2556313—H  | 31 OCT 2018 

 

                                   Introduction |

 1

 

On / Off Digital Wall & Duct Humidistat Installation Instructions 

 

This document covers the operation and installation instructions for the following Condair Duct Humidistat: 

Part #:    

Description: 

2520273* 

  On/Off Digital Duct Humidistat Pkg. 

 

Note: Part #2520273 is comprised of two parts: 

2520265 

Humidistat w/o sensor 

1509857 

Duct Sensor

 

 

2520273 – On/Off Digital Duct Humidistat Installation 

Note: The duct sensor (Part # 2520265) must be wired to the humidistat w/o sensor (Part # 1509857). 

Part # 2520265 – Duct Humidistat Package Installation 

Location 

1.

 

The duct sensor should be installed directly on the duct in an area where the air is well mixed with uniform flow. 

2.

 

The supply air sensor should be mounted downstream of the steam distributor at a distance 1.5 times the absorption distance (typically 

10-12 feet or 3-3.7m). 

3.

 

If a return air humidity sensor is used it should be mounted close to the air inlet but downstream from a return fan if one is present. 

Installation 

1.

 

Open the housing by removing the 4 screws securing the housing together. 

2.

 

Push the probe through the center hole and tighten the 2 mounting screws. 

3.

 

Drill a 1/2” (13mm) hole in the duct and insert the probe into the air stream. 

4.

 

Secure the sensor to the duct using 2 sheet-metal screws. 

5.

 

Connect the signal wires to the sensor terminal strip. Table 1 outlines the terminal layout of the digital humidistat. 

6.

 

Connect the plug from the temperature probe to the PCB board into the plug marked ‘PROBE’. 

7.

 

Close the cover and secure using the 4 Screws removed in step 1. 

 

Table 1:  Humidistat Terminal Layout 

 

Controller w/o Sensor - (Part # 2520265) 

Ground 

24 VAC 

Digital Out (Common) 

Digital Out 

Outdoor Temperature Input 

Duct Sensor Input 

 

Part # 1509857 – Duct Sensor Installation 

Location 

1.

 

The duct sensor should be installed directly on the duct in an area where the air is well mixed with uniform flow. 

2.

 

The supply air sensor should be mounted downstream of the steam distributor at a distance 1.5 times the absorption distance (typically 

10-12 ft or 3-3.7 m). 

3.

 

If a return air humidity sensor is used it should be mounted close to the air inlet but downstream from a return fan if one is present. 

Installation 

1.

 

Open the housing by removing the 4 screws securing the housing together. 

2.

 

Push the probe through the center hole and tighten the 2 mounting screws. 

3.

 

Drill a 1/2” (13mm) hole in the duct and insert the probe into the air stream. 

4.

 

Secure the sensor to the duct using 2 sheet-metal screws. 

5.

 

Connect the signal wires to the sensor terminal strip. Table 1 outlines the terminal layout of the digital humidistat. 

6.

 

Connect the plug from the temperature probe to the PCB board into the plug marked ‘PROBE’. 

7.

 

Close the cover and secure using the 4 Screws removed in step 1. 

 

Table 2:  Sensor Terminal Connections 

 

Duct Sensor - (Part # 1509857) 

GND 

24 VAC 

Humidity Output 

 
 