Warning 

 

Please read this instruction sheet carefully before use. 

 

Switch off the power before wiring. 

 

DVP04TC-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, 
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device 
(e.g. key or specific tools are required to open the enclosure) in case danger and damages on the device may occur. 

 

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all 
the wiring again before switching on the power. 

 

DO NOT touch any terminal when the power is switched on. 

 

Make sure the ground termnial 

  is correctly grounded in order to prevent electromagnetic interference. 

 

Keep the wire as short as possible between RTD and PLC and the power wire as far away as possible from I/O wire 
to prevent interference. 

 

When setting the 

thermocouple temperature sensor mode, please make sure that the setting of CR#1 is correct, or it will cause 

serious  errors.

 

 Introduction

 

 Model Explanation & Peripherals

 

 

Thank you for choosing Delta’s DVP series PLC. DVP04TC-H2 is able to receive 4 points of external 
thermocouple  temperature sensors (J-type, K-type, R-type, S-type, T-type) and convert them into 14-bit 
digital signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, the data in 
DVP04TC-H2 can be read or written. There are 49 16-bit control registers (CR) in DVP04TC-H2. 

 

DVP04TC-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F). 

 Product Profile (Indicators, Terminal Block, I/O Terminals) 

 

Unit: mm 

D

 -

L

 +

L

 -

L

 +

2

4

V

0

V

L

 -

L

 +

L

 -

L

 +

L

 -

D

 +

S

L

D

8

S

L

D

S

L

D

S

L

D

C

H

1

C

H

2

C

H

3

C

H

4

R

S

-4

8

5

 

1

 DIN rail (35mm) 

 

6

 Terminals 

2

 Connection port for extension unit/module 

 

7

 Mounting  hole 

3

 Model name 

 

8

 I/O terminals 

4

 POWER, ERROR, A/D indicator 

 

9

 Mounting port for extension unit/module 

5

 DIN rail clip 

 

ENGLISH 

 External Wiring 

CH1

CH4

DC/  DC

5V

AG
+15V

-15V

AG

24+

0V

L -

*2

*3

+
-

10 k

MUX

+
-

L -

Thermoc ouple

Thermoc ouple

Shielding 
cable *1

Shielding 
cable *1

Cold-Junction
Compensation

System 
grounding

 

Terminal of

power module

 

Earth

(100    or less)

 

*1:  The  wiring  used  for  analog  input  should  adopts  the  connection  cable  or  shielding  cable  of  thermocouple  temperature  sensor 

J-type / K-type / R-type / S-type / T-type and should be separated from other power cable or wirings that may cause interference. 
The screw torque of the terminal should be 1.95 kg-cm (1.7 in-lbs).   

*2: Terminal SLD is the ground location for noise suppression. 

*3:  Please  connect  the 

  terminal  on  both  the  power  module  and  DVP04TC-H2  to  the  system  earth  point  and  ground  the  system 

contact or connect it to the cover of power distribution cabinet.   

Note:

 DO NOT wire empty terminal  . Use 60/75°C copper conductor only. 

 

Specifications

 

Temperature 

measurement module 

Explanation 

Power supply voltage 

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%) 

Analog output channel 

4 channels/module 

Applicable sensor types 

J-type, K-type, R-type, S-type, T-type Floating thermocouple sensor 

Range of input 
temperature 

See the table in Section 

 

Range of digital 
conversion 

See the table in Section 

 

Resolution 

14 bits (0.1°C/0.18°F) 

Overall accuracy 

±

0.5% when in full scale (25°C, 77°F) 

±

1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F 

Response time 

200ms × the number of channels 

Isolation 

Isolation between digital area and analog area. No isolation among channels. 

Digital data format 

13 significant bits out of 16 bits are available; in 2’s complement 

Average  function 

Yes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K20 

Self-diagnosis 

Upper and lower bound detection/channel 

Communication mode 
(RS-485) 

ASCII/RTU mode. Communication speed: 4,800/9,600/19,200/38,400/57,600  /115,200 bps. 
ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 stop 
bit (8, E, 1). RS-485 cannot be used when connected to PLC MPU. 

When connected to 
DVP-PLC MPU in series 

The modules are numbered from 0 to 7 automatically by their distance from MPU. No. 0 is the 
closest to MPU and No. 7 is the furthest. Maximum 8 modules are allowed to connect to MPU 
and will not occupy any digital I/O points. 

 Other Specifications 

Power supply 

Max. rated power 
consumption 

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2.5W supplied by external power. 

 

Environment 

Operation/storage 

1. Operation: 0°C~ 55°C (Temperature), 50 ~ 95% (Humidity), pollution degree 2 
2. Storage: -25°C~ 70°C (Temperature), 5 ~ 95%

Humidity

 

Vibration/shock  immunity  Standard:  IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 

 

Control Register

 

CR 

RS-485 

parameter 

address 

Latched 

Register content 

b15 b14 b13 b12 b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 

#0 

H’4096 

 

Model name 

Set up by the system.   
DVP04TC-H2 model code = H’6403. 
You can read the model name from the program and see 
if the extension module exists. 

Reserved 

CH4 

CH3 

CH2 

CH1 

#1 

H’4097 

 

R/W  Thermocouple type 

Take the setting of CH1 for  example: 

1. When (b2, b1, b0) is set as (0,0,0), choose J-type 

2. When (b2, b1, b0) is set as (0,0,1), choose K-type 

3. When (b2, b1, b0) is set as (0,1,0), choose R-type 

4. When (b2, b1, b0) is set as (0,1,1), choose S-type 

5. When (b2, b1, b0) is set as (1,0,0), choose T-type 

CR#1: The working mode of the 4 channels in the sensors selected by the temperature measurement module. There are 
2 modes (J-type and K-type) for each channel which can be set up separately. For example, if the user needs to set up 
CH1: mode 0 (b2 ~ b0 = 100); CH2: mode 1 (b5 ~ b3 = 001); CH3: mode 0 (b8 ~ b6 = 000) and CH4: mode 1 (b11 ~ b9 = 
001), CR#1 has to be set as H0208 and the higher bits (b12 ~ b15) have to be reserved. The default value = H’0000. 

#2 

H’4098 

 

R/W  CH1 average time 

#3 

H’4099 

 

R/W  CH2 average time 

#4 

H’409A 

 

R/W  CH3 average time 

#5 

H’409B 

 

R/W  CH4 average time 

Range of settings in CH1 ~ CH4: K1 ~ K20. Default =K10. 

Please note that when PLC MPU writes in the average 
time by TO/DTO instruction, please use the rising/falling 
edge contact detection instructions (LDP/LDF…) in case 
you may not obtain the correct average temperature. 

#6 

H’409C 

 

Average °C temp. measured at CH1 

#7 

H’409D 

 

Average °C temp. measured at CH2 

#8 

H’409E 

 

Average °C temp. measured at CH3 

#9 

H’409F 

 

Average °C temp. measured at CH4 

Average Celsius temperature measured at CH1 ~ CH4.   

Unit: 0.1°C 

CR#6 ~ CR#9: The average Celsius temperature measured at CH1 ~ CH4 obtained from the average time settings in 
CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#6 ~ CR#9 will be the average of the most 
recent 10 temperature signals in Celsius at CH1 ~ CH4. 

#10  H’40A0 

 

Average °F temp. measured at CH1 

#11 

H’40A1 

 

Average °F temp. measured at CH2 

#12  H’40A2 

 

Average °F temp. measured at CH3 

#13  H’40A3 

 

Average °F temp. measured at CH4 

Average Fahrenheit temperature measured at CH1 ~ 
CH4. 

Unit: 0.1°F 

CR#10 ~ CR#13: The average Fahrenheit temperature measured at CH1 ~ CH4 obtained from the average time settings 
in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#10 ~ CR#13 will be the average of the 
most recent 10 temperature signals in Fahrenheit at CH1 ~ CH4. 

#14  H’40A4 

 

Present °C temp. measured at CH1 

#15  H’40A5 

 

Present °C temp. measured at CH2 

#16  H’40A6 

 

Present °C temp. measured at CH3 

#17  H’40A7 

 

Present °C temp. measured at CH4 

Present Celsius temperature measured at CH1 ~ CH4. 
Unit: 0.1°C 

#19  H’40A9 

 

Present °F temp. measured at CH1 

#20  H’40AA 

 

Present °F temp. measured at CH2 

#21  H’40AB 

 

Present °F temp. measured at CH3 

#22  H’40AC 

 

Present °F temp. measured at CH4 

Present Fahrenheit temperature measured at CH1 ~ CH4. 
Unit: 0.1°F 

CR 

RS-485 

parameter 

address 

Latched 

Register content 

b15 b14 b13 b12 b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 

#24  H’40AE 

 

R/W  OFFSET value of CH1 

#25  H’40AF 

 

R/W  OFFSET value of CH2 

#26  H’40B0 

 

R/W  OFFSET value of CH3 

#27  H’40B1 

 

R/W  OFFSET value of CH4 

Adjustable OFFSET settings at CH1 ~ CH4. 
Range: -1,000 ~ +1,000 
Default = K0 
Unit: 0.1°C 

#30  H’40B4 

 

Error status 

Register for storing all error status.   
See the table of error status for more information. 

CR#30: Error status (see the table below) 

Error status 

Content 

b15 ~ b8 

b7 

b6 

b5 

b4 

b3 

b2 

b1 

b0 

Abnormal power supply 

K1 (H’1) 

Wiring to empty external contact  K2 (H’2) 

Incorrect mode setting 

K4 (H’4) 

OFFSET/GAIN error 

K8 (H’8) 

Hardware malfunction 

K16 (H’10) 

Abnormal digital range 

K32 (H’20) 

Incorrect average times setting 

K64 (H’40) 

Instruction error 

K128 (H’80) 

Reserved 

Note:

 Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the 

same time. 0 = normal; 1 = error. 

 

#31  H’40B5 

 

R/W  Communication address setting 

For setting RS-485 communication address.   
Range: 01 ~ 254, Default = K1. 

#32  H’40B6 

 

R/W 

Communication speed (baud rate) 
setting 

For setting up communication speed: 4,800/9,600/19,200/ 
38,400/57,600/115,200 bps. ASCII data format: 7-bit, even 
bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 
stop bit (8, E, 1). Default: H’0002. 
b0: 4,800 bps.   
b1: 9,600 bps (default).   
b2: 19,200 bps.   
b3: 38,400 bps.   
b4: 57,600 bps.   
b5: 115,200 bps. 

 

b14: High/low bit exchange of CRC checksum (only valid 

in RTU mode) 

b15: Switch between ASCII/RTU modes; 0 = ASCII mode 

(default) 

b15 b14 b13 b12 b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 

ERR LED 

CH4 

CH3 

CH2 

CH1 

#33  H’40B7 

 

R/W  Returning to default setting 

Take the setting of CH1 for  example: 
1.  b0 is reserved. 
2.  b1 is reserved. 
3.  When b2 is set as 1, all the settings will return to 

default settings. 

ERR LED definition: default of b12 ~ b15 = 1111 
1.  When b12 = 1, CH1 wiring to empty external contact, 

ERR LED will flash. 

2.  When b13 = 1, CH2 wiring to empty external contact, 

ERR LED will flash. 

3.  When b14 = 1, CH3 wiring to empty external contact, 

ERR LED will flash. 

4.  When b15 = 1 CH2 wiring to empty external contact, 

ERR LED will flash. 

#34  H’40B8 

 

Firmware version 

Displaying the current firmware version in hex; e.g. 
version 1.0A is indicated as H’010A 

#35 ~ #48 

For system use 

 

PID Control Registers 

CR# 

CH1  CH2  CH3  CH4 

Latched 

Register content 

Explanation 

#51 

#71 

#91  #111 

 

R/W  Temperature SV   

Range: K-1,000 ~ K8,000. Default = K0. 

#52 

#72 

#92  #112 

 

R/W  Sampling time (s)   

Range: K1 ~ K30 (s). Default = K2. 

#53 

#73 

#93  #113 

 

R/W  KP   

Default = K121. 

#54 

#74 

#94  #114 

 

R/W  KI   

Integral constant, Default = K2,098. 

#55 

#75 

#95  #115 

 

R/W  KD 

Derivative constant, Default = K-29. 

#56 

#76 

#96  #116 

 

R/W  Upper limit of I value 

Range: K-32,760 ~ K32,760. Default = K0. 

#57 

#77 

#97  #117 

 

R/W  Lower limit of I value   

Range: K-32,760 ~ K32,760. Default = K0. 

#58 

#78 

#98  #118 

 

I value 

Current accumulated offset value. Default = K0. 

#59 

#79 

#99  #119 

 

R/W  Heating/cooling control 

0: Heater, 1: Cooler. Default = K0. 

#60 

#80  #100  #120 

 

R/W  Upper limit of output 

Range: K-32,760 ~ K32,760. Default = K4,000. 

#61 

#81  #101  #121 

 

R/W  Lower limit of output 

Range: K-32,760 ~ K32,760. Default = K0. . 

#62 

#82  #102  #122 

 

Output percentage (%) 

Range: K0 ~ K1,000 (Unit: 0.1%). Default = K0. 

#63 

#83  #103  #123 

 

Output width (ms)   

Width of control output, Unit: ms. Default = K0. 

#64 

#84  #104  #124 

 

Output cycle (ms)   

Cycle of control output, Unit: ms. Default = K0. 

#65 

#85  #105  #125 

 

Output volume 

Default = K0. 

#66 

#86  #106  #126 

 

R/W  PID_Run/Stop   

0: Stop, 1: Run. Default = K0. 

#67 

#87  #107  #127 

 

R/W  Auto Tune   

0: Disabled, 1: Auto-tuning. Default = K0. 

  CR#0 ~ CR#127: The corresponding parameter address H’4096 ~ H’4115 are for users to read/write data by 

RS-485 communication. When using RS-485, the user has to separate the module with MPU first. 

1.  Modbus ASCII/RTU communication protocol: ASCII data format (7-bit, even bit, 1 stop bit (7, E, 1)); RTU 

data format (8-bit, even bit, 1 stop bit (8, E, 1)). 

2.  Function: H’03 (read register data); H’06 (write 1 word datum into register); H’10 (write many word data 

into register). 

3.  Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written 

by MPU through TO/DTO instruction 

4.  Symbols: 

: Latched. 

: Non-latched. R: Able to read data by FROM instruction or RS-485 

communication. W: Able to write data by TO instruction or RS-485 communication. 

 

Temperature / Digital Curve 

°C/°F Temperature Measurement Mode: 

Max.

Min.

Digital output

Measured 
temperature input

Min.

Max.

 

 

Range of input temperature 

Range of digital conversion 

Thermo 

-couple 

Min. (°C / 

°F) 

Max. (°C / 

°F) 

Min. (°C / 

°F) 

Max. (°C / 

°F) 

J type 

-100°C / -148°F 

700°C / 1,292°F 

K-1,000 / K-1,480 

K7,000 / K12,920 

K type 

-100°C / -148°F  1,000°C / 1,832°F  K-1,000 / K-1,480 

K10,000 / K18,320 

R type 

-10°C / -14°F 

1,700°C / 3,092°F 

K-100 / K-140 

K17,000 / K30,920 

S type 

-10°C / -14°F 

1,700°C / 3,092°F 

K-100 / K-140 

K17,000 / K30,920 

T type 

-100°C / -148°F 

350°C / 662°F 

K-1,000 / K-1,480 

K3,500 / K6,620 

 

 

 

注意事項 

 

請在使用之前,詳細閱讀本使用說明書。

 

 

實施配線,務必關閉電源。

 

 

本機為開放型

  (OPEN TYPE) 

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊

擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意

外衝擊本體,造成危險及損壞。

 

 

交流輸入電源不可連接於輸入

出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認電源配線。

 

 

請勿在上電時觸摸任何端子或進行維修。

 

 

本體上之接地端子

 

 

務必正確的接地,可提高產品抗雜訊能力。

 

 

由測溫體到溫調本體的配線路請用最短距離配線,為了避免雜訊及誘導的影響儘可能將電源線和負載配線分

開。

 

 

感測器熱電耦型式設定,請檢查

CR#1

,如設定錯誤會造成量測重大誤差。

 

 

產品簡介

 

     說明及週邊裝置    

 

謝謝您採用台達

DVP

系列產品。

DVP04TC-H2

溫度量測模組可接受外部

4

點(熱電耦溫度感測器

J, K, R, S, 

T

型),將之轉換成

14

位元之數位信號。透過

DVP-PLC EH2

主機程式以指令

FROM/TO

來讀寫模組內之

資料,模組內具有

49

CR (Control Register) 

暫存器,每個暫存器有

16 bits

 

 

使用者可選擇攝氏溫度或華氏溫度,攝氏溫度輸入解析度為

0.1

°C

,華氏溫度輸入解析度為

0.18

°F

 

 

產品外觀及各部介紹

 

 

尺寸單位:

mm

 

D

 -

L

 +

L

 -

L

 +

2

4

V

0

V

L

 -

L

 +

L

 -

L

 +

L

 -

D

 +

S

L

D

8

S

L
D

S

L

D

S

L
D

C
H
1

C
H
2

C
H
3

C
H
4

R

S

-

4

8

5

 

1

 

DIN

軌糟

  (35mm) 

6

  端子

 

2

  擴充機/擴充模組連接口

 

7

  固定孔

 

3

  機種名稱

 

8

  端子配置

 

4

  電源、錯誤及轉換指示燈

 

9

  擴充機/擴充模組連接座

 

5

 

DIN

軌固定扣

 

 

繁體中文 

 

外部配線

 

熱電耦

CH1

CH4

DC/ DC

5V

AG
+15V

-15V

AG

24+

0V

L -

L+

轉換器

系統接地點

第三種接地

接地阻抗

以下

(100     

)

接至電源模

隔離線 *1

*2

*3

隔離線 *1

熱電耦

+

-

10 k

MUX

冷接點補償

組之

 

+

-

L -

L+

SLD

SLD

 

1

:使用於類比輸入的配線應採用

J / K / R / S / T

型熱電耦溫度感測器之連接線或隔離線且應與其他電源線或可能引起雜訊

之接線分開。端子鏍絲扭力為

1.95  kg-cm (1.7 in-lbs)

 

2

:如果雜訊過大請將

SLD

及接地端子連接。

 

3

:請將電源模組之

 

 

端及

DVP04TC-H2

溫度量測模組之

 

 

端連接到系統接地點,再將系統接點作第三種接地或接到

配電箱之機殼上。

 

注意:空端子

   

請勿配線。只能使用

60/75°C

的銅導線。

 

 

規格

 

溫度量測模組

 

規格說明

 

電源電壓

 

24V DC (20.4V DC ~ 28.8V DC) (-15%  ~  +20%) 

類比訊號輸出通道

 

4

通道/台

 

適合感應器形式

 

J-type,  K-type, R-type,  S-type, T-type

非接地型熱電耦感測器

 

輸入溫度範圍

 

請參閱

 

 

附表

 

數位轉換範圍

 

請參閱

 

 

附表

 

解析度

 

14  bits  (0.1°C/0.18°F) 

總和精密度

 

±

0.5% 

  (25°C,  77°F) 

範圍內滿刻度時。

±

1% 

  (0 ~ 55°C, 32 ~ 131°F) 

範圍內滿刻度時。

 

響應時間

 

200ms  × 

通道數

 

隔離方式

 

數位區與類比區有隔離,通道間未隔離。

 

數位資料格式

 

16

位元二補數,有效位

13  bits

 

平均功能

 

有(

CR#2 ~ CR#5

可設定,範圍

K1  ~  K20

 

自我診斷功能

 

上下極限偵測/通道

 

通訊模式

  (RS-485) 

包含

ASCII/RTU

模式,通訊速率可選

  (4,800/9,600/19,200/38,400/57,600/115,200)

ASCII

模式資

料格式固定為

7-bit

、偶位元、

1 stop bit (7, E, 1)

RTU

模式資料格式固定為

8-bit

、偶位元、

1 stop  bit 

(8, E, 1)

。當與

PLC

主機串接時,

RS-485

通訊無法使用。

 

DVP-PLC

主機

 

串接說明

 

模組編號以靠近主機之順序自動編號由

0

7

,最大可連接

8

台且不佔用數位

I/O

點數

 

 

其他規格

 

電源規格

 

額定最大消耗功率

 

直流

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2.5W, 

由外部電源供應

 

 

Reviews: