background image

Installation and Operating Instruction for 

B.E.G.

 - Occupancy detector PD2-M-DALI/DSI-1C-DE

LUXOMAT

®

PD2-M-DALI/DSI-1C/PD2-S

EN

  1. Product information 

• 

For group operation of up to 50 lights

• 

 Suitable for dimmable digital electronic ballasts and 

control moduls

• 

 One additional switching channel for controlling lights and 

HVAC (heating, ventilation, air conditioning) devices 

• 

DALI/DSI interface

• 

Constant light control

• 

Manual switching / dimming

• 

Full or semi-automatic mode

• 

 Set value brightness, follow-up time – LIGHT/HVAC and 

orientation light adjustable

• 

Sensor and power supply in one housing

• 

Infrared remote control

2. Operation

The presence detector controls the light automatically according 

to people present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient light  

and compares it with the brightness level on the detector. If the 

ambient light is sufficient, lighting will not be switched.  

If the ambient light level is below the brightness level, a move-

ment activates the lighting in the room.
The detector switches the light off, if there is enough natural light 

for 5 min. or if no movement is detected for one follow-up time.
The second channel can be interpreted as HVAC channel 

(heating, ventilation, air conditioning). This channel switches the 

connected load independent of the brightness. 

 3. Safety advice

!

   

Work on the 110-240V mains supply may only be 

carried out by qualified professionals or by instructed 

persons under the direction and supervision of quali-

fied skilled electrical personnel in accordance with 

electrotechnical regulations

!

  Disconnect supply before installing!

!

  This device is not suitable for disconnection.

!

   After having connected all cables, please mount the 

cap onto the detector.

4.  Mounting FC

A circular opening of diameter 68 mm must be drilled into the ceil-

ing. Having connected the cables in accor dance with regulations, 

the detector is inserted into the opening as shown in the drawing 

above and has to be fixed into position by means of the spring clips.

!

   In Master/Slave operation, the master device must always 

be installed at location with least daylight.

5.  

Position DIP switches, LEDs  

and potentiometers

PD2- 

False ceiling  

mounting

C

B

A

Light  

measurement

DALI_D

SI

HV

AC_

LI

GHT

 

VA_HA

1

2

3

6. Self test cycle/Startup behavior

The product enters an initial 60-second self-test cycle, when the  

supply is first connected. During this time, the device does not 

respond to movement and stays on. 

The initialization mode can be changed by using the remote 

control.

7. Putting into operation / Settings

Twilight-switch for constant light control

The set value brightness can be adjusted at between 10 and 

2000 Lux. Using the potentiometer, the set value brightness 

can be adjusted as desired. 
Symbol

 

: Night-time operation 

Symbol

 

:  Day/night time operation

Follow-up time for light control

The time can be set infinitely variably  between  

1 and 30 minutes.
Symbol 

TEST

: Test mode  

Every movement switches on the light independent of 

brightness for a period of 1 second, switching it off for a 

period of 2  seconds.

Orientation light

The follow-up time can be set infinitely variably at between 

5 and 60 minutes. Manually switching ON/OFF the 

orientation light.  

„ON“ for permanent orientation light 

„OFF“ for deactiviation of orientation light

Follow-up time for device control

The follow-up time can be adjusted between 5 min. and

120 min. The delay is active from a set time of >15 minutes.

This delay is about 5 min. If no other movements are detec-

ted during this time, the delay starts again.

Impulse function

The impulse function can be used to control external HVAC 

systems. All 9 s will be set a 2.5 sec.

Alarm impulse

In order to initiate an alarm impulse, there have to be three 

detected movements within a period of 9 sec.

This function can be used to display a presence in the room 

on external visualizations. All 9 sec. will be set an impulse 

of 2.5 sec.

The device does not fulfil the requirements of DIN EN50131-

2-2 and therefore cannot be used in professional intrusion 

detection systems.

Pulse spacing PD-Slave

2 or 9 seconds can be set for the pause between 2 pulses 

sent to the master. The setting can be made with activated  

( ) or deactivated ( ) LED indicator.
For devices with a separate slave input, 2 sec.  

can be set.

DIP switch functions

DIP 1

Fully automatic mode 

(VA) 

Semi-automatic mode 

(HA) 

DIP 2

HVAC function

Light control*

DIP 3

Operation mode DALI

Operation mode DSI

 

* If you select „LIGHT“, the switching relay R2 operates synchro-

nously to the DALI light channel. The potentiometer R2 has no 

function in this setting.

Potentiometer  A

 Lux Channel 1

Potentiometer  B

 Time Channel 1

Potentiometer  C

 Orientation light

Potentiometer D

 HVAC Channel 2

LED I

   green

LED II  

red 

LED  III  

white

8.  Wiring diagram

Standard mode with Master/Slave

L

N

L

N

N

N

S

Master

Slave

R

L

L

R

-

+

L‘

T1

DA1

M1

T2

DA

DA

E1     DALI/DSI

9. Manual switching and dimming

By pressing the push button, the phase can be given to the S

terminal.
To turn on or off, press the push button briefly. The light will remain 

on or off, as people are detected plus the follow-up time.
With a long key press the light will be dimmed manually. When

you release the button, the current brightness value is retained.

Upon renewed dimming, the dimming direction is reversed.
Taking the phase to the R terminal by using a button, the HVAC 

channel can be switched with a short key press.

10. Range

10 m

6 m

4 m

10 m

360°

2.50 m

2

1

1

2

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

Walking across
Walking towards
Seated

!

   

Connected slaves must have the same phase  

as the Master.

R1

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

R2

A

120

60

5

15

30

40

50

20%

60

5

10

50 30

O

FF

ON

9s

2s

LED ON

LED OFF

R1

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

R2

A

120

60

5

15

30

40

50

20%

60

5

10

50 30

O

FF

ON

R1

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

R2

A

120

60

5

15

30

40

50

20%

60

5

10

50 30

O

FF

ON

!

R1

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

R2

A

120

60

5

15

30

40

50

20%

60

5

10

50 30

O

FF

ON

68 mm

A