COMPUTHERM 

WPR-100GE

Pump controller with immersion sleeve

 

 

 Operating Instructions

Summary of Contents for WPR-100GE

Page 1: ...COMPUTHERM WPR 100GE Pump controller with immersion sleeve Operating Instructions ...

Page 2: ... V or other electrical appliance within the load capacity limits can be easily controlled The pump controller is responsible for turning the pump on and off at the set and measured temper ature so it only operates when it is necessary Intermittent operation saves significant energy and increases pump life and reduces operating costs Its digital display allows easier and more accurate temperature m...

Page 3: ... switches on off accor ding to set temperature and the switching sensitivity 1 LOCATION OF THE DEVICE It is recommended to install the pump controller in an immersion sleeve installed in the heating cooling pipe or boiler on which the control is based so that it is as close as possible to a maximum of 1 5 m from the pump to be controlled and the 230 V supply Do not use a wet chemically aggressive ...

Page 4: ...operly connected and that that there is no risk of electric shock or short circuit Connect your device as follows Before installing disconnect the immersion sleeve from the back of the pump control after loosening the screw there After installing the immersion sleeve place the pump controller s heat sensor in the immersion sleeve and reattach the device again to the immersion sleeve using the scre...

Page 5: ...zivattyú szivattyúvezérlő Warning Always take into account the loadability of the controller relay when connecting 10 A 3 Inductive load and follow the instructions of the manufacturer of the pump which you would like to control Pump controller Pump ...

Page 6: ...is turned on if the measured temperature is higher than the set temperature The switching sensitivity is taken into account when switching F2 Control of a cooling system s circulating pump the output is turned on if the measured temperature is lower than the set temperature The switching sensitivity is taken into account when switching F3 Manual mode regardless of the measured temperature the outp...

Page 7: ...tches the connected pump on off below above the set temperature The lower this value is the more constant the temperature of the circulating fluid will be The switching sensitivity can be set between 0 1 C and 15 0 C in 0 1 C steps Except some special cases we recommend setting 1 0 C factory default setting See Chapter 4 for more information on switching sensitivity To change the switching sensiti...

Page 8: ...n the function is on the output will turn on every 5 days for 15 seconds if the output has not been turned on in the last 5 days During this time will appear on the display instead of the measured temperature To activate deactivate the pump protection function first switch off the appliance by pressing the button once the display switches off then press and hold the button for 3 seconds POFF facto...

Page 9: ...he measured temperature rea ches 5 C again to protect the pump and the heating system During this time the display alternates between and the measured temperature When the frost protection function is activated it ope rates in all three modes F1 F2 and F3 To switch the frost protection function ON OFF first switch off the appliance by pressing the button once it switches OFF the display then press...

Page 10: ...witching sensitivity of 1 0 C the pump connected to it switches ON and at temperatures below 39 0 C the output switches OFF the pump connected to it switches OFF In F2 mode the output switches exactly the opposite way You can adjust the set temperature with the and buttons In F3 mode the output is permanently ON OFF according to the setting regardless of the measured temperature in F3 mode You can...

Page 11: ...emperature measurement accuracy 1 0 C Power supply 230 V AC 50 Hz Output voltage 230 V AC 50 Hz Loadability max 10 A 3 Inductive load Environmental protection IP40 Immersion sleeve connector size G 1 2 Ø8x60 mm Length of wires for electrical connection approx 1 5 m Max ambient temperature 80 C probe 100 C Storage temperature 10 C 80 C Operating humidity 5 to 90 without condensation ...

Page 12: ...the requirements of standards EMC 2014 30 EU LVD 2014 35 EU and RoHS 2011 65 EU Manufacturer QUANTRAX Kft H 6726 Szeged Fülemüle u 34 Telefon 36 62 424 133 Fax 36 62 424 672 E mail iroda quantrax hu Web www quantrax hu www computherm info Country of origin China ...