European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. IS 2446-76-P      Issue 1          24/04/13                                Sheet 1 of 6

 

Mod No: ACN0012

 

  

  

INSTRUCTION MANUAL (ATEX / IECEx) 

BExDCTS110-05D 

Electronic Sounder / Beacon with Call Relay 

For use in Flammable Gas and Dust Atmospheres 

 

 
 
 
 
 
 

1)  Introduction 

 
The  BExDCTS110-05D  is  a  flameproof  combined  electronic 
Sounder  /  Beacon  with  Call  Relay  which  is  certified  to  meet 
the  requirements  of  the  ATEX  directive  94/9/EC  and  the 
IECEx Scheme. The combined Sounder / Beacon produces a 
loud  audible  signal  and  a  visual  signal,  when  triggered  by  a 
telephone ringing signal and can be used in hazardous areas 
where  potentially  flammable  gas  and  dust  atmospheres may 
be  present.  Thirty-two  different  sounds  can  be  selected  by 
internal switches, (

see tone table on Page 5

).  The electronic 

sounder  produces  output  levels  in  the  110dB(A)  range  and 
the beacon produces an output level of 5 joules. The unit can 
be used in Zone 1 and Zone 2 areas with gases in groups IIA 
and  IIB  and  with  Temperature  Classifications  of  T1,  T2,  T3, 
and T4 and can also be used in Zone 21 and Zone 22 areas 
for  combustible  dusts  and  have  an  IP  rating  of  IP  67  and  a 
surface temperature rating of T115ºC (T100ºC at +55ºC). 
 

2)  Marking 

 
All  units  have  a  rating  label,  which  carries  the  following 
important information: 
 
Unit Type No.     

       BExDCTS110-05D

 

 
Input Voltage:    DC Units    12V  or 24V  or  48V 

            AC Units         230V or 115V 

 

        

Codes:   Ex d IIB T4 for Ta 

–50°C to +70ºC 

Ex tD A21 IP6X T115°C based on max Ta of +70°C 

 

       

 

            

Certificate No.

 

KEMA 01ATEX2223X 
IECEx KEM 10.0025X 

 

 

 

 

 
 

“Warnings”

 

 

DO NOT OPEN WHEN AN EXPLOSIVE  

                            GAS OR DUST ATMOSPHERE IS PRESENT 
 

      COVER BOLTS CLASS A4-80 

 

                    USE HEAT RESISTING CABLES AND        

                   CABLEGLANDS (Rated 110ºC) AT  

                       AMB. TEMPERATURES OVER 40ºC 

 
Year of Construction /  
Serial No.       

 

 i.e.  10 / 1DCTS21000001 

 
 

3) 

Type Approval Standards

 

 
The units have an EC Type examination certificate issued by 
DEKRA and have been approved to the following standards: 

 

 
 
 
 
 
 
 
 
 
EN60079-0:2006   IEC60079-0:2004 (Ed4)

      

General Requirements

 

EN60079-1:2007   IEC60079-1:2007

 

(Ed6)

        F

lameproof Enclosure ‘d’ 

EN61241-0:2006   IEC61241-0:2004 (Ed1)       Dust General 

          Requirements 

EN61241-1:2004   IEC60079-1:2004 (Ed1)       Dust Enclosures tD 

 

4) 

Installation Requirements

 

 
The  unit  must  be  installed  in  accordance  with  the  latest 
issues of the relevant parts of the EN 60079 specifications or 
the equivalent IEC specifications 

– Selection, Installation and 

maintenance  of  electrical  apparatus  for  use  in  potentially 
explosive  atmospheres  (other  than  mining  applications  or 
explosive processing and manufacture):- 
 

EN60079-14:2008

    

Electrical Installations in Hazardous 

IEC60079-14:2007 (Ed4) 

Areas (other than mines)

 

 

EN60079-10:2003

   

Classification of Hazardous Areas

 

IEC60079-10:2008 (Ed1) 

 
The  installation  of  the  unit  must  also  be  in  accordance  with 
any  local  codes  that  may  apply  and  should  only  be  carried 
out  by  a  competent  electrical  engineer  who  has  the 
necessary training. 

 

5) 

Zones,  Gas  Group,  Category,  IP  Rating  and 
Temperature Classification 

 

The BExDCTS110-05D unit has been certified Ex d IIB T4 for 
Ta 

–50°C  to  +70ºC  for  gas  and  Ex  tD  A21  IP6X  T115ºC 

based  on  max.  Ta  of  +70ºC  for  dust.  This  means  that  the 
units  can  be  installed  in  locations  with  the  following 
conditions:- 
  

Area Classification Gas: 

 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 
normal operation. 

Zone 2 

Explosive  gas  air  mixture  not  likely  to  occur, 
and if it does, it will only exist for a short time. 

  

Gas Groupings: 

 

Group IIA 

Propane 

Group IIB 

Ethylene 

  

 
Temperature Classification: 

 

T1 

400

o

 C  

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

 
 
 
 

0518 

II 2G/D 

Epsilon x: 
Equipment Group and 
Category: 

CE Marking: 
Notified Body No. 
 

Summary of Contents for BExDCTS110-05D

Page 1: ... DUST ATMOSPHERE IS PRESENT COVER BOLTS CLASS A4 80 USE HEAT RESISTING CABLES AND CABLEGLANDS Rated 110ºC AT AMB TEMPERATURES OVER 40ºC Year of Construction Serial No i e 10 1DCTS21000001 3 Type Approval Standards The units have an EC Type examination certificate issued by DEKRA and have been approved to the following standards EN60079 0 2006 IEC60079 0 2004 Ed4 General Requirements EN60079 1 2007...

Page 2: ...that these screws and their spring washers are kept in a safe place during installation On completion of the cable wiring installation the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged during installation Also check that the earth bonding wire between the two casting sections is secure and the O ring seal is in place When replacing the beac...

Page 3: ...tries which have an M20 x 1 5 entry thread as standard Only cable glands approved for Ex d applications can be used which must be suitable for the type of cable being used and also meet the requirements of the Ex d flameproof installation standard EN 60079 14 2008 IEC60079 14 2007 When only one cable entry is used the other one must be closed with an Ex d flameproof blanking plug which must be sui...

Page 4: ...elephone pcb see figures 6 and 7 The Telephone Selection Table on page six shows the switch positions 1 4 for the country setting and switch 5 for the beacon continuous or pulse mode and switch 6 for the sounder continuous or pulse mode When making any changes to the country selection the unit needs to be de energised for a minimum of 2 minutes for the changes to take effect When pulse mode of ope...

Page 5: ... 1200 500Hz at 0 3Hz 1 1 1 0 0 9 Sawtooth 1200 500Hz at 1Hz 0 0 0 1 0 10 Alternating 2400 2900Hz at 2Hz 1 0 0 1 0 11 Intermittent 1000Hz at 0 5Hz General alarm 0 1 0 1 0 12 Alternating 800 1000Hz at 0 875Hz 1 1 0 1 0 13 Intermittent 2400Hz at 1Hz 0 0 1 1 0 14 Intermittent 800Hz 0 25s on 1s off 1 0 1 1 0 15 Continuous at 800Hz 0 1 1 1 0 16 Intermittent 660Hz 150mS on 150mS off 1 1 1 1 0 17 Alternat...

Page 6: ...D CONTINUOUS OR PULSE SELECTION TABLE Telephone Selection Settings DIP Switch Settings DIP Switch Settings Dialing Country Setting 1 2 3 4 5 6 Australia Ireland New Zealand Singapore South Africa UK 0 0 0 0 Belgium Canada Cyprus Hong Kong Spain Turkey USA 1 0 0 0 Czech Republic Finland France Germany Greece Italy Luxemburg Netherlands Norway Switzerland 0 1 0 0 Austria Iceland Portugal Sweden 1 1 ...