1.1 Product overview

TXgard-Plus is a flameproof toxic and oxygen gas detector

suitable for use in zone 1 or 2 hazardous areas. It is designed to detect

the following gases when fitted with the appropriate electrochemical

sensor:

Gas

Range

Type

Hydrogen sulphide

0–25 ppm

Toxic

Carbon monoxide

0–250 ppm

Toxic

Ammonia

0–50 ppm

Toxic

Oxygen

0–25% vv

Oxygen

Sulphur dioxide

0–10 ppm

Toxic

A local display and magnetically operated switches allow non-

intrusive one-man calibration without a hot work permit. Powered by

24 V dc (nominally) TXgard-Plus provides a 4-20 mA signal (sink or

source) proportional to the gas concentration and can also be fitted

with optional alarm and fault relays. 

1.2 Product description

TXgard-Plus comprises four parts; 96HD sensor housing, junction box, amplifier

and terminal board. Diagram 1 details TXgard-Plus. The overall assembly is

certified EEx d IIC T6 in Europe and Class 1 , Zones 1&2 AEx d IIC T6 in the USA.

The 96HD sensor housing is a modular stainless steel assembly that

dismantles to allow plug-in sensors to be replaced easily (see Diagram 4). The

assembly screws into an M20 entry on the junction box.

The junction box is manufactured from marine grade alloy and is supplied

with 2 x M20 (1/2” NPT for USA) cable entries for customer use. Alternative cable

entries are available from Crowcon.

The amplifier plugs into the terminal board, and is held in place by two

captive screws. The amplifier provides power to the sensor, local display and

controls, and a 4-20 mA signal proportional to the gas concentration for  connection

to a control panel. To remove, turn screws anti-clockwise and use them to pull

amplifier out of the enclosure.

All electrical connections are made via the terminal board mounted in the

base of the junction box (see Diagram 2). Optional alarm relays (AL1 & AL2) and one

fault relay (FAULT) are mounted on the terminal board which may be used to drive

local warning devices or connect TXgard-Plus to a control panel.

TXgard

-Plus

Flameproof
Toxic and Oxygen
Gas Detector

with Non-intrusive One-man Calibration

1. INTRODUCTION

Instructions

Diagram 1

: TXgard Plus general arrangement

TAMPER PROOF
GRUB SCREW
(1.5mm ALLEN KEY)

STEADY ON
INDICATES
ZERO/ CAL
MODE
ACTIVATED

EXTERNAL
EARTH POINT

"UP"

M20 (

1

/

2

" NPT)

CABLE ENTRY

UNITS

M20 (

1

/

2

" NPT)

CABLE ENTRY

115 (4

1

/

2

")

HEIGHT =  115 (4

1

/

2

")

All dimensions in mm unless otherwise stated

83 (3

1

/

4

")

 200 (8")

 135 (5 

5

/

16

")

LOCAL
DISPLAY

FLASHING
INDICATES
4-20mA/RELAYS
INHIBITED

ALARM 1 & 2
ADJUSTMENT
POTS

4 OFF
FIXING HOLES
O 6mm (

1

/

4

")

STATUS
LED

"DOWN"

ppm

TXgard

-Plus

Relay version only

1.3 Status Indication

TXgard-Plus includes a local display and status LED, visible through

the junction box window, see Diagram 1. The display shows the gas

concentration and current mode of operation ie. NORMAL, ZERO or CAL.

The LED shows the current alarm state of the detector. This is summarised in

Table 1.

Operational LED

Relay 

Comment*

state

indication

states*

Normal

Steady green

AL1 - Off

Gas level < AL1

operation

AL2 - Off

Current output = 4–20 mA

FAULT - On

Normal

Steady red

AL1 - On

AL1 < gas level < AL2

operation

AL2 - Off

Current output = 4–20 mA

(alarm 1)

FAULT - On

Normal 

Flashing red

AL1 - On

Gas level > AL2

operation

AL2 - On

Current output = 4–20 mA

(alarm 2)

FAULT - On

Over-range

Flashing red

AL1 - On

Gas level > full scale

AL2 - On

Display backlight flashes

FAULT - On

Current output = 24 mA

Zero/calibration 

Flashing green

Configuration

Latched until reset by ‘MENU’

mode

dependent

Current output = 2 mA

(see section 2)

(4 mA option)

Detector

Steady amber

AL1 - Off

Current output = 0 mA

fault

AL2 - Off

FAULT - Off

*See section 2 for AL1 and AL2 standard settings

Table 1: LED status indicator summary

.