CLT- & CLX-1FAN4

 

Functional Summary 

The Crestron

 1-Feed, 4-Fan Terminal Block and Module 

(CLT-1FAN4 and CLX-1FAN4, respectively), are 
considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLT-1FAN4 prior to installation of the 
CLX-1FAN4, as described in this guide. The module is a 
capacitive–type fan speed control that connects to the 
terminal block and controls four ceiling fan motors. The 
maximum load is 2 amps for any controlled circuit. The 
module requires 120VAC 60 Hz, 1 phase input voltage. 
The terminal block and module can be mounted in any 
Crestron Automation Enclosure (CAEN-Series 
Enclosures). The terminal block is designed to terminate 
the circuit feed (HOT and NEUTRAL) and distribute the 
controlled circuit to the fan(s) (LOAD). An oversize heat 
sink dissipates heat efficiently. There are LEDs on the 
module to indicate communication to a Cresnet

 network, 

input power to the module, and output power to the 
ceiling fan motors. 

NOTE:  

This module is for speed control of a ceiling 

fan (paddle fan) only. The CLX-1FAN4 cannot 
change the fan direction. The module provides four 
speed settings as well as turning the fan off. 

NOTE:

  This module cannot control fans with 

remote-controlled integrated speed controls. 

Industry Compliance 

This product is Listed to applicable UL Standards and 
requirements by Underwriters Laboratories Inc. 

     

(E103692)

 

Installation 

The terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

CAUTION:  

This equipment is for indoor use only 

and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be 
32

°

F to 104

°

F (0

°

C to 40

°

C). The relative humidity 

must be 0% to 90% (non-condensing).  

Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-

wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
below when considering the location of terminal blocks 
and modules within an enclosure.  

NOTE:  

Modules and terminal blocks must be 

installed into the lowest available spaces and 
continue toward the top of the enclosure. 

Terminal Block & Module Locations (Single-wide Enclosure) 

CRESTRON

N OUT 4

N OUT 3

N OUT 2

N OUT 1

1 FEED

120VAC 60 Hz

8A MAX

2A MAX/CKT

CLX-1FAN4

GROUNDING

TERMINAL

BLOCK

FAN 4

FAN 3

FAN 1
FAN 2

4 FAN

LINE

TERMINAL

BLOCK

N IN

MODULE

 

Terminal Block & Module Locations (Double-wide Enclosure) 

Crestron Electronics, Inc.

 

Installation Guide – DOC. 6032A

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2002099)

 

Tel: 888.CRESTRON

 

10.05

 

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

TERMINAL BLOCK

(RIGHT)

CRESTRON

N OUT 4

GROUNDING TERMINAL BLOCKS

TERMINAL BLOCK

(LEFT)

N OUT 3

N OUT 2

N IN

N OUT 1

FAN 4

FAN 3

FAN 1
FAN 2

LINE

1 FEED

120VAC 60 Hz

8A MAX

2A MAX/CKT

4 FAN

CLX-1FAN4

MODULE

CRESTRON

CLX-1FAN4

120VAC 60 Hz

8A MAX

2A MAX/CKT

1 FEED

4 FAN

N OUT 4
N OUT 3
N OUT 2
N OUT 1

N IN

FAN 4
FAN 3
FAN 2
FAN 1

LINE

 

Summary of Contents for CLT-1FAN4

Page 1: ...th all national and local codes CAUTION This equipment is for indoor use only and needs to be air cooled Mount in a well ventilated area The ambient temperature must be 32 F to 104 F 0 C to 40 C The relative humidity must be 0 to 90 non condensing Terminal blocks are installed along the left side of single wide enclosures and along the outside edges left and right sides of double wide enclosures M...

Page 2: ...on this page NOTE Both left and right wiring labels are provided The left side labels are common for both single and double wide enclosures The right side labels are only used in double wide enclosures since the modules and terminal blocks along the right side must be inverted when mounting Wiring Diagram of the Terminal Block to the Feed and Load s Right Side Double wide Enclosures NEUTRAL FROM 1...

Page 3: ...NOT MADE 4 Turn on the circuit breaker and verify that the green PWR LED on the module lights and that the breaker does not trip NOTE Each fan that is to be controlled must be set to full speed Refer to the fan s instruction manual for instructions on setting the fan to full speed NOTE If a light is included with the fan it must be wired to a separate lighting control module e g CLX 1DIM4 The CLX ...

Page 4: ...erials and workmanship under normal use for a period of three 3 years from the date of purchase from CRESTRON with the following exceptions disk drives and any other moving or rotating mechanical parts pan tilt heads and power supplies are covered for a period of one 1 year touchscreen display and overlay components are covered for 90 days batteries and incandescent lamps are not covered This warr...