InstallatIon GuIde

 

Models 7860, 7863, 7870, 7873

Touch Screen LCD Keypads 

SLEEP

HOME

AWAY

Summary of Contents for 7873

Page 1: ...Inst alla tion Guide Models 7860 7863 7870 7873 Touch Screen LCD Keypads SLEEP HOME AWAY ...

Page 2: ... 2011 Digital Monitoring Products Inc Information furnished by DMP is believed to be accurate and reliable This information is subject to change without notice ...

Page 3: ...e Models 7870 and 7873 keypads provide four fully programmable Class B Style A supervised power limited protection zones you can program for a variety of burglary and access control applications The Model 7863 and 7873 keypads provide a built in proximity card reader designed to read DMP HID proximity credentials The Model 7873 keypad provides a door strike relay and allow Wiegand input from exter...

Page 4: ...ls wide or less The name of the image must be set to custom bmp for the keypad to recognize Cleaning the Touchscreen Display Clean the touchscreen using a water dampened soft lint free cloth Apply the water onto the cloth do NOT apply directly onto the touchscreen After cleaning wipe the touchscreen dry with a dry soft lint free cloth Micro SD Card The 7800 Series keypads have a Micro SD card slot...

Page 5: ...7 yellow to terminal 8 green to terminal 9 and black to panel terminal 10 Use 1k Ohm EOL resistors DMP Model 311 on keypad zones 1 through 4 The 7860 and 7863 keypads are supplied with a 4 wire harness for panel keypad bus connection The 7870 and 7873 keypads are supplied with a 12 wire data bus zone harness Four wires connect to the keypad bus The remaining eight wires are for the four zone input...

Page 6: ...ad Connect the Red and Black power wires from the reader to the power wires from the panel These connect in parallel with the keypad power wires Connect the Reader Data 1 wire to the White wire on the 5 wire keypad harness Connect the Reader Data 0 wire to the Green White wire on the 5 wire keypad harness See Figure 2 1K EOL 1K EOL 1K EOL 1K EOL Green White Connect Reader Data 0 White Connect Read...

Page 7: ...device being controlled by the relay is connected to the N O and C wires install the suppressor on the N O and C wires If the device is connected to the N C and C wires install the 333 on N C and C wires Refer to Figure 3 Door Strike Relay Operation As soon as the user code sent from the reader is verified by the panel the keypad door strike relay activates for 5 seconds During this time the acces...

Page 8: ...ed within 5 seconds the relay restores to its locked state Note A Zone 3 Request to Exit is inhibited for 3 seconds after the keypad reads a card and a door strike occurs This is to allow area entry and pass under a REX PIR Keypad Backlighting The touchscreen illuminates at full brightness any time the display is touched When the speaker is sounding the backlight illuminates at one half 1 2 bright...

Page 9: ...l sends the following zone alarm reports to the central station Panic Zone 19 Device Address Emergency non medical Zone 29 Device Address Fire Zone 39 Device Address 9 0 CMD 5 6 7 8 1 2 3 4 A C B D F E G I H J L K V X W S U T P R Q M O N Y Z JONES RESIDENCE FRI 12 51 PM Panic icon PANIC FIRE EMERGENCY Panic Menu Graphic Keypad Panic Icons Internal Speaker Operation All keypads emit standard tones ...

Page 10: ...e Level Set the keypad speaker volume level for key touches and entry delay tone conditions During alarm and trouble conditions the volume is always at maximum level Use the left to decrease the keypad volume and the right to increase the volume Model number 7873 v100 080211 Model Number The LCD displays the keypad model number and firmware version and date The user cannot change this information ...

Page 11: ...this option to configure the Panic Icons To enable or disable a Panic Icon touch the icon name PN Panic EM Emergency and FI Fire Once the panic icon is enabled an asterisk displays next to the description and the respective Panic icons display for the user Refer to the Panic Icon Options section in this document SYSTEM AREA A P H A HSA System Mode Configure the keypad as the same system type selec...

Page 12: ...oft Shunt works using the default 40 second timer P 5 Second Strike 40 Second Soft Shunt and entry exit timer At 30 seconds the keypad beeps if door is still open End of timer 40 Seconds A zone fault is indicated if door is still open Figure 7 Door Strike Relay Operation Time Line RELOCK ZONE 2 FAULT no yes Relock on Zone 2 Fault 7873 only Select NO to leave the relay on when Zone 2 faults to an o...

Page 13: ...tomatically selects the YES or the AWAY key Enter zero 0 to disable this feature The delay also occurs when any credential is presented for arming the HOME SLEEP AWAY system CARD OPTIONS DMP CUSTOM Card Options 7863 7873 only Select DMP to indicate the reader sends a 26 bit DMP data string Select CUSTOM if using a non DMP credential To select CUSTOM touch the right side of the keypad display Defau...

Page 14: ...ess CMD to view the site code entry display Default is NO In addition to User Code verification door access is only granted when any one site code programmed at the SITE CODES entry option matches the site code received in the Wiegand string You can program up to eight three digit site codes Note A card with a site code greater than three digits cannot be used Use only cards with three digit site ...

Page 15: ...u earlier in this document KPD KPD OPT DIAG STOP Keypad Diagnostics KPD DIAG The Keypad Diagnostic option allows you to check the display segments keyboard backlighting and test individual keys Press the Select key under KPD DIAG The keypad lights all display segments and illuminates the keyboard in Red In approximately one second the display backlighting changes to Green The keypad alternates bet...

Page 16: ...credential to the reader The keypad works by reading the 4 to 10 digit user code from the data sent by the access control reader For more information refer to Entry Cards in the programming section of this document and the panel User s Guide section on adding deleting and changing user codes Proximity Credentials Compatibility DMP Keypads with internal proximity readers are compatible with most st...

Page 17: ...l areas for which you are authorized Figure 9 Area Arming and Disarming All Perimeter System Arming and Disarming Present your card to the reader the keypad displays DISARM or PERIM ALL when arming Select the desired option The keypad displays ENTER CODE Present your card to the reader Once validated by the system the selected areas arm or disarm automatically On 7873 keypads the Door Strike relay...

Page 18: ... for 5 seconds during which time you can open the door Once you open the door you have 40 seconds to exit and close the door before the Zone 2 Soft Shunt expires Figure 11 Present Access Card Keypad Entry Delay All Systems Once the entry delay starts the keypad sounds an entry tone and displays ENTER CODE Present your card to the reader Once validated the system disarms all areas accessible by you...

Page 19: ...ide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harm...

Page 20: ... increases DC voltage on the wire decreases 3 Maximum number of devices per 2 500 feet circuit is 40 Note Each panel allows a specific number of supervised keypads Add additional keypads in the unsupervised mode Refer to the panel installation guide for the specific number of supervised keypads allowed 4 Maximum voltage drop between the panel or auxiliary power supply and any device is 2 0 VDC If ...

Page 21: ... Proprietary Burglar ANSI UL 1610 Central Station Burglar ANSI UL 1635 Digital Burglar ANSI UL 985 Household Fire Warning ANSI UL 864 Fire Protective Signaling 7870 7873 only Accessories Keypad Wiring Harness 313 4 4 wire harness 313 5 5 wire harness 313 12 12 wire harness Proximity Credentials 1306P Prox Patch 1306PW Prox Patch 26 Bit 1326 HID ProxCard II Card 1386 HID ISOProx II Card 1346 HID Pr...

Page 22: ...LT 1162 1 01 11355 ...