Step 7 :

 Time settings and basic operation

Step 6 :

 Option setup

Urinal Control System

 

Installation & Operating Instructions

UC07-001

PP00

-1

51

 2

70

61

9

PP00

-1

51

 2

70

61

9

On the board you will notice three in-line switches fitted to the 
right side of the DIP switches (Fig. 4). Only switch A is used.

Option switch A (when switched ON) provides two functions, a 
pre-flush and a purge option. 

The pre-flush opens the valve for 1 second after the first 2 
seconds of detection. This helps to prevent splashing by wetting 
the urinal bowl. After the pre-flush the timing continues.

The purge is initiated every 12 hours of non-use on either channel. 
This helps reduce smells from the urinal during periods of non-
use.

Settings:

Switch A ON = Pre-flush plus purge

Whilst the unit is still powered down the time settings can be 
setup.

The numbers printed on the switches (1, 2, 3, 4) simply identify 
the switch number; the actual time settings available are shown 
below:

Switch 1 ON = 1 seconds
Switch 2 ON = 2 seconds
Switch 3 ON = 4 seconds
Switch 4 ON = 8 seconds

Example above (Fig 5) shows switch 2 and 3 ON. This gives a total 
flush-time of 6 seconds

Testing the sensors

A test routine is included for verifying the operation of the 
sensors.

After installation of external equipment, the supply should be 
connected.

ON

12

34

To put the unit into test mode set DIP switches 1-4 to the OFF 
position. 

When power is applied LED’s 2 and 3 (Fig 2) will switch on 
corresponding to an object within range. For example, if sensor 
1 (left hand channel) detects and object in range then LED 3 (left 
hand LED) will be on as long as the sensor detects the object. 
Sensor 2 operates LED 2 as above. This routine helps to identify if 
the sensors are detecting unwanted objects.

Operation:

When a person comes into range of a sensor a counter starts 
and after 10 seconds it is determined that the person is an actual 
user.

When the person leaves the sensing range the corresponding 
valve is opened for the set flush-time. However, a 2 second delay 
is built into the counter to allow the person to leave the range 
and return after or before the 10 seconds without effect on 
the counter. This also means that the valve will not open for 2 
seconds after the user has left the area.
 
Each of the two channels operates independently, but both use 
the same settings.

Page

 4

IMPORTANT :

 Changes to settings can only take place when 

power has been disconnected for at least 5 seconds.

IMPORTANT :

 Changes to settings can only take place when 

power has been disconnected for at least 5 seconds.