Type 2530H1 HART

 

Interchange Multiplexer

Contents

Introduction

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Scope of Manual

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Description

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Specifications

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Installation

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Mounting

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Multiplexer Mounting

4

. . . . . . . . . . . . . . . . . . . . . . . . 

HART

 Filter Mounting

4

. . . . . . . . . . . . . . . . . . . . . . 

Junction Box Mounting

6

. . . . . . . . . . . . . . . . . . . . . . 

Connecting Multiplexer Power

7

. . . . . . . . . . . . . . . . . 

Connecting Multiple HART Interchange

Multiplexers

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Connecting Multiplexers to the

RS232-to-RS485 Converter

7

. . . . . . . . . . . . . . . . . 

Converter DIP Switches

7

. . . . . . . . . . . . . . . . . . . . . . 

Setting the Converter RS485 Termination

and Biasing

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Setting the Converter Baud Rate

9

. . . . . . . . . . . . . . 

Multiplexer DIP Switches

9

. . . . . . . . . . . . . . . . . . . . . . 

Setting the Multiplexer RS485 Addresses

9

. . . . . . 

Setting the Multiplexer RS485 Baud Rate

9

. . . . . . 

Connecting Field Devices to the Multiplexer

10

. . . 

Connecting HART Filters Directly to the

Multiplexer

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Connecting HART Filters to the Multiplexer

Using the Type HJ200 Junction Box

11

. . . . . . . . 

Connecting Field Devices Directly to the

 Multiplexer (without HART Filters)

11

. . . . . . . . . 

Connecting Field Devices to the Multiplexer

Using the Type HJ200 Junction Box
(without HART Filters)

12

. . . . . . . . . . . . . . . . . . 

Connecting a HART Communicator Using

the Type HJ200 Junction Box

12

. . . . . . . . . . . . 

System Startup

12

. . . . . . . . . . . . . . . . . . . . . . . . . . 

Verifying Connections

12

. . . . . . . . . . . . . . . . . . . . . . 

Verifying the Network Baud Rate

13

. . . . . . . . . . . . . 

Verifying the HART Interchange

Multiplexer Addresses

13

. . . . . . . . . . . . . . . . . . . . 

Verifying the RS485 Network

13

. . . . . . . . . . . . . . . . 

Reading the Converter LED Indicators

13

. . . . . . . . 

Reading the Multiplexer LED Indicators

13

. . . . . . . 

Service

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Figure 1. Type 2530H1 HAR

T Interchange Multiplexer

W6486/IL

Introduction

Scope of Manual

This instruction manual includes installation and main-
tenance information for the Type 2530H1 HART inter-
change multiplexer. Refer to separate manuals for
additional information on other FIELDVUE

 products

used with the multiplexer such as the Type DT4000
digital transducer, DVC5000 Series digital valve con-
trollers, HF200 Series HART filters, and the
ValveLink

 Series VL2030 software.

Only personnel qualified through training or experience
should install, operate, and maintain the Type 2530H1
HART interchange multiplexer. If there are any ques-
tions concerning these instructions contact your Fisher
Controls sales office or sales representative before
proceeding.

Description

The Type 2530H1 HART interchange multiplexer is a
HART-based multiplexer that links installed HART-
based field devices to a centralized personal computer
(PC). When used in conjunction with the ValveLink
Type VL2030 software, the multiplexer provides the

Instruction Manual

Form 5407

February 1996

Type 2530H1

Summary of Contents for HART 2530H1

Page 1: ...1 Connecting Field Devices to the Multiplexer Using the Type HJ200 Junction Box without HART Filters 12 Connecting a HART Communicator Using the Type HJ200 Junction Box 12 System Startup 12 Verifying...

Page 2: ...5 DIN46277 or T type EN50022 DIN46277 3 DIN rail Dis tance from RS232 to RS485 converter is 3000 feet 914 m maximum longer distances are possible with an RS485 repeater Dimensions 14 2 in 360 mm long...

Page 3: ...nicates to the multiplexer network through a serial port using RS232 signal levels Therefore a converter is required to convert the RS232 signal to an RS485 sig nal Typically the multiplexer is insta...

Page 4: ...ccepts up to 16 filter or field device connections Specifications Specifications for the Type 2530H1 HART interchange multiplexer are listed in table 1 Specifications for the Type HJ200 junction box a...

Page 5: ...es HART Filters Instruction Manual WARNING To avoid personal injury or property damage from an uncontrolled process Figure 7 Type HF210 HART Filter Showing Normal Polarity Orientation CONTROL SYSTEM C...

Page 6: ...rminal cage clamp style connectors for the filter input filter Figure 9 Type HJ200 Junction Box Printed Wiring Board Removal APPLY PRESSURE TO WALLS OF MOUNTING TRACK TO REMOVE PRINTED WIRING BOARD W6...

Page 7: ...nd B terminal of the next unit i e A to A and B to B 2 Place a 100 ohm resistor between the A and B ter minals on the last multiplexer in the arrangement Note The following step is optional 3 Connect...

Page 8: ...up position connects a 1k ohm pull down resistor between the DATA line and ground Placing the switch labeled 220 in the up position terminates the RS485 input or output with a 220 ohm resistor For ad...

Page 9: ...network address es There are a total of 32 possible addresses 0 through 31 for assignment to the multiplexer Each multiplexer in an RS485 network must have a different address When setting an address...

Page 10: ...UTION To avoid HART communication failure do not use more than one of the above methods to connect a single field device to the same multiplexer Connecting HART Filters Directly to the Multiplexer For...

Page 11: ...connec tor on the multiplexer labeled LOOPS 1 16 Channel numbers 17 through 32 designate the channel number Figure 16 Junction Box Printed Wiring Board Show ing HART Communication Channel Identificat...

Page 12: ...eld device with the handheld HART communicator To use the junction box as a connection point for a HART communicator 1 Mount the junction box as described in the Installa tion section 2 Connect the fi...

Page 13: ...er Addresses Note After changing the multiplexer switch positions power to the multiplexer must be removed and reapplied before the change will become effective There are 32 available addresses for th...

Page 14: ...the off position d Remove power from the multiplexer e Re apply power to the multiplexer All three LEDs flashing together indicate a seri ous fault Return the unit for service All three LEDs lit cont...