*For best results, operate the UV-1500 continuously 24 hours a day

.

 

UV-AIRE™ AIR PURIFYING SYSTEM  

Model: UV-1500C 

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION 

LEAVE THE INSTALLATION INSTRUCTIONS WITH THE OWNER/OPERATOR OF THE DEVICE 

AFTER OPENING THE CARTON, UNPACK AND INSPECT THE UNIT AND LAMP FOR DAMAGE. 

DO NOT 

INSTALL THIS UNIT IF ANY DAMAGE IS NOTICEABLE. 

 

SAFETY CONSIDERATIONS 

WARNING:

  

Never expose eyes or skin to UVC light from any source. 

• 

Looking directly at the UVC light may cause permanent eye damage or blindness.  

• 

Never operate the UV-Aire™ Air Purifying System with the UV chamber open

WARNING:  DO NOT mount this unit outdoors. 

• 

This product is designed for indoor installation only. 

 

ITEMS INCLUDED IN KIT: 

1-UV-Aire

 UV-1500 units  

10-Sheet metal mounting screws 
2-drop ceiling cover plates 
4-Wall and drop ceiling mounting 

brackets 

1-Ultra Violet lamp 
1-Instruction Sheet 
1-2x4 Electrical Conduit Box and Cover 
4-Intake Air Filters 
1-Carbon Filter 

UV-C light inhibits the growth and reproduction of germs and bacteria in the air of a home or 
office.  The treatment is a safe, silent, and proven way to make your home or office a 
healthier place to live and work.  

Summary of Contents for 46448400

Page 1: ...y at the UVC light may cause permanent eye damage or blindness Never operate the UV Aire Air Purifying System with the UV chamber open WARNING DO NOT mount this unit outdoors This product is designed for indoor installation only ITEMS INCLUDED IN KIT 1 UV Aire UV 1500 units 10 Sheet metal mounting screws 2 drop ceiling cover plates 4 Wall and drop ceiling mounting brackets 1 Ultra Violet lamp 1 In...

Page 2: ...n the front access door The circuit board indicates good operation of the lamp by a continuous GREEN color on the LED light After 8320 hrs of lamp operation the circuit board indicates the elapsed time of lamp operation by a continuous YELLOW color on the LED light and the internal alarm will beep every 15 minutes After 9000 hrs of lamp operation the circuit board indicates the elapsed time of lam...

Page 3: ... receptacle Turn the speed control knob clockwise to turn on the unit and adjust the motor fan speed control to the desired airflow 7 After the fan has started the LED light will show a continuous GREEN color indicating proper unit operation VI SUSPENSION OR DROP CEILING OPTION The UV 1500C must be wired in accordance with the National Electrical Code and any applicable local codes The UV 1500C mu...

Page 4: ...ll eyelet screws or other appropriate anchors into the ceiling joists above the location where the will be installed If installing the UV 1500C into 4 foot by 2 foot title grid install an additional suspended ceiling tee bracket into the ceiling grid to form a 2 foot by 2 foot title location See Figure 14 10 Install the UV 1500C into the suspended ceiling grid then install support wires 16 gauge w...

Page 5: ...maximum output intensity The lamp should operate continuously for maximum lamp life and light effectiveness VI REPLACEMENT PROCEDURES REPLACING THE UV LAMP VERY IMPORTANT Turn the speed control switch on unit to OFF position and unplug unit from outlet or turn off power to the unit before replacing the UV lamp 1 Loosen the two door mounting screws on front cover of the UV 1500C See Figure 17 2 Ope...

Page 6: ...been reset 11 Release the door switch turn the knob on the speed control to the off position and close the front cover of the unit Secure the cover with the door mounting screws 12 Turn the speed control knob clockwise to turn on the unit and adjust the motor fan speed control to the desired airflow After the fan has started the LED light will show a continuous GREEN color indicating proper unit o...

Page 7: ...nd of invoice price constitutes agreed and liquidated damages for any breach of warranty by Field FIELD S LIABILITY UNDER THIS WARRANTY IS LIMITED TO THE REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT WITH THE EXCEPTION OF DAMAGES RESULTING FROM FIELD S FAILURE TO COMPLY WITH FEDERAL OR STATE WARRANTY LAW FIELD SHALL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES WHETHER DIRECT OR INDIREC...

Page 8: ...Page 8 P N 46448400 Rev D 09 05 ...