900 Series
Buccaneer
IP68 and IP69K Waterproof Connectors
Wiring Assembly Instructions
www.bulgin.co.uk
Buccaneer 900 Series Environmentally Sealed Connectors
Mains Wire Connections
Important connect wires
Brown to terminal L
Blue to terminal N
Green/Yellow to
terminal E
Material:
Body Mouldings:
Polyamide
Flammability Rating:
UL94V-0
Contacts:
Machined Solid Brass, Nickel plated
O Rings:
Nitrile
Panel Sealing Gasket:
Silicone Rubber
Mechanical:
Sealing:
IP6
9K
,
EN60529
Contact
Accommodation:
2.5
to
4mm
2
(13-10AWG)
conductor,
single
or
multi stranded
Cable Retention force: 22mm dia, 150N
15mm dia, 150N
7mm dia, 80N
Cable Acceptance and
Gland Tightening Torques:
Cable dia
Gland Colour
Tightening Torque
PX0 version
13-15mm
Yellow (standard) 3.16Nm (28 lb/in)
11-13mm
Black
3.16Nm (28 lb/in)
9-11mm
White
3.16Nm (28 lb/in)
7-9mm
Dark Grey
3.16Nm (28 lb/in)
PXA version
20-22mm
Yellow (standard) 3.16Nm (28 lb/in)
18-20mm
Black
3.16Nm (28 lb/in)
16-18mm
White
3.16Nm (28 lb/in)
14-16mm
Dark Grey
3.16Nm (28 lb/in)
Panel mount nut
-
-
2.25Nm
Flange & Bulkhead
fixing screws
-
-
0.9Nm
IMPORTANT
-
PLEASE
READ
Before
using
the
connector,
it
is
important
that
these
instructions
are
carefully
read
and
understood
to
ensure
the
connector
system
is
completely
water
tight
and
electrically
safe.
IF
IN
DOUBT
CONSULT
A
QUALIFIED
ELECTRICIAN.
NEVER UNMATE OR MATE THE PRODUCT WHILE STILL UNDER LOAD
The
900
Series
Buccaneer
is
available
in
2,
3,
4,
5
,
7
and 10
pole
versions.
The
3,
4,
5
and
7
pole
versions
have
a
‘Leading
Earth’
pin
arrangement
for
added
protection.
The
socket
insert
of
the
connector
should
always
be
the
live
part
of
the
connector
from
the
supply.
The
pin
insert
of
the
connector
should
always
lead
to
the
load
or
electrical
device.
The
pin
or
socket
inserts
can
be
fitted
to
any
body
style
to
provide
the
correct
arrangement
for
the
application.
To
ensure
efficient
sealing
use
only
smooth,
circular
cable
with
appropriate
gland
for
the
cable
diameter.
The
sealing
glands
supplied
with
the
Flex
and
Flex
In-line
connectors
accommodate
cables
sizes
as
follows:
Version
Cable Dia.
Cable Gland Colour
PX0
13-15mm
Yellow (standard)
PX0
11-13mm
Black
PX0
9-11mm
White
PX0
7-9mm
Dark Grey
PXA
20-22mm
Yellow (standard)
PXA
18-20mm
Black
PXA
16-18mm
White
PXA
14-16mm
Dark Grey
Assembly/Wiring instructions
1.
Remove the pin or socket insert from the housing of the connector.
There is a slot for a flat blade screwdriver in the centre of the insert.
NOTE: The inserts have a LEFT HAND THREAD and should be turned
clockwise
to remove.
2.
For Flex and In-Line connector bodies, remove the gland nut, gland
cage and gland from the rear of the housing and slide onto the
cable. NOTE for PXA version there is no gland cage. Thread the
cable through the connector body. See assembly drawings, figs. 1-5
and 8 for different body styles.
3.
Prepare the cable and bare the wire ends as shown in fig. 6, wire
stripping details.
4.
Insert the bared wire ends into the terminals on the back of the
pin/socket insert and fully tighten the wire retention screws.
NOTE: If the connector is to be used with ‘mains’ voltages, ensure
the wires are connected in the correct orientation as shown in the
diagram below.
After the wires have been connected securely, pull the cable and
insert back into the housing and tighten with a screwdriver to ensure
the insert is seated correctly.
NOTE: LEFT HAND THREAD, turn the insert
anti-clockwise
when
assembling.
When assembling the Chassis (fig 3) and Flange (fig 4 and 5)
housing types, the cable should be left free behind the panel to
prevent it twisting.
5.
For Flex and Flex In-line housings:
PX0 version: Slide the gland, gland cage and gland nut along the
cable into the body and tighten the gland nut to the appropriate
torque to seal.
Please note change to PXA assembly:
PXA version: Slide 1 washer, the gland, the final washer and gland
nut along the cable into the body and tighten to the appropriate
torque to seal then tighten clamp screws to secure. See fig 8.
6.
For the Bulkhead, Flange and Chassis body styles, correctly seat the
gaskets and housing onto the mounting surface and secure with rear
nut or screws/bolts with seals. Ensure all seals and glands are kept
clean during assembly.
NOTE: To ensure that the correct sealing properties of the connector are
achieved it is imperative that all ‘O’ rings are correctly located and
seated before assembly. Please refer to the exploded diagrams for the
locations of these seals.
Part
no.:
13672
Issue
no:
12
IF IN DOUBT SEEK ADVICE
IMPORTANT SAFETY NOTICE
For your protection all mains (250V) equipment
used out of doors, in damp or wet conditions
should be supplied from a correctly fused
source and protected by an approved R.C.D. to
BS7071, BS7288, BS4293, BS EN 61008-1,
BS EN 1008-2-2
900
Series
Wiring
13672iss1
2
:900 Series Wiring 13672iss
12
19/9/12 16:34 Page 1
Specification
Electrical:
Current Rating: CSA
Current Rating:
Voltage Rating:
Contact Resistance:
Insulation Resistance:
Dielectric strength:
Approvals
:
4,5 Poles
7 Pole
10 Pole
32A
30A
600V ac/dc
32A
25A
600V ac/dc
2,3 Poles
32A
30A
415V ac/dc
10A
10A
250V ac/dc
<10m Ohm (initial)
>10M Ohm (@500V dc)
2.2Kv ac min
UL/VDE/CSA/CCC
UL/VDE/CCC
CCC
CSA Pending
UL/VDE/CSA
Pending
ʻCaution not for Interrupting currentʼ
ʻAttention; Ne pas utiliser pour couper le courantʼ