background image

 
 

EMS Group Head Office, Technology House, Sea Street, Herne Bay, Kent CT6 8JZ, England 

Tel: +44 (0) 1227 369570 Fax: +44 (0) 1227 369679 Email: 

[email protected]

  Website: 

www.emsgroup.co.uk

 

 
FireCell Radio Detector Installation Guide (Iss 7)

 

 

 

 

Page 1

 

 

 

 

Radio Detector 

Installation Guide 

 

General 

 

The  Radio  Detector  variants  and  ancillary  equipment  are  available  under  the  following  part 
numbers; 

 
 

Part No 

Variant Type 

 

FCX-100-001 

Radio Optical Detector 

0359-CPR-0041 & 0359-CPR-0017

 

FCX-120-011 

Radio Heat CS Detector 

0359-CPR-0041 & 0359-CPR-0016

 

FCX-120-001 

Radio Heat A1R Detector 

0359-CPR-0041 & 0359-CPR-0015

 

FCX-130-001 

Radio Multisensor Detector 

0359-CPR-0041 & 0359-CPR-0018

 

FCX-170-001 

Radio Module Only (No Head) 

0359-CPR-0041 

FCX-177-001 

Optical Head Only 

0359-CPR-0017 

FCX-176-001 

Heat CS Head Only 

0359-CPR-0016 

FCX-175-001 

Heat A1R Head Only 

0359-CPR-0015 

FCX-174-001 

Multisensor Head Only 

0359-CPR-0018 

 

Type A: for indoor use   

 

EN54-5:2001 Heat Detectors – Point Detectors (FCX-174-001, FCX-175-001 & FCX-176-001 variants only) 
EN54-7:2001 Smoke Detectors – Point Detectors using scattered light (FCX-174-001 & FCX-177-001 variants only) 
EN54-25:2008 Component using RF links for the fire detection and fire alarm systems for buildings (FC-170-001 only) 

 

The  address  of  the  unit  is  set  when  programming  the  device  to  the  systems  Radio  Hub  (see 
commissioning  manual  for  details).  The  installation  must  conform  to  BS5839:  Part  1  (or 
applicable local codes).   

 

Installation of Radio Detector 

 

Ensure  that  all  Detectors  are  sited  in  accordance  with  the  survey  and  design  details.  Wherever 
practical, the red LED should face the main entrance to the room. 

 

Remove  the  ceiling  mounting  plate  by  turning  it  counter  clockwise.  This  dis-assembles  the 
mounting  plate  from  the  radio  module  and  head.    The  ceiling  mount  will  now  be  available  for 
fixing to the ceiling. 

 

Ensure that the Detector head and radio module is suitably stored so as to prevent the possibility 
of accidental damage. 

 

Fix  the  ceiling  mounting  plate  to  the  ceiling  using  suitable  fixings  and  fasteners.  A  minimum  of 
two mounting holes must be used. (See Figure 1) 

 

It  is  important  that  fastener  heads  are  flush  or  sub-flush  with  the  internal  surface  of  the  ceiling 
mount to avoid the risk of damaging the battery PCB.   

                            

 
 
 
                                                                                                           Ceiling Mounting 
                                                                                                           Positions 
                                                                        
 
 
 
 
 

                                                                                                                                               

Figure 1 