DESIGN & TECHNICAL MANUAL

SINGLE

INDOOR

OUTDOOR

AO

A30LBTL  AO

A30LFTL

AO

A36LBTL  AO

A36LFTL

AU

A30LBLU

AU

A36LBLU

AIR CONDITIONER

Cassette type

Summary of Contents for AO*A30LBTL Series

Page 1: ...DESIGN TECHNICAL MANUAL SINGLE INDOOR OUTDOOR AO A30LBTL AO A30LFTL AO A36LBTL AO A36LFTL AU A30LBLU AU A36LBLU AIR CONDITIONER Cassette type ...

Page 2: ...1 INDOOR UNIT D2D_AU034E 04 2010 07 07 CASSETTE TYPE AU A30LBLU AU A36LBLU ...

Page 3: ... 1 AIR VELOCITY DISTRIBUTION 01 12 7 2 AIR FLOW 01 17 7 3 FRESH AIR 01 19 7 4 DUCT CONNECTION 01 20 8 OPERATION NOISE 01 22 8 1 NOISE LEVEL CURVE 01 22 8 2 SOUND LEVEL CHECK POINT 01 23 9 ELECTRIC CHARACTERISTICS 01 24 10 SAFETY DEVICES 01 25 11 EXTERNAL INPUT OUTPUT 01 26 11 1 EXTERNAL INPUT 01 26 11 2 EXTERNAL OUTPUT 01 27 12 FUNCTION SETTING 01 29 12 1 INDOOR UNIT 01 29 12 2 WIRED REMOTE CONTRO...

Page 4: ...ption of new type turbo fan Improvement of air stream Adoption of high efficiency turbo fan High efficiency achieved by equaling the performance of the wing and air passing the heat exchanger Improvement of the flap Making space between the ceiling the air flows far wide and ceiling does not get dirty Rear part Front part Ceiling Round Flap Much less temperature irregularity happens by spreading a...

Page 5: ...RAIN CAP DRAIN COVER Easy installation z z Easy setting by wired remote controller Improvement of installation maintenance z z Adjustment of nut is possible after installation Mounting position of body can be fine adjusted after Decoration panel mounting Grille corner Adjustment can be done just taking off the corner part Wide powerful airflow The wind is widely delivered by a high efficiency fan ...

Page 6: ...lter Cooling room temperature correction z z Heating room temperature correction z z Auto restart z z The units restart automatically when the current was returned even when there was a power interruption during operation Room temperature sensor switching z z Switches from room temperature judgment by room temperature sensor attached to indoor unit body to room temperature judgment by room tempera...

Page 7: ...ned in one unit Built in timers z z Wired remote controller Weekly timer Setback timer Weekly timer Setback timer At Weekly timer Set back timer setup Easy to understand operation z z Variable timer control The operation display sections are zoned according to time and operation enabling variable programming to match application Simple installation z z Components are compatible with standard switc...

Page 8: ... Temporarily cancels of one day timer 8 Set back button Pressed to select the set back timer 9 Set time button Pressed to set time 10 Delete button The schedule of a weekly timer is deleted 11 Set button Sets the date hour minute and on off time 12 Vertical airflow direction and swing button Push for two seconds to change the swing mode 13 Horizontal airflow direction and swing button Push for two...

Page 9: ...32 32 Heating High 40 43 Med 38 38 Low 36 36 Quiet 32 32 Heat exchanger type Dimensions H W D mm 252 2030 26 6 252 2093 26 6 252 2030 26 6 252 2093 26 6 Fin pitch 1 2 1 2 Rows x Stages 2 12 2 12 Pipe type Copper Copper Fin type Aluminium Aluminium Enclosure Panel Material HIPS Colour WHITE Approximate colour of MUNSELL N 9 25 Dimensions H W D NET Unit mm 288 842 842 Panel 50 950 950 Gross Unit 360...

Page 10: ...lt pitch 860 910 mm Ceiling opening 950 mm Panel frame m m 5 4 0 2 m m 5 4 0 2 840 mm Body frame 860 910 mm Ceiling opening 60 mm 278 mm 358 mm 140 mm 180 mm 200 mm Drain pipe Connect the attached drain hose 88 mm 70 mm 2 5 mm hole 2 5 mm hole 250 mm 352 mm 100 mm 83 mm 83 mm 90 mm 100 mm m m 5 8 1 m m 5 8 1 Airflow split flow duct connecting port Airflow split flow duct connecting port Airflow sp...

Page 11: ...s the air outlet shutter plate UTR YDZC sold separately must be installed and outlet direction switched to 3 way by remote controller 1 500 or more 1 000 or more 1 800 or more Obstruction 3 000 or more Strong and durable ceiling Floor Ceiling mode Low 2 7 m Ceiling mode Standard 3 2 m Ceiling mode High 3 6 m 30 model 4 2 m 36 model 100 or more ...

Page 12: ... 01 09 CASSETTE TYPE AU A30 36L CASSETTE TYPE AU A30 36L WIRING DIAGRAMS 555 MODEL AU A30L AU A36L ...

Page 13: ... 7 69 3 54 40 6 16 5 13 2 94 6 86 5 16 2 99 7 09 5 61 3 01 7 56 5 63 3 04 7 80 6 08 3 05 8 26 6 05 3 08 8 73 6 45 3 11 46 5 44 4 92 2 91 6 06 4 95 2 96 6 27 5 39 2 97 6 68 5 40 3 00 6 89 5 83 3 02 7 30 5 81 3 05 7 71 6 19 3 08 AFR 30 0 Indoor temperature CDB 18 21 23 25 27 29 32 CWB 12 15 16 18 19 21 23 Outdoor temperature CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 1...

Page 14: ... 44 11 25 3 51 10 96 3 57 15 10 10 86 2 52 10 60 2 57 10 34 2 62 10 09 2 67 9 83 2 71 20 15 10 87 2 23 10 61 2 28 10 35 2 33 10 09 2 37 9 83 2 41 24 18 11 31 2 25 11 04 2 30 10 78 2 34 10 51 2 39 10 24 2 43 AFR 30 0 Indoor temperature CDB 16 18 20 22 24 Outdoor temperature CDB CWB TC PI TC PI TC PI TC PI TC PI 15 16 9 63 3 92 9 40 4 00 9 17 4 08 8 94 4 17 8 71 4 25 10 11 9 70 3 96 9 47 4 04 9 24 4...

Page 15: ...dition Fan speed High Operation mode FAN Ceiling mode Standard 5 4 3 2 1 0 1 2 3 4 5 Unit m s m m TOP VIEW VERTICAL LOUVER Upward 3 2 2 1 0 Unit m s m m SIDE VIEW VERTICAL LOUVER Upward 3 2 2 1 0 Unit m s m m SIDE VIEW VERTICAL LOUVER Downward 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 ...

Page 16: ...FAN Ceiling mode Standard 5 4 3 2 1 0 1 2 3 4 5 Unit m s m m TOP VIEW VERTICAL LOUVER Upward 3 2 2 1 0 Unit m s m m SIDE VIEW VERTICAL LOUVER Upward 3 2 2 1 0 Unit m s m m SIDE VIEW VERTICAL LOUVER Downward 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 ...

Page 17: ...FAN Ceiling mode Standard 5 4 3 2 1 0 1 2 3 4 5 Unit m s m m TOP VIEW VERTICAL LOUVER Upward 3 2 2 1 0 Unit m s m m SIDE VIEW VERTICAL LOUVER Upward 3 2 2 1 0 Unit m s m m SIDE VIEW VERTICAL LOUVER Downward 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 ...

Page 18: ...FAN Ceiling mode Standard 5 4 3 2 1 0 1 2 3 4 5 Unit m s m m TOP VIEW VERTICAL LOUVER Upward 3 2 2 1 0 Unit m s m m SIDE VIEW VERTICAL LOUVER Upward 3 2 2 1 0 Unit m s m m SIDE VIEW VERTICAL LOUVER Downward 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 ...

Page 19: ...MODEL AU A36L 4 way air outlet z z Note Condition Fan speed High Operation mode FAN Ceiling mode Standard 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 m Unit m s 3 2 2 1 0 m SIDE VIEW VERTICAL LOUVER Special upward m SIDE VIEW VERTICAL LOUVER Special upward Unit m s m 3 2 2 1 0 ...

Page 20: ...n speed Number of rotations r p m Airflow HIGH 570 m3 h 1600 l s 444 CFM 942 MED 510 m3 h 1400 l s 389 CFM 824 LOW 470 m3 h 1270 l s 353 CFM 747 QUIET 420 m3 h 1150 l s 319 CFM 677 Fan speed Number of rotations r p m Airflow HIGH 640 m3 h 1800 l s 500 CFM 1059 MED 510 m3 h 1400 l s 389 CFM 824 LOW 470 m3 h 1270 l s 353 CFM 747 QUIET 420 m3 h 1150 l s 319 CFM 677 ...

Page 21: ...ns r p m Airflow Max Min HIGH 610 m3 h 1550 1350 l s 431 375 CFM 912 794 MED 550 m3 h 1350 1200 l s 375 333 CFM 794 706 LOW 510 m3 h 1250 1100 l s 347 306 CFM 736 647 QUIET 460 m3 h 1100 950 l s 306 264 CFM 647 559 Fan speed Number of rotations r p m Airflow Max Min HIGH 680 m3 h 1700 1550 l s 472 431 CFM 1000 912 MED 550 m3 h 1350 1200 l s 375 333 CFM 794 706 LOW 510 m3 h 1250 1100 l s 347 306 CF...

Page 22: ...xible duct 2 Fan 2 Insulation 1 250 mm 185 mm 2 5 mm hole 4 70 mm 62 mm 62 mm Fresh air inlet position A View A Fresh air inlet position Refrigerant pipe Drain pipe 1 In case of fresh air intake please remove the insulation 2 Locally procured parts 98 49 0 10 8 6 4 2 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Air flow m3 min Duct static pressure Pa Duct static pressure mmAq Duct Inside Dia ø70mm Static press...

Page 23: ...1 0 0 2 4 6 8 10 12 14 Duct static pressure mmAq Air flow m3 min AU A36L Duct static pressure Pa Fan speed High Fan speed Quiet L 10m L 5m L 1m 98 49 0 10 9 8 7 6 5 4 3 2 1 0 0 2 4 6 8 10 12 14 Duct static pressure mmAq Air flow m3 min AU A30L Duct static pressure Pa Fan speed High Fan speed Qutiet L 10m L 5m L 1m Duct Inside Dia 350mm 100mm L ...

Page 24: ...tern when a branch duct is installed Bi directional branching main unit bi directional branching z zOnce the location where the duct is to be connected is decided always be sure to close the outlets in the same direction A B C D Close Close Branch Branch Close Close Branch Branch DUCT Locally procured parts Close the outlet here Use only after closing the outlet of the cassette on the side on whic...

Page 25: ...d sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 MODEL AU A36L Cooling z z NC 65 NC 60 NC 55 NC 5...

Page 26: ... 01 23 CASSETTE TYPE AU A30 36L CASSETTE TYPE AU A30 36L SOUND LEVEL CHECK POINT 88888 Microphone Microphone CENTER 1 5m ...

Page 27: ...ELECTRIC CHARACTERISTICS 999 Model Name AU A30L AU A36L Power Supply Voltage V 230V Frequency Hz 50Hz Max Operating Current Indoor unit A 0 7 Wiring Spec Indoor unit to outdoor unit Circuit breaker A 0 8 Connection Cable mm2 1 5 2 5 Limited wiring length m 51 ...

Page 28: ...TYPE AU A30 36L CASSETTE TYPE AU A30 36L SAFETY DEVICES 1111 Protection form Model AU A30L AU A36L Circuit protection Current fuse PCB 3 15A 250V Fan motor protection Thermal protection program 110 15 C OFF 105 15 C ON ...

Page 29: ...r power turned on Starting other than at the left Operation mode Auto changeover Mode at previous operation Set temperature 24 C Temperature at previous operation Air flow mode AUTO Mode at previous operation Up down air direction swing Standard air direction swing OFF Air direction at previous operation Left right air direction swing Standard air direction swing OFF Air direction at previous oper...

Page 30: ...iagram example z z Field supply Ex Display Indoor control PC board Connected unit Ex Relay unit 1 2 Signal Relay power supply V Connector Make the distance from the PC board to the connected unit within 10m Relay spec Max 24VDC 10mA to less than 500mA 10 m 24V DC ON OFF Operation Stop Indoor unit Output signal Parts Optional z z Model name UTY XWZX Wire External output ...

Page 31: ... Connector 1 12 V on off 2 Signal Relay power supply Make the distance from the PC board to the connected unit within 10m Relay spec Rated 12VDC 50mA or less Ex Fan Connected unit Ex Relay unit 10 m ON OFF Operation Stop Indoor fan Output signal Parts Optional z z Model name UTD ECS5A Wire Fresh air output The wire fresh air output for connecting the fresh air intake kit optional parts is attached...

Page 32: ...gnal code INDOOR UNIT DIP SW 1 Setting forbidden 2 3 4 Jumper Wire JM1 Remote control unit signal code JM2 JM3 Setting forbidden JM3 JM2 JM1 Indoor unit Printed circuit board MAIN PCB Indoor unit setting Factory setting Jumper wire Remote control unit signal code JM 1 JM 2 Connect Connect A Disconnect Connect B Connect Disconnect C Disconnect Disconnect D ...

Page 33: ...of the settings stored in memory will be deleted if there is a power failure DIP SW 1 Can not be used Do not change 2 Dual remote controller setting 3 Can not be used Do not change 4 Can not be used Do not change 5 Can not be used Do not change 6 Memory backup setting ON ON OFF 1 2 3 4 5 6 Front case back side Do not use this DIP Switch DIP Switch Factory setting Number of remote controller Master...

Page 34: ...BACK SU MO TU WE TH FR SA Unit number of INDOOR UNIT 3 Press the set time buttons to select the function number Function number SU MO TU WE TH FR SA 4 Press the set temperature buttons to select the setting value The display flashes as shown to the right during setting value selection 5 Press the TIMER SET button to confirm the setting Press the TIMER SET button for a few seconds until the setting...

Page 35: ...rature Sensor Switching Function Wired remote controller only Setting Description Function Number Setting Value No 42 00 Yes 01 If setting value is 00 room temperature is controlled by the indoor unit temperature sensor If setting value is 01 room temperature is controlled by either indoor unit temperature sensor or remote control unit sensor Setting record Record any changes to the settings in th...

Page 36: ...height behind the ceiling is low Normal behind the ceiling installation height is 298mm IR Receiver kit UTY LRH A1 Unit control is performed by wireless remote controller Wired remote controller UTB UD Unit control is performed by wired remote controller Insulation kit for high humidity UTZ KXGA Install when the under roof condition is expected to be the humidity of over 80 and the temperature of ...

Page 37: ...CASSETTE TYPE AU A30 36L Exterior Parts name Model No Summary Fresh air intake kit UTZ VXGA It can be taken in fresh air of up to 10 of high air volume of the indoor unit by attaching Fresh Air Intake Kit to cassette type indoor unit ...

Page 38: ...D2D_AO022E 02 2010 01 18 SINGLE TYPE AO A30LBTL AO A30LFTL AO A36LBTL AO A36LFTL 2 OUTDOOR UNIT ...

Page 39: ... 4 WIRING DIAGRAMS 02 06 5 CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DEFFERENCE 02 09 6 ADDITIONAL CHARGE CALCULATION 02 11 7 AIR FLOW 02 12 8 OPERATION NOISE 02 14 8 1 NOISE LEVEL CURVE 02 14 8 2 SOUND LEVEL CHECK POINT 02 15 9 ELECTRIC CHARACTERISTICS 02 16 10 SAFETY DEVICES 02 17 ...

Page 40: ...3800 3800 Type Q ty Propeller 1 Motor output W 103 103 Sound pressure level Cooling dB A 53 54 Heating 55 55 Heat exchanger type Dimensions H W D mm 798 900 36 4 798 900 36 4 Fin pitch 1 30 1 30 Rows x Stages 2 38 2 38 Pipe type Copper Fin type Aluminium Compressor Type Q ty Twin Rotary 1 Motor output W 1700 Refrigerant Type R410A Charge g 2100 Refrigerant oil Type PVE Enclosure Material Steel she...

Page 41: ...pe Q ty Propeller 1 Motor output W 100 100 Sound pressure level Cooling dB A 53 54 Heating 55 55 Heat exchanger type Dimensions H W D mm 798 900 36 4 798 900 36 4 Fin pitch 1 30 1 30 Rows x Stages 2 38 2 38 Pipe type Copper Fin type Aluminium Compressor Type Q ty Twin Rotary 1 Motor output W 2100 Refrigerant Type R410A Charge g 2100 Refrigerant oil Type POE RB68 Enclosure Material Steel sheet Colo...

Page 42: ... 170 147 12 Top view Front view Side view Bottom view When there are obstacles at the back or front sides 600 mm or more 250 mm or more 250 mm or more 300 mm or more 600 mm or more 100 mm or more 300 mm or more 100 m m or m ore 250 mm or more Service space When there are obstacles at the back side s and top When there are obstacles at the back side with the installation of more than one unit ...

Page 43: ... 02 04 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L REFRIGERANT CIRCUIT 333 MODEL AO A30LB AO A36LB ...

Page 44: ... 02 05 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A30LF AO A36LF ...

Page 45: ... 02 06 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L WIRING DIAGRAMS 444 MODEL AO A30LB AO 36LB ...

Page 46: ... 02 07 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A30LF ...

Page 47: ... 02 08 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A36LF ...

Page 48: ... 0 966 0 954 0 939 0 920 10 0 983 0 966 0 954 0 939 0 920 20 0 966 0 954 0 939 0 920 30 0 954 0 939 0 920 HEATING Pipe length m 5 7 5 10 20 30 40 50 Height difference H m 1 Indoor unit is upper than outdoor unit 30 0 931 0 914 0 899 20 0 954 0 931 0 914 0 899 10 0 990 0 954 0 931 0 914 0 899 7 5 0 991 0 990 0 954 0 931 0 914 0 899 5 1 000 0 991 0 990 0 954 0 931 0 914 0 899 0 1 000 0 991 0 990 0 9...

Page 49: ... 966 0 954 0 939 0 920 20 0 966 0 954 0 939 0 920 30 0 954 0 939 0 920 HEATING Pipe length m 5 7 5 10 20 30 40 50 Height difference H m 1 Indoor unit is upper than outdoor unit 30 0 931 0 914 0 899 20 0 954 0 931 0 914 0 899 10 0 990 0 954 0 931 0 914 0 899 7 5 0 991 0 990 0 954 0 931 0 914 0 899 5 1 000 0 991 0 990 0 954 0 931 0 914 0 899 0 1 000 0 991 0 990 0 954 0 931 0 914 0 899 2 Indoor unit ...

Page 50: ...UNIT AO A30 36L ADDITIONAL CHARGE CALCULATION 666 MODEL AO A30LB AO A36LB AO A30LF AO A36LF REFRIGERANT CHARGE z z Refrigerant type R410A Refrigerant amount g 2100 Pipe length m 20 30 40 50 40g m Additional charge g 0 Chargeless 400 800 1200 ...

Page 51: ... MODEL AO A36LB COOLING z z HEATING z z Number of rotations r p m Air flow 850 m3 h 3600 l s 1000 CFM 2119 Number of rotations r p m Air flow 900 m3 h 3800 l s 1056 CFM 2236 Number of rotations r p m Air flow 950 m3 h 4000 l s 1111 CFM 2354 Number of rotations r p m Air flow 900 m3 h 3800 l s 1056 CFM 2236 ...

Page 52: ... AO A36LF COOLING z z HEATING z z Number of rotations r p m Air flow 850 m3 h 3600 l s 1000 CFM 2119 Number of rotations r p m Air flow 900 m3 h 3600 l s 1000 CFM 2119 Number of rotations r p m Air flow 950 m3 h 3800 l s 1056 CFM 2236 Number of rotations r p m Air flow 900 m3 h 3800 l s 1056 CFM 2236 ...

Page 53: ... 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HEATING z z Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15...

Page 54: ... 02 15 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L SOUND LEVEL CHECK POINT 88888 ...

Page 55: ...Committee E0005 3 Limited wiring length This is the wiring length in case voltage descent is less than 2 When the wiring length becomes long please select the wiring of a more larger diameter Model name AO A30LB AO A30LF AO A36LB AO A36LF Power supply Voltage V 230 Frequency Hz 50 1 Max operating current A 17 0 20 0 Starting current A 15 0 2 Wiring spec Main fuse Circuit breaker current A 30 Power...

Page 56: ...rent fuse FILTER PRINTED CIRCUIT BOARD 10A 250V Current fuse MAIN PRINTED CIRCUIT BOARD 3 15A 250V Fan motor protection Thermal protection program OFF 140 20 C ON 110 20 C High Pressure Protection Pressure Switch OFF 4 2 0 1MPa ON 3 2 0 15MPa Compressor protection Thermal protection program COMPRESSOR TEMP OFF 120 C ON 80 C Thermal protection program DISCHARGE TEMP OFF 110 C ON After 7 minutes ...