INSTRUCTION MANUAL 

D2xB1LD2 LED Beacons 
For use in Hazardous Locations

 

 

D2XB1LD2

 

 

 
D2XB1LD2-H 

 

1)  Product Table 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

2)  Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGISED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD - CLEAN ONLY WITH A DAMP 
CLOTH 
 

Avertissement: 

 NE PAS OUVRIR UN PRESENCE 

D’ATMOSPHERE EXPLOSIVE 

 NE PAS OUVRIR ENERGIE 

 DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE 

 

3)  Rating & Marking Information 

 

3.1. Fire Alarm Ratings 

 
All models are approved for use as Visual Appliance for use 
in Fire Alarm Systems – Private Mode and General Signalling 
UL1638A. 
 
The  D2xB1LD2DC024  Product  Version  H  (D2xB1LD2-H)  is 
certified  for  use  as  a  public  mode  visual  alarm  device  in 
accordance  with  UL1971  Third  Edition  and  UL1638  Fifth 
Edition  /  CAN/ULC-S526  Fourth  Edition.  For  use  in  public 
mode  the  beacon  must  be  without  the  wire  guard  or  plastic 
lens cover. 
 
See fire instruction manual D211-00-401-IS-SC-UL 
 

 

 
3.2. ATEX / IECEx / UKEx Ratings 
 

Standards 

EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7): 

Explosive Atmospheres - Equipment. General Requirements 

EN IEC 60079-7:2015 +A1:2018 / IEC 60079-7:2018 (Ed. 5.1): 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): 

Explosive Atmospheres - Equipment Dust Ignition Protection by 
Enclosure "t"

 

Ratings 

D2xB1LD2:  Ex ec IIC T4 Gc Ta -40°C to +50°C 

Ex tc IIIC T75°C Dc Ta -40°C to +50°C 

 

Certificate No. 

DEMKO 14 ATEX 4786493904X 
IECEx ULD 14.0004X 
UL21UKEX2131X 

ATEX Mark, Equipment 
Group and Category: 

 

II 3G 
II 3D

 

CE Marking 
 

 

 

UKCA Marking 

 

 

 

Model 

Nom. Voltage 

Voltage Range 

Max Operating 

Current*

 

D2xB1LD2DC024 

24Vdc 

18-54Vdc 

346mA 

      D2xB1LD2DC024 -H

#

 

24vdc 

16-33Vdc (Regulated) 

346mA 

D2xB1LD2AC115 

115Vdc 

115-120Vac 50/60Hz 

102.4mA 

D2xB1LD2AC230 

230Vdc 

220-230Vac 50/60Hz 

75mA 

*Max. rms current at worst-case voltage in voltage range. 

#

D2xB1LD2-H public mode beacon (Product Version H). See Section 3.1 

For detailed current ratings of the device please see Section 15.  

Table 1: Electrical Ratings. 

Summary of Contents for D2xB1LD2

Page 1: ...n For use in public mode the beacon must be without the wire guard or plastic lens cover See fire instruction manual D211 00 401 IS SC UL 3 2 ATEX IECEx UKEx Ratings Standards EN IEC 60079 0 2018 IEC6...

Page 2: ...20 C to 50 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Group Category and Temperature Classification When connected to an approved system the D2XB1LD2...

Page 3: ...st first be fitted to the base using the 2 off M4 X 12mm countersunk screws provided Additional feet are available as spare parts if required The unit can also be pole mounted using the NPT Entry in t...

Page 4: ...used If fitting 2 off wires to one terminal way the sum of the 2 off wires must be a maximum cross sectional area of 2 5mm Strip wires to 8mm Wires may also be fitted using ferrules Terminal screws ne...

Page 5: ...g crimp terminal to secure the earth conductor to the earth stud The external earth conductor should be at least 4mm2 in size The external earth crimp ring should be located between the two M5 plain w...

Page 6: ...new lens cover aligning the fixing holes of the guard lens cover and housing Refit the fixings to hold into place the fixings MUST be fitted in the order shown above 14 Maintenance Overhaul Repair Mai...

Page 7: ...3Hz 104mA 143mA Flashing 2Hz 103mA 146mA Flashing Double Strike 122 4mA 180mA Flashing Triple Strike 144 8mA 211 2mA D2xB1LD2AC115 115Vac 60Hz 115 120Vac 50 60Hz Steady High Power 83mA 102 4mA Steady...

Page 8: ...on 10 For light output ratings see section 2 Up to 6 off units can be connected to the same wire run without a separate synchronization module and meet the synchronization requirements of UL1971 UL163...

Page 9: ...h rate 0 100 38 38 35 87 25 97 5 25 90 34 54 32 28 23 37 30 45 75 28 79 26 90 19 48 50 55 21 11 14 28 14 28 55 45 17 27 11 69 11 69 60 40 15 35 10 39 10 39 65 35 13 43 9 09 9 09 70 35 13 43 9 09 9 09...

Page 10: ...L 1971 UL1638 CAN ULC S526 at worst case min input voltage 2 4 On axis light output rating private mode Table 3 Vertical Light Output Dispersion for Ceiling Mounting Viewing Angle Of Rating Intensity...

Page 11: ...7QH www e2s com Tel 44 0 208 743 8880 Document No D211 00 401 IS SC UL Issue A 22 07 2022 Sheet 4 of 4 3 Electrical Ratings 3 1 Surge current for Fire Alarm system use Table 6 Surge Currents Model No...

Page 12: ...attern Apply power to ve ve Stage 2 Flash Pattern Apply power to ve ve Connect Stage 2 to ve Stage 3 Flash Pattern Apply power to ve ve Connect Stage 3 to ve AC LED D2XB1LD2 UNITS Power Live Neutral R...

Page 13: ...herlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc I...

Page 14: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 15: ...Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80...

Page 16: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Reviews: