INSTRUCTION MANUAL 

D1xS2 
Alarm Horn Sounder

 

Class I, Zone 1, 2, 21 & 22

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D190-00-101-IS

 

Issue 2

 

17-03-2022

 

Sheet 1 of 8

 

D1xS2F

 

D1xS2H

 

1) Product Table

Unit Type Code 

Nominal 

Input Voltage 

Nominal 

Current P2 

Nominal 

Current P3 

Voltage Range 

Sound 

Pressure Level 

dB(A) 

Max* 

P2/P3 

Nom

.† 

P2/P3

 

 

D1xS2FDC024-A 

12Vdc 

289mA 

356mA 

11.5-54Vdc 

120/123  115/118 

24Vdc 

324mA 

740mA 

48Vdc 

195mA 

391mA 

D1xS2FAC230-A 

115Vac 

125mA 

282mA 

100-240Vac 50/60Hz 

230Vac 

78mA 

167mA 

D1xS2HDC024-A 

12Vdc 

289mA 

356mA 

11.5-54Vdc 

124/127  119/122 

24Vdc 

324mA 

740mA 

48Vdc 

195mA 

391mA 

D1xS2HAC230-A 

115Vac 

125mA 

282mA 

100-240Vac 50/60Hz 

230Vac 

78mA 

167mA 

*Max = Tone 4

Nom. = Tone 44 

The table shows the input current taken by the various sounders. 
The current levels shown above are for the 440Hz Continuous tone @ nominal input voltage. 
Nominal current at nominal voltage. 
Table 1: Electrical Ratings. 

2) Warnings

CAUTION 
TO  REDUCE  THE  RISK  OF  IGNITION  OF  HAZARDOUS 
ATMOSPHERES: 
DISCONNECT FROM SUPPLY BEFORE OPENING. 
KEEP TIGHTLY CLOSED WHEN IN OPERATION. 
WARNING 
FIT  SEALING  FITTING  IN  CONDUIT  RUNS  WITHIN  18  INCHES 
FROM ENCLOSURE. 
EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING 
UPWARDS OF HORIZONTAL 
DO  NOT  OPEN  WHEN  AN  EXPLOSIVE  ATMOSPHERE  IS 
PRESENT  
DO NOT OPEN WHEN ENERGISED  
POTENTIAL  ELECTROSTATIC  CHARGING  HAZARD  -  CLEAN 
ONLY WITH A DAMP CLOTH  
ENCLOSURE ENTRIES: TWIN M20 X 1.5 / SINGLE 1/2” NPT 
ATEX/IECEx  &  UKEx  INSTALLATIONS:  IF  TEMPERATURE 
EXCEEDS 70°C AT ENTRY OR 80°C AT BRANCHING POINT USE 
SUITABLE RATED CABLE AND GLANDS 

ATTENTION 
POUR 

REDUIRE 

LE 

RISQUE 

D’INFLAMMATION 

DES 

ATMOSPHÈRES DANGEREUSES : 
COUPER L 'ALIMENTATION AVANT OUVERTURE. 
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT. 
AVERTISSEMENT 
CONDUITS DOIVENT ETRE SCELLES EN MOINS DE 18 POUCES. 
ÉQUIPEMENT  NE  DOIT PAS  ETRE INSTALLE  AVEC  LE  KLAXON 
TOURNEE VERS LE HAUT DE HORIZONTAL. 
NE PAS OUVRIR UN PRESENCE D’ATMOSPHERE EXPLOSIVE  
NE PAS OUVRIR ENERGIE  
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE  
ENTRÉES DE BOÎTIER: 2 x M20 X 1.5 / 1 x 1/2” NPT 
ATEX/IECEx  &  UKEx  INSTALLATIONS :  SI  LA  TEMPÉRATURE 
DÉPASSE  70  °C  À  L'ENTRÉE  OU  80  °C  AU  POINT  DE 
BRANCHEMENT,  UTILISER  UN  CÂBLE  ET  DES  JOINTS 
D'ÉTANCHÉITÉ APPROPRIÉS 

Summary of Contents for D1xS2FDC024-A

Page 1: ...ATMOSPHERES DISCONNECT FROM SUPPLY BEFORE OPENING KEEP TIGHTLY CLOSED WHEN IN OPERATION WARNING FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING UPWARDS OF HORIZONTAL DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGISED POTENTIAL ELECTROSTATIC CHARGING HAZARD CLEAN ONLY WITH A DAMP CLOTH ENCLOSURE ENT...

Page 2: ...0 C Ex tb IIIC T95 C Db Ta 55 C to 75 C D1xS2 AC230 A Ex db IIC T5 Gb Ta 55 C to 75 C Ex db IIC T6 Gb Ta 55 C to 60 C Ex tb IIIC T93 C Db Ta 55 C to 75 C See Product table for electrical ratings of each unit model Certificate No DEMKO 19ATEX2141X IECEx ULD 19 0008X UKEx UL UL21UKEX2132X Epsilon x Equipment Group and Category II 2G II 2D CE Marking and Notified Body No 2813 UKCA Marking and Notifie...

Page 3: ...harges on non conducting surfaces Only the explosionproof cover is to be used for access to the enclosure for installation service and maintenance 6 Specific Conditions for Safe Use Flameproof threaded joints and cemented joints are not permitted to be repaired 7 Product Mounting and Access 7 1 Mounting The D1x Alarm Horn may be secured to any flat surface using at least two of the three or four 7...

Page 4: ...and the length of the cable runs The cable size selected must have the necessary capacity to provide the input current to all the sounders connected to the line AC 1 0 2 5mm2 AWG18 AWG12 DC 0 2 2 5mm2 AWG24 AWG12 Fig 3 Wire Preparation When connecting wires to the terminals great care should be taken to dress the wires so that when the cover is inserted into the chamber the wires do not exert exce...

Page 5: ...nders See schematic diagram D190 06 001 for details 9 1 Configuration See Table 1 for product power supply and Sound Pressure Levels SPL Configuration for DC Units Fig 5 DC PCBA Configuration for AC Units Fig 6 AC PCBA 9 2 Stage Switching Polarity DC Units Switching from positive switching default to negative switching DC Only NOTE Max supply is 33V DC if higher DC voltage is required use Negative...

Page 6: ...wiring options Config Voltage Configuration Description Features Product Option Identifier 1a DC Single Stage Configuration Line monitoring Positive Switching 1 1b DC Two Stage Configuration Common Negative Positive Switching 1 1c DC Three Four Stage Configuration Common Negative Positive Switching 1 2 DC Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Configuration Common Positive Cus...

Page 7: ...Of Line Monitoring An optional 12 way terminal module is available to enable up to four alarm stages to be activated from three DC voltage output channels The three alarm stage activation inputs can be independently monitored Refer to Schematic D190 06 001 Config 6 Specify Product option V when ordering Spare part code for field installation SP78 0001 11 Maintenance Overhaul and Repair Maintenance...

Page 8: ...ices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short Refer to the compatible control panel specification for EOL device values and ratings Model Nominal Voltage Voltage Range P1 Nominal Operating Current P2 Nominal Operating Current P3 Nominal Ope...

Page 9: ... 0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 0...

Page 10: ...100 2dB A CA 108 5dB A P3 US 103 5dB A CA 111 6dB A at 10 feet 24Vdc For Fire Alarm applications the Sounder Volume must be at the highest setting see volume control section For fire alarm use Tone 12 as shown below must be selected Connection Terminals Pluggable AC 1 0 2 5mm2 AWG18 AWG12 DC 0 2 2 5mm2 AWG24 AWG12 Terminal Tightening torque 0 4Nm To maintain Ingress Protection cable entries must b...

Page 11: ...cal Axis 3dB A 39 41 38 41 6dB A 45 47 64 69 D1xS2FDC024 A D1xS2FDC024 S Sounder Directional Characteristics for Canadian Fire CAN ULC S525 P3 OSPL Horizontal Axis Vertical Axis 3dB A 46 48 46 47 6dB A 52 54 52 53 D1xS1RDC024 A D1xS1RDC024 S Sounder Directional Characteristics for Canadian Fire CAN ULC S525 OSPL Horizontal Axis Vertical Axis 3dB A 42 41 42 41 6dB A 48 48 48 49 D1xS2HDC024 A D1xS2H...

Page 12: ...NE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve R1 R1 S2 R1 S2 S3 Stage 1 ve IN Stage 1 ve OUT Stage 1 ve IN Stage 1 ve OUT Sing...

Page 13: ... ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Set H1 H2 to ve switching Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Confi...

Page 14: ...r to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage 2 Cconnect Stage 2 ve to Common ve Stage 3 Connect both Stage 1 ve Stage 2 ve to Common ve CUSTOM CONFIGURATION PRODUCT OPTION Y Cut Link W1 H2 H1 Set H1 H2 to ve switching CUSTOM CONFIGURATION PRODUCT...

Page 15: ...05 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2 Common N N L L E N N L L E C N N L L E C S2 S3 Live IN Live OUT Neutral IN Neutral OUT Stage 1 Live IN Stage 1 Live OUT Stage 1 Neutral IN Stage 1 Neutral OUT Single Stage Configuration Config 1a Stage 1 Apply Power...

Page 16: ...awarden Industrial Park Hawarden Deeside CH5 3US UK Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6...

Page 17: ...te and Place of Issue London 10 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Page 18: ... CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007...

Page 19: ...Date and Place of Issue London 24 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ...

Page 20: ...Page left Intentionally blank ...

Reviews: