DPR-05 relay is a three-phase (line to neutral) 
voltage asymmetry protection relay designed for 
electric motor protection. 

It offers adjustable asymmetry limit together with 
adjustable trip and reset delays. The unit has also 
phase sequence protection, phase failure and 
phase overvoltage protections. 

The asymmetry limit can be adjusted or disabled 
via trimmers on the front panel of the device.  

Delay timers are adjusted through related 
trimmers. 

 

ASYMMETRY PROTECTION 

The maximum allowed asymmetry limit is 
adjusted between 5 to 15% with the ASYM 
trimmer. If the voltage unbalance (asymmetry) 
goes over the set asymmetry limit, the 

ASM

” led 

turns on and the adjusted Delay timer starts to 
count. If the fault condition disappears before the 
Delay timer expires, then the

ASM

” led turns off. 

If the fault condition persists until the expiration of 
the Delay timer, the relay output is deactivated 
and the “

OUT

” led turns off.  

The asymmetry is defined with below formula: 

Asymmetry % = [(Vmax

LN

 - Vmin

LN

) / 230V] x 100 

When the measured asymmetry is again below 
the  adjusted limit, the 

ASM

” led turns off and the 

adjusted Reset Delay timer starts to count. When 
the timer is expired, the relay output is activated 
and the 

OUT

” led turns on. 

PHASE FAILURE PROTECTION 

If the voltage of any phase falls below 50% of the 
nominal value, then 

ASM

” led turns on and 

immediately the relay output is deactivated and 
the “

OUT

” led turns off. 

OVERVOLTAGE PROTECTION 

If the voltage of any phase goes 50% above the 
nominal value, then 

ASM

” led turns on and 

immediately the relay output is deactivated and 
the “

OUT

” led turns off. 

PHASE SEQUENCE PROTECTION 

If the phase sequence is reversed, the 

SEQ

” led 

starts to flash, the relay output is deactivated and 
the “

OUT

” led turns off. 

 

* Electrical equipment should be installed only by 
qualified specialist. No responsibility is assured by 
the manufacturer or any of its subsidiaries for any 
consequences resulting from the non-compliance 
to these instructions. 
* Check the unit for cracks and damages due to 
transportation. Do not install damaged equipment. 
* Do not open the unit. There is no serviceable 
parts inside. 
* Fuses of fast type (FF) with a maximum rating of 
6A must be connected to phase voltage inputs, in 
close proximity of the unit. 
* Disconnect all power before working on 
equipment. 
* When the unit is connected to the network do 
not touch terminals. 
* Any electrical parameter applied to the device 
must be in the range specified in the user manual. 
* Do not try to clean the device with solvent or the 
like. Only clean with a dump cloth. 
* Do not allow water to come inside the unit. 
* Verify correct terminal connections before 
applying power. 
* Only for DIN rail mounting. 

 

Before installation: 

 Read this manual carefully, determine the 

correct connection diagram. 

 Make sure to use adequate fuses.

 

 Do not subject the unit to water spill.

 

Below conditions may damage the device: 

 Incorrect connections. 

 Incorrect power supply voltage. 

 Overload or short circuit at relay outputs 

 Power supply frequency out of specified limits 

 

 

Do not install the unit close to high 
electromagnetic noise emitting devices like 
contactors, high current busbars, switchmode 
power supplies and the like. Although the unit 
is protected against electromagnetic 
disturbances, excessive disturbance can affect 
the operation and measurement precision. 

  Use adequate cable section, at least 0.75mm

(AWG18).  

 

OPERATION

 

 

Do not overload relay 
outputs. Use extra 
contactors if required. 

 

ELECTRICAL INSTALLATION 

 

PRE-INSTALLATION

 

 

SAFETY NOTICE  
Failure to follow below 
instructions will result in 
death or serious injury

 

 

DPR-05 VOLTAGE 

ASYMMETRY 

PROTECTION RELAY 