1.1 Product overview

Flamgard Plus is a flameproof flammable gas detector

suitable for use in zone 1 or 2 hazardous areas. It is designed to detect

flammable gas, present in ambient air, at concentrations not

exceeding the Lower Explosive Limit (LEL) of the target gas for which

it is calibrated. A local display and magnetically operated switches

allow non-intrusive one-man calibration without a hot work permit.

Powered by 24 V dc (nominally) Flamgard-Plus provides a 4-20 mA

signal (sink or source) proportional to the gas concentration and can

also be fitted with optional alarm and fault relays. For a list of

flammable gases that can be detected, please contact Crowcon.

1.2 Product description

Flamgard Plus comprises four parts; 96HD sensor housing, junction box, amplifier and

terminal board. Diagram 1 details Flamgard Plus. The overall assembly is certified EEx d

IIC T6 in Europe and Class 1 , Zones 1&2  AEx d IIC T6 in the USA.

The 96HD sensor housing is a modular stainless steel assembly that

dismantles to allow plug-in pellistor sensors to be replaced easily (see Diagram 4). The

assembly screws into an M20 entry on the junction box.

The junction box is manufactured from marine grade alloy and is supplied with

2 x M20 (1/2” NPT for USA) cable entries for customer use. Alternative cable entries are

available from Crowcon.

The amplifier plugs into the terminal board, and is held in place by two captive

screws. The amplifier provides power to the pellistor sensor, local display and controls,

and a 4-20 mA signal proportional to the gas concentration for connection to a control

panel. To remove, turn screws anti-clockwise and use them to pull amplifier out of the

enclosure.

All electrical connections are made via the terminal board mounted in the base

of the junction box (see Diagram 2). Optional alarm relays (AL1 & AL2) and one fault relay

(FAULT) are mounted on the terminal board which may be used to drive local warning

devices or connect Flamgard-Plus to a control panel.

Flamgard

-Plus

Flameproof
Flammable Gas
Detector

with Non-intrusive One-man Calibration

1. INTRODUCTION

Instructions

Diagram 1

: Flamgard Plus general arrangement

TAMPER PROOF
GRUB SCREW
(1.5mm ALLEN KEY)

STEADY ON
INDICATES
ZERO/ CAL
MODE
ACTIVATED

EXTERNAL
EARTH POINT

"UP"

M20 (

1

/

2

" NPT)

CABLE ENTRY

UNITS

M20 (

1

/

2

" NPT)

CABLE ENTRY

SET BRIDGE VOLTS POT 'A'

SET BALANCE POT 'B'

115 (4

1

/

2

")

HEIGHT =  115 (4

1

/

2

")

All dimensions in mm unless otherwise stated

83 (3

1

/

4

")

TEST POINTS 'A'

 200 (8")

 135 (5 

5

/

16

")

TEST POINTS 'B'

LOCAL
DISPLAY

FLASHING
INDICATES
4-20mA/RELAYS
INHIBITED

ALARM 1 & 2
ADJUSTMENT
POTS

4 OFF
FIXING HOLES
O 6mm (

1

/

4

")

STATUS
LED

"DOWN"

LEL

Diagram 2

: Terminal and amplifier layouts

CONTACT
REVERSING
LINKS

TO
96HD
SENSOR

4-20mA

10-30V

0V

RL3

RL2

RL1

ALARM 2

12

4

SENSOR

56

3

OXYGEN

OUTPUT

SK

SR

OTHER

CONTROL
EQUIPMENT

ALARM2

RELAY
CONTACTS

INTERNAL TERMINAL LAYOUT

= ALARM  RELAY VERSION ONLY

REAR VIEW OF
AMPLIFIER

FAUL

T

ALARM1

ALARM 

4mA

OUTPUT OPTIONS

TEST

POINT

40-200 mV

INHIBIT

N

Y

17 4 2

GAS

RANGE

ALARM

ALARM 1

78

9

10

11

12

ISOLATE

0V

GND

NC  NO

NC  NO

NO  NC

GND
ISOLATE
LINK

ALARM1

FAULT

ALARM
SET POTS

USED FOR
OXYGEN TXGARD.
FOR FLAMGARD
LINK SET
TO OTHER

Reviews: