F300-11-00                                                                                                    8                                                                                              I56-0047-005R

[10.2] Power Board Replacement

1. Disconnect wiring from the terminal block.
2. Remove the two power board mounting screws.
3. Pull gently on the board to remove it. 
4. To replace the board, align the board mounting features, holes, and the interconnect terminals. 
    Push the board into place.
5. Secure board with the two mounting screws.
6. Re-connect wiring to terminal block.

[12] Model D350RP Air Duct Smoke Detector Specifications 

Operating Temperature Range                +32° to +131°F (0° to +55°C)
Storage Temperature Range                    –22° to +158°F (–30° to +70°C)
Humidity Range                                    10% to 93% (non-condensing)
Air Velocity                                           500 to 4000 ft/min (2.54 to 20.32 m/sec)
Dimensions                                           14

3

⁄8

  L x 5

1

⁄2

 W x 2

3

⁄4

 D (37 cm L x 14 cm W x 7 cm D)

Programming Specifications/Requirements for Intelligent System Control Panels

There are a limited number of devices that can have their LEDs programmed to illuminate. The actual number of devices 
is determined by the control panel and its ability to supply LED current. Refer to the Control Panel Installation Manual for 
details.

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this 

device must accept any interference received, including interference that may cause undesired operation.

Note:    This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to 

            provide reasonable protection against harmful interference  in  a  residential  installation. This equipment generates, uses and can radiate radio frequency energy and, 

            if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no  guarantee that interfer-

            ence will not occur in a particular installation. If  this equipment does cause harmful interference to radio or television reception, which  can be determined  by turning 

            the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

                 – Reorient or relocate the receiving antenna.

                 – Increase the separation between the equipment and receiver.

                 – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

                 – Consult the dealer or an experienced radio/TV technician for help.

To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum, 

the requirements of Chapter 7 of NFPA 72, the National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the local 

manufacturer’s representative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm equipment, or any component 

of that system which fails shall be repaired or replaced as soon as possible.

Current Requirements (using no accessories)

Power supply voltage:            20-30 VDC             24 VAC, 50-60 Hz         120 VAC, 50-60Hz      220/240 VAC, 50-60Hz
Max. standby current:               26 mA                    65 mA RMS                 44 mA RMS                  25 mA RMS 
Max. alarm current:                   87 mA                   182 mA RMS                52 mA RMS                  30 mA RMS
Alarm resonse time:               3 to 10 Sec.                 3 to 10 Sec.                  3 to 10 Sec.                    3 to 10 Sec.
Power up time:                           2 Sec.                          2 Sec.                           2 Sec.                            2 Sec.

Accessories

                                

Part No.

Remote LED                                 RA400Z
Magnetic Remote Test                   RTS451
Key-Activated Remote Test            RTS451KEY
Replacement Filters                      F36-09-11
Replacement Test Magnet             M02-04-00

Accessories                                                               Part No.

Replacement Photo Insect Screen                                S08-39-01
Replacement End Cap for Plastic Sampling Tube          P48-61-00
Replacement End Cap for Metal Sampling Tubes          P48-21-00 
Replacement Photoelectric Sensor Board                     A5053FL 
Replacement Power Board (w/relay)                           A5060

Accessory Current Loads at 24 VDC

Device                      Standby        Alarm
PA400                         0 mA      15 mA Max.
RA400Z                      0 mA      12 mA Max.
RTS451/RTS451KEY     0 mA      10 mA Max.

Contact Ratings

Alarm auxiliary contacts* (DPDT)                10 A @ 30 VDC
                                                    10 A @ 277 VAC (.75 power factor)
                                                  240 VA @ 249 VAC (0.4 power factor)
                                                                1/8 HP @ 120 VAC
                                                                1/4 HP @ 240 VAC
Supervisory contact (SPST)                  2.0 A @ 30 VDC (resistive)

*Minimum switching current for auxiliary contact must be 100 mA DC minimum @ 5 VDC. 

 

F300-11-00                                                                                                    1                                                                                              I56-0047-005R

Fire•Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472, 203-484-7161

Before installing detectors, please thoroughly read the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications, 
which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of 
this manual are available from NEMA (National Electrical Manufacturers Association, 2101 L Street NW, Washington, DC 
20037). NFPA Standards 72 and 90A should also be referenced for detailed information. 

NOTICE:

 This manual shall be left with the owner/user of this equipment.

IMPORTANT:

  This  detector  must  be  tested  and  maintained  regularly  following  NFPA  72  requirements.  The  detector 

should be cleaned at least once a year.

GENERAL DESCRIPTION

An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct system 
is distributed to the entire building. Smoke detectors designed for use in air duct systems are used to sense the presence 
of smoke in the duct.
 The D350RP air duct smoke detector is a photoelectric detector. This smoke detection method combines with an efficient 
housing design that samples air passing through a duct and allows detection of a developing hazardous condition. When 
sufficient smoke is sensed, an alarm signal is initiated at the fire control panel monitoring the detector, and appropriate 
action can be taken to shut off fans, blowers and change over air handling systems, etc. This can prevent the distribution 
or it can isolate toxic smoke and fire gases throughout the areas served by the duct system.
Two LEDs on each detector may illuminate, if programmed by the system control panel, to provide a local alarm indica-
tion. There is also a remote alarm output for use with auxiliary devices. The D350RP has remote test capability with the 
RTS451/RTS451KEY Remote Test Station.
The D350RP incorporates a cover tamper feature. When the cover is removed for more than 20 minutes, the unit loses 
communication at the panel, a trouble is indicated at the panel and the alarm relay switches states thereby shutting down 
fans, dampers and blowers. In the case when the sensor is removed or when there is no power to the unit, only a trouble 
is indicated at the panel (alarm relay does not work any longer).

Figure 1. Exploded view of duct smoke detector components:
CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT

The D350RP Duct Smoke Detector consists of the following items
(See Figure 1.):

D350RP INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS

NOTE:

  For ducts over 1

1

⁄2

 feet, longer sampling tubes must be ordered to complete the installation. They must be the 

correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine the 
sampling tube required for different duct widths.

Contents Of The Duct Smoke Detector

1.   Complete duct smoke detector         
       

assembly with sensor

2.  Two #10 x 1

1/4

″ 

sheet metal screws

3.  Two sampling tube filters
4.  One test magnet
5.  Drilling template
6.  Two foam gaskets
7.  Four  #6-self  tapping  mounting  screws 

for  the  sampling  tube  and  optional   
exhaust tube extension

8.  One sampling tube end cap
9.  One plastic sampling tube
10. One  #8  self-tapping  screw  for  plastic 

sampling tube 

 

NOTE: A detector sensor board DOES
NOT need to be ordered separately.

����

�������

������������

�������������

��������

�������

��������������

��������

�����

�������������

����������

�������

����

������������

�����

�����������

��������������

��������������

������

H0106-00

Please refer to insert for the Limitations of Fire Alarm Systems

Summary of Contents for D350RP

Page 1: ...53FL Replacement Power Board w relay A5060 Accessory Current Loads at 24 VDC Device Standby Alarm PA400 0 mA 15 mA Max RA400Z 0 mA 12 mA Max RTS451 RTS451KEY 0 mA 10 mA Max Contact Ratings Alarm auxiliary contacts DPDT 10 A 30 VDC 10 A 277 VAC 75 power factor 240 VA 249 VAC 0 4 power factor 1 8 HP 120 VAC 1 4 HP 240 VAC Supervisory contact SPST 2 0 A 30 VDC resistive Minimum switching current for ...

Page 2: ...ED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety Nor are they a substitute for early warning in a building s regular fire detection system It is strongly recommended that the user read NFPA Standards 90A 72 and 101 WARNING This device will not operate without electrical power Fire situations may cause an interruption of power The system safeguards should be ...

Page 3: ...timal performance The exhaust tube is molded onto the base of the duct housing and the A2440 00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not extend at least 2 inches into the duct The sampling tube is always installed with the air inlet holes facing into the air flow To assist proper installation the tube s mounting flange is marked with...

Page 4: ...r to set the sensor above address number 99 on compatible systems remove the breakaway stop on the left hand rotary switch Using pliers carefully twist and pull off stop as shown in Figure 7 7 Perform Detector Check 1 Perform STANDBY AND TROUBLE TEST per Section 9 2 1 2 Perform MAGNET TEST per Section 9 2 2 1 The RTS451 test of Section 9 2 2 2 may substitute for this requirement 3 Perform AIR FLOW...

Reviews: