INSTRUCTION 

MANUAL

DRIVER TMFE2 FOR TMFR-TSFR PUMP 

AND MOTOR UNIT

LEGEND

Puts in evidence the presence Indicates a warning of 
a dangerous voltage. Concerning a generic danger 
this symbol indicates a high or important operative 
notes. Voltage condition which may cause a serious 
accident or death. 

FOREWORD

REPAIRS NOTE

Repairs may be performed only by workshops authorized by 

Fluid-o-Tech who must use genuine spare parts.
Unauthorized repairs and the use of other spare parts can result 
in personal injuries and property damage as well as loss of UL 
approvals and safety functions, such as Safety Integrated.

Warning

 TMFR/TSFR units are used in high voltage 

installations and are operated at voltages that when 
touched can cause serious injuries or death!

PROPER USE

Note the following:

Warning 

This device may only be used as described 

in the catalog and in the technical description and 
only in connection with third–party devices and

 

components recommended or approved by Fluid-o-Tech.
To ensure trouble–free and safe operation of the product, it must 
be transported, stored and installed as intended and maintained 
and operated with care.

SAFETY INFORMATION

This documentation contains information that must be observed 
to ensure your personal safety and to prevent material damage. 
The instructions for your personal safety are marked by a warning 
triangle. Instructions relating solely to material damage are not 
marked by a warning triangle. The warnings appear in decreasing 
order of risk as given below.

Danger

 Indicates that death or serious injury will result 

if proper precautions are not taken.

Warning

 Indicates that death or serious injury may 

result if proper precautions are not taken.

Caution

 With a safety alert signal indicates that minor 

personal injury can result if proper precautions are not 
taken.

Without a safety alert symbol, indicates that property damage can 
result if proper precautions are not taken.

Notice

 Indicates that an undesirable result or state may arise if the 

relevant note is not observed.

Warning: leakage current 

as a result of the high 

switching frequencies, capacitances (parasitic and 
integrated) with respect to ground may cause leakage 
currents. This is the reason that a permanent 

PE connection is required.The presence of the filter implies 
an unavoidable increase of leakage current to the ground; it is 
therefore suggested the use of a proper differential switches with 
intervention for current ≥ 30 mA.

Warning: 

the TMFR/TSFR board control is not 

insulated from power network. The components 
of the inverter are under voltage when the unit 

is connected to main supply. Contact with this voltage 
can cause serious damage. The power supply of the 
inverter must be protected by a fuse or with an automatic 
cutout. Make sure that cables, especially ground wire, 
are fixed properly. Keep separate the power cables 
from the signal cables. Connect a spark quenching unit 
in parallel to relays coils, solenoid valves and remote control 
switches closely to the electronic, as in the following table:

Summary of Contents for TMFE2

Page 1: ...amage are not marked by a warning triangle The warnings appear in decreasing order of risk as given below Danger Indicates that death or serious injury will result if proper precautions are not taken Warning Indicates that death or serious injury may result if proper precautions are not taken Caution With a safety alert signal indicates that minor personal injury can result if proper precautions a...

Page 2: ...s must be taken into account All work should be undertaken with the system in a no voltage condition If this is not observed this can result in injury Warning The capacitors mounted in the unit have dangerously high voltage For this reason once the power cord has been disconnected it is necessary to wait three 3 minutes minimum before any service on the device ESDS information and instructions Ele...

Page 3: ...tamination of the cooling system in order to maintain proper cooling efficiency Supply system Switches contactors fuses Filter MicroProcessor Power module Pump Motor Sensoriess feed back Cable Choke Cable Filter optional Closed loop control Digital Analog Optional MODEL Input Inverter Nominal Out motor Motor Weight Standard Vac KW input current power Kg current A A FEXXEXXX 230V 10 0 25 1 8 0 9 Sa...

Page 4: ...ose proximity to the inverter storage temperature 20 C to 60 C Environment conditions ventilation natural circulation humidity from 20 to 90 without condensation altitude of installation max 2000 m u s l derating for higher altitudes protection IP 20 Type External connections Digital opto coupled LED orange Indication of Supply permanent Alarms blink Alerts Is located in the center of the main boa...

Page 5: ...eve max Conductor cross section stranded min 0 2 mm 1 5 mm Conductor cross section stranded max 2 5 mm Conductor cross section stranded with ferrule with plastic sleeve min Conductor cross section stranded with ferrule 0 25 mm Without plastic sleeve min Conductor cross section stranded with ferrule with plastic sleeve max 1 5 mm Conductor cross section AWG kcmil min 24 Conductor cross section AWG ...

Page 6: ...C NC NC 5 to 24 V polarity can be reversed 0 V polarity can be reversed NC NC SERVICE CONNECTOR TYCO 3 643814 7 OR EQUIVALENT 1 2 3 4 5 6 7 MODE OPTO DIGITAL EXTERNAL DIP MOTOR OFF ON 4 2 1 3 6 5 MOTOR ON DIP SWITCH SETTINGS see previous table 0V 0 5 to 24 V 1 PIN 3 DIP STATUS SERVICE Connector 0V 0 0V 0 PIN 4 SERVICE Connector FUNCTION MODE DIGITAL OPTO ON OFF 7 6 5 4 3 2 1 NC NC NC 5 to 24 V pol...

Page 7: ...STATUS ON 4 2 7 6 5 4 3 2 0 Vs 0 Vs A I 4 20 mA 0 Vs ON 5 V FAULT OUT Active low 1 3 6 5 DIP STATUS ON 4 2 7 6 5 4 3 2 1 NC 0 Vs A I PWM 5 to 95 TTL signal 0 Vs ON 5 V FAULT OUT Active low 5 Vs SERVICE CONNECTOR TYCO 3 643814 7 OR EQUIVALENT MODE ANALOG IN PWM COMMAND 100 10 000 Hz 1 3 6 5 TATUS 4 7 6 5 4 3 2 1 NC 0 Vs A I 0 5 V 0 Vs ON 5 V FAULT OUT Active low 5 Vs SERVICE CONNECTOR TYCO 3 643814...

Page 8: ...rature controller 4 Start up 5 Rotor blocked 6 Module Fault hardware 7 Over load power 8 Over current limit 50 more than the over load power In the picture below there is the diagram with the electronic characteristic of the Fault Signal It is active when low 0V When the TMFR TSFR unit runs correctly the FAULT signal is high 5V From µProcessor R 2 1 JP4 5 VField FAULT 0V Field 6 From µProcessor R ...

Page 9: ... over load power semi permanent alarm mode ELECTRIC INSTALLATION The power connection wires must be of appropriate section in proportion to the current absorbed in the specific application The cable shield must be connected to the ground both on the inverter and on the motor side The power cables must be separated from the control cables it is forbidden passing them in the same raceway It is impor...

Page 10: ......

Page 11: ...ncy 50 60Hz OUTPUT RATING Vn 180 Vac 3phase P N FEE2AWR1 99260905 02 I in 5 4 A rms In 1 89A rms W in 375 W 4 3110 in 4 7243 in 2 1692 in 4 2795 in Ø 23 82 5 3 25 in 36 5 57 2 24 in 114 4 49 in 38 1 5 in 90 3 54 in 125 4 92 in X X 4x Ø11 2 x 3 8 NPT 2 x 3 8 GAS TO CONTROLLER CARD BY CONNECTION CABLE X X 125 4 92 in 37 1 46 in 65 2 56 in Ø 0 91 in 1 44 in Ø 0 43 in ...

Page 12: ...garded The unit has been disassembled or modified by anyone other than a Fluid o Tech or authorized by Fluid o Tech engineer or repaired with non original components The unit operated dry or in cavitation throttled undersized inlet or filter Solid extraneous particles are found in the pump Evident signs of operating pressure higher than 16 bar high pressure may compromise the integrity of the inte...

Reviews: