background image

HOW-TO INSTRUCTIONS

 

                           

LT-1225 © 2017 Digital Monitoring Products, Inc.

17072

734N How-To Programming Instructions

To program a 734N, you must complete the programming process in two places: the panel and the 734N. This guide 

walks you through programming the 734N into an XR150/XR550 Series panel and then programming the 734N itself.

Program the XR150/XR550 Series Panel

1.  Momentarily place a jumper over both pins on the panel’s RESET header.
2.  Enter the code 6653 (PROG) and press CMD.
3.  The keypad displays PROGRAMMER. Press any select key or area.
4.  Press CMD until NETWORK OPTIONS. Press any select key or area. 
5.  CMD through the options until LOCAL IP ADDRESS is displayed.
6.  Write down the LOCAL IP ADDRESS of the panel to use when programming the 734N module.
7.  CMD through the options until 734N LISTEN PORT is displayed.
8.  Enter the port number that the 734N will use to send communication to the panel. Default is 2002. Write 

down the port number, as this must be the same port that is programmed in PANEL IP PORT within the 734N 

COMMUNICATION programming menu. Press CMD to display 734N Passphrase.

Note:

 The 734N LISTEN PORT cannot be the same as the panel network programming port.

9.  Enter an 8 to 16-character passphrase to encrypt communication with the 734N module. The 734N passphrase 

must match the 734N passphrase entered in COMMUNICATION programming of the 734N.

Note:

 A passphrase is required for communication to occur with the panel.

10. Exit NETWORK OPTIONS and CMD to DEVICE SETUP.
11. Enter the device number of the 734N you are programming. For example, a 734N with an address of 505 on 

AX500 would represent Door 505 and zones 505-508. See Table 1 for device addresses and zones.

 

Note:

 XR150 Series panels only support addresses 2-8. 

Table 1: Device Addresses and 734N Zone Numbers

Device/

Door

Zones

Device/

Door

Zones

Device/

Door

Zones

Device/

Door

Zones

Device/

Door

Zones

Device/

Door

Zones

501

501-504

601

601-604

701

701-704

801

801-804

901

901-904

2

21-24

505

505-508

605

605-608

705

705-708

805

805-808

905

905-908

3

31-34

509

509-512

609

609-612

709

709-712

809

809-812

909

909-512

4

41-44

513

513-516

613

613-616

713

713-716

813

813-816

913

913-916

5

51-54

517

517-520

617

617-620

717

717-720

817

817-820

917

917-920

6

61-64

521

521-524

621

621-624

721

721-724

821

821-824

921

921-924

7

71-74

525

525-528

625

625-628

725

725-728

825

825-828

925

925-928

8

81-84

529

529-532

629

629-632

729

729-732

829

829-832

929

929-932

9

91-94

533

533-536

633

633-636

733

733-736

833

833-836

933

933-936

10

101-104

537

537-540

637

637-640

737

737-740

837

837-840

937

937-940

11

111-114

541

541-544

641

641-644

741

741-744

841

841-844

941

941-944

12

121-124

545

545-548

645

645-648

745

745-748

845

845-848

945

945-948

13

131-134

549

549-552

649

649-652

749

749-752

849

849-852

949

949-952

14

141-144

553

553-556

653

653-656

753

753-756

853

853-856

953

953-956

15

151-154

557

557-560

657

657-660

757

757-760

857

857-860

957

957-960

16

161-164

561

561-564

661

661-664

761

761-764

861

861-864

961

961-964

12. Enter a device name. To add a device name, press any select key or area. The default device name (DEVICE x) 

displays. Select CMD to accept the default name or press a select key or area to enter a new name (up to 32 

alphanumeric characters). Press CMD when finished.

13. Based on the device number, the DEVICE TYPE may be assumed. Device 501 or higher will automatically be 

selected as a DOOR device type.        

14. For DEVICE COMMUNICATION TYPE, select the blank select key or area and then select NETWORK.
15. Exit DEVICE SETUP. CMD through options until STOP. Exit programming.