaker

Circuit
Breaker

Diesel Generator

GEN

GEN

UTILITY

ATS

UTILITY

ATS

Distribution 
Cab

Distribution 
Cab

  PMSC

Controller

 Cabinet

Control Wires

            Power Manager Integrated Controller Layout                           Power Manager System Controller Layout

FEATURES

Modular Power
System   (MPS)

         

           

        

Powered with Generac’s 13.3 Natural Gas Engine

MPSG350

   350 kW

®

Summary of Contents for MPSG350

Page 1: ...85 link is also available n Flexibility The Modular Power systems flexibility allows for a wide variety of configurations including single or multiple automatic transfer switch arrangements roof application where better weight distribution is required and areas with specific height or depth limitations Since MPS gensets need not be located together space can be utilized wherever it is available Sm...

Page 2: ...8 W x 24 D 1600 Amp 80 H x 48 W x 48 D 2600 3200 Amp Wire access top side bottom NEMA 3R or 4X Optional Wt 1250 lbs 1000 1600 Amp 1850 lbs 2600 3200 Amp Connection Cabinet Optional NEMA 12 3R 80 H x 48 W x 48 D Lug capacity 16 for Generator Controller GC 12 for ATS Each lug accepts 4 4 to 750 MCM see Dwg OD4482 Floor mounting Aluminum or Copper Wire compatible 4500 amp bus Sequence of Operations 1...

Page 3: ...90 120 208 Motor Starting 277 480 600 421 1 200 kW 1 150 kW TOTAL SYSTEM PARAMETERS 50 Neg Sequence Reactance Time Constant Seconds Max Harmonics Efficiency Output Voltage 60 Hz Alternator Parameters Sub Transient Reactance 526 Transient Reactance Synchronous Reactance Alternator Models 75 25 60 Load 1128 Exhaust Flow FL 120 º F Exhaust 1174 cfm Total 618 cfm 556 cfm 4017 CFM for the 2 units 2257 ...

Page 4: ...laced end to end side by side or wherever room is available The transfer switch or switches are generally placed close to the main electric service Consult State Federal and Local codes for specific installation requirements Power Connections are in one area in the left rear quadrant of the genset All controls are through a single 2 wire RS485 connection that can be daisy chained between generator...

Reviews: