BSL10T3/BSL06T3

8/19/22

Li - ion

Self-Testing Emergency LED Driver

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

! IMPORTANT SAFEGUARDS !

WHEN USING ELECTRICAL EQUIPMENT, BASIC
SAFETY PRECAUTIONS SHOULD ALWAYS BE 
FOLLOWED, INCLUDING THE FOLLOWING:

1.  This product is for use with an emergency LED lighting load and supplies nominally 10.0 W/6.0 W 

(depending on model) of power, with a voltage of 15-54 VDC in emergency mode for a minimum of 90 

minutes, in compliance with NFPA 101 and NEC 700.12. 

2.  Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical 

Code and any local regulations.

3.  To reduce the risk of electric shock, disconnect both normal and emergency power supplies before 

servicing. Follow the instructions in the OPERATION section to disable the output of this LED driver.

4.  This emergency driver is suitable for both factory or field installation.

5.  This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum, 

+55ºC maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is 

not suitable for heated air outlets and wet or hazardous locations. Maximum allowable case temp is 

65ºC. See unit label for Tc measurement location.

6.  An unswitched AC power source is required (120-277 VAC, 50/60 Hz).

7.  Do not install near gas or electric heaters.

8.  Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field 

replaceable. Contact the manufacturer for information on service.

9.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe 

condition.

10.  Do not use this product for other than intended use.

11.  Servicing should be performed by qualified service personnel.

12.  Equipment should be mounted in locations and at heights where it will not be subjected to tampering 

by unauthorized personnel.

13.  For Canadian application the output terminals should be in compliance with the accessibility 

requirement of the Canadian Electric Code.

14.  This device complies with part 15 of the FCC Rules. Operation is subject to the following two 

conditions: (1) this device may not cause harmful interference, and (2) this device must accept any 

interference received, including interference that may cause undesired operation.

15.  This product must be grounded. See the wiring diagrams for details.

Installation Instructions

Summary of Contents for BSL10T3

Page 1: ...the ambient temperature is 0ºC minimum 55ºC maximum Product is also suitable for installation in sealed and gasketed fixtures Product is not suitable for heated air outlets and wet or hazardous locations Maximum allowable case temp is 65ºC See unit label for Tc measurement location 6 An unswitched AC power source is required 120 277 VAC 50 60 Hz 7 Do not install near gas or electric heaters 8 Do n...

Page 2: ...This is the current into the blue wire connector 4 Ensure there will be sufficient light output in the end application Estimate the egress lighting illumination levels by doing the following A Find the efficacy of the LED load This can be given by the luminaire manufacture This number will be given in lumens per watt lm w It is the installer s responsibility to validate the luminaire manufacturer ...

Page 3: ...abels STEP 4 WIRING THE EMERGENCY DRIVER Fixture or Test Monitor Plate 2 Wire Illuminated Test Switch Hex Nut Red Black When AC power fails the emergency driver automatically switches to emergency mode powering the LED load per the rating of the emergency driver for a minimum of 90 minutes When AC power is restored the emergency driver returns to charging mode ABConnect Applying AC power to the un...

Page 4: ...or is still present then recalibrate the commission value by deactivating the unit Apply AC mains to activate unit and it will recommission itself after one hour 3 Check for Open or Short circuit on the output connections Red 5x Flashes Temperature Product temperature is beyond its rated temperature range 1 Ensure unit is within the rated temperature range stated on the product label 2 Confirm by ...

Page 5: ...S NOTE Emergency driver case and green connector must be grounded EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY MAY BE USED WITH OTHER DRIVERS CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS NOTE 1 For short term testing of the emergency function the battery must be charged for at least one hour The emergency driver must be charged for at least 24 ho...