background image

 1 

INSTRUCTION  

MANUAL #105 

 

THREE PHASE POLE MOUNTED DISTRIBUTION TRANSFORMER 

ERMCO | 2225 Industrial Road |   Dyersburg, TN 38024 | (800)238

5587 

INTRODUCTION 

This instruc on manual provides general informa on for the 
installa on, opera on, and maintenance of ERMCO three

phase, pole 

mounted transformers. These transformers are to be applied and used 
per the “usual service condi ons” describes in IEEE C57.12.00 (General 
Requirements for Liquid

Immersed Distribu on, Power and Regula on 

Transformers). 

 

RECEIVING AND INSPECTION 

ERMCO pole transformers are shipped 

fi

lled with insula ng 

transformer oil. Immediately upon receipt, and before being put in 
service, transformers should be inspected for any external damage or 
loose parts caused by shipping and handling. Damage presumed to 
have occurred during shipment should be noted, and your ERMCO 
sales representa ve contacted.  
 
Extreme care is taken at the factory in the processing and sealing of 
the transformer to insure that it is clean and dry, and of adequate 
dielectric strength. Normally, therefore, it is not recommended that 
the transformer seals be broken for internal inspec on. If it is decided, 
nevertheless, that the transformer be opened, adequate precau ons 
should be taken as outlined elsewhere in these instruc ons. 
 

HANDLING AND INSTALLATION 

Transformers should be li ed by the li ing lugs only. The transformer 
bushings should not be used for li ing or moving the transformer into 
posi on. The transformer should be kept upright at all  mes and not 

pped over on its side for any reason. This will prevent air bubbles 

from entering the coil which could degrade the dielectric strength. 
Support lugs for direct pole moun ng are provided in accordance with 
IEEE standards. Hangers and kickers for cross arm moun ng  is  to  be 
provided by the user. When installed, transformers should be 
protected from dangerous overloads, over voltages and lightning by 
suitable, approved devices. 

 

OIL 

Transformers are thoroughly dried at the factory and 

fi

lled with 

ERMCO inhibited mineral oil having a minimum dielectric strength of 
30 kV at 60 Hz when tested per ASTM D

877. ERMCO inhibited mineral 

oil contains less than 1 ppm of PCB's at  me of manufacture. The 
transformer should never be energized unless it is 

fi

lled with oil. 

 
If it should be found necessary to add to or replace the oil in the 
transformer, only clean dry oil having the minimum dielectric strength 
of 30 kV and less than 1 ppm PCB's should be used. Before opening 
the transformer, su

cient  me should be allowed for the transformer 

to come to temperature equilibrium with the air in the room to 
eliminate the possibility of moisture condensa on from the air. 
 
A recommended procedure for opening the transformer is to 

fi

rst 

bring the interior of the transformer to atmospheric pressure by 
ven ng the automa c pressure relief valve furnished on all ERMCO 
transformers. The cover may then be removed. Natural rubber hose 
should not be used in the transfer of oil. The correct oil level at 25°C is 
marked on the inside of the tank. 
 
Care should be taken to re

seal the transformer so that moisture is 

permanently excluded from the interior. A pressure test using dry air 
or nitrogen, may conveniently be made through the pressure

vacuum 

fi

ng, a er removing the pressure relief valve, to be sure all seals are 

ght. Pressurize the transformer to 5 psig and hold for 30 minutes. A 

drop in pressure during this  me would indicate the transformer is not 
properly sealed and the tank and 

fi

ngs should be checked and the 

leak repaired. Finally, the pressure relief valve should be installed and 
carefully  ghtened. 
 

CONNECTIONS 

Refer to the transformer nameplate for the kVA ra ng and the 
permissible connec ons. No connec ons other than those shown on 
the nameplate should be made; and none of the connec ons should 
be changed while voltage is applied to the transformer. Provision is 
made for grounding the tank by means of a tapped pad or ground 
connector. 
 

OVERLOAD AND OVERVOLTAGE PROTECTION 

Transformer protec on against overloads and over voltages may be 
obtained by suitable devices applied in the 

fi

eld to conven onal 

transformers, or by use of protected transformers (ERMCO CSP or CP 
types) as supplied from the factory. 
1. 

Fuses: 

High voltage fused cutouts are recommended for 

protec on of conven onal transformers against overloads and to 
protect the line against outages. On ERMCO CSP and CP 
transformers, a fusible protec ve link, mounted inside the tank, 
is  provided  in  series  with  each  HV  terminal.  In  case  of  internal 
failure of the transformer, the protec ve link disconnects the 
transformer from the line without a

ec ng line fuses or breakers. 

When the available fault current exceeds the maximum 
interrup ng ra ng of the protec ve link, a current limi ng fuse 
should be used in series with the protec ve link. 

 

Reviews: