manualshive.com logo in svg
background image

                                                                                                                                     

2007-10-12

5011644101-PDT1

 

Profibus Communication Module (CME-PD01) Instruction Sheet 

‹

 Profibus is a registered trademark of Profibus International. 

‹

 Please thoroughly read and understand the following contents to ensure correct use before operation. 

‹

 The content of this instruction sheet may be revised without prior notice. Please consult our distributors or 

download the most updated version at http://www.delta.com.tw/industrialautomation

 

A. Panel 

Appearance

 

1: Reserved  

2: EV     

5: SG+  
6: Reserved 

7: Reserved  
8: Reserved

3: GND 
4: SG-            

Profibus-DP

Interface (DB9)

RS-485 (RJ45)

ADDH ADDL

SP

NET

CME-P D01

SP LED

NET LED

Address Switches

 

1. 

SP LED:

 Indicating the connection status between 

VFD-E and CME-PD01. 

2. 

NET LED:

 Indicating the connection status between 

CME-PD01 and PROFIBUS-DP. 

3. 

Address Switches:

 Setting the address of 

CME-PD01 on PROFIBUS-DP network. 

4. 

RS-485 Interface (RJ45):

 Connecting to VFD-E, and 

supply power to CME-PD01. 

5. 

PROFIBUS-DP Interface (DB9):

 9-PIN connector 

that connects to PROFIBUS-DP network. 

6. 

Extended Socket:

 4-PIN socket that connects to 

PROFIBUS-DP network.

 

B. Dimensions 

5

7.

3

[2

.2

6]

59

.7

[2

.3

5]

3.

6

[0

.1

4]

72.2 [2.84]

3.5 [0.14]

34.8 [1.37]

ADDH ADDL

SP

NET

CME-P B01

 

 
 
 
 

 

C. 

Parameters Setting in VFD-E 

 

VFD-E 

Baud Rate 9600 

Pr.09.01=1 

RTU 8, N, 2 

Pr.09.04=3 

Freq. Source 

Pr.02.00=3 

Command Source 

Pr.02.01=3 

D. Power 

Supply 

The power of CME-PD01 is supplied from VFD-E. Please 
connect VFD-E to CME-PD01 by using 8 pins RJ-45 cable, 
which is packed together with CME-PD01. After connection 
is completed, CME-PD01 is powered whenever power is 
applied to VFD-E.

 

E. PROFIBUS 

Address 

 

 

CME-PD01 has two rotary s select the PROFIBUS address. 
The set value via 2 address switches, ADDH and ADDL, is 
in HEX format. ADDH sets the upper 4 bits, and ADDL sets 
the lower 4 bits of the PROFIBUS address.   

 

 

Address 

Meaning 

1..0x7D 

Valid PROFIBUS address 

0 or 0x7E..0xFE 

Invalid PROFIBUS address 

 

NOTE

 

Please download the GSD file and user manual at 
http://www.delta.com.tw/industrialautomation/ 

Отзывы: