ON/OFF regulators, 4-20 mA input, 2 relays and acoustic alarm, for moisture, pressure, level, etc.

Devices designed to display, process control and regulation, with 4-20 mA input type for

sensors and converters. Both outputs with SPDT relays can be configured for two indepen-

dent stages, 2 related stages, neutral zone, or also as 1 stage + alarm.

Index

1 - Versions and references

6 - Menus, parameters and messages

2 - Technical data

7 - Parameter transfer

3 - Instalación

8 - Relay operation and control

4 - Front panel functions

9 - Maintenance

5 - Adjustment and configuration

10 - Warnings

1- VERSIONS AND REFERENCES

MODEL

RELAYS

POWER SUPPLY, 50/60 Hz

AKO-14532

8 A, 250 V, cos 

ϕ

=1, SPDT

230 V~ ±10%

AKO-14534

8 A, 250 V, cos 

ϕ

=1, SPDT

120 V~ +8% -12%

2- TECHNICAL DATA

Configuration range: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . from -999 to 999
Resolution, Set Point and differential:. . . . . (0,1 from -99,9 to 99,9)  (1 from -999 to 999)
Accuracy: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 %
Maximum input power: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 VA
Working ambient temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 ºC to 50 ºC
Storage ambient temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 ºC to 70 ºC
Control device classification: Independent mounting, with characteristic of automatic ope-
ration Type 1.B action, to be used in a clean situation, logical medium (software) class A
and continuous operation.
Double insulation between the power supply, secondary circuit and relay output.
Allocated pulse voltage: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 800 V
Pressure ball test temperature:

Accessible parts: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC
Parts that position active elements: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 ºC

Voltage and current declared by the EMC tests:. . . . . . . . . . . . . . . . . . . . . 207 V,    16 mA
Current of radio jamming suppression test: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270mA

3- INSTALLATION

The controller must be installed in a place protected from vibrations, water and corrosive

gases, and where ambient temperature does not surpass the value specified in the techni-

cal data.
In order for the controllers to have IP65 protection, the gasket must be properly installed

between the apparatus and the perimeter of the panel cut-out where it is to be fitted.

3.1 Fastening units for panel mounting:

GB

UP key

Press once to cancel the alarms, but they
remain displayed (optional by parameter

AtA

). When pressed for at least 5 seconds,

the 

SP1

Set Point of Relay 

R1

is displayed.

In programming, it increases the displayed
value.

DOWN key

Press once to cancel the alarms, but they
remain displayed (optional by parameter

5- ADJUSTMENT AND CONFIGURATION

It must only be programmed or modified by personnel who are fully conversant with the
equipment operation and possibilities.

5.1 Set Point configuration.

The factory SET POINT default value is 0.
- Press 

key for at least 5 seconds to DISPLAY SET POINT in Relay R1 or 

key for Relay

R2. It displays the CURRENT SET POINT value and LED “

PR

” starts flashing.

- Press 

or 

keys to CHANGE SET POINT to the required value.

LED R1: Relay 1 indicator enabled

LED AL: Alarm indicator enabled

LED R2: Relay 2 indicator enabled

LED PR: Flashing, programming phase

5.2 Parameter configuration

Level 1

Menus

- Press 

keys simultaneously for at least 10 seconds. The LED “

PR

” will start flas-

hing, LEVEL 1 MENUS programming has been accessed and the first menu “

Po1

” is dis-

played.

- Press 

key to access the next menu and 

key to return to the previous one.

- Pressing 

keys simultaneously in the last menu EP, the controller returns to the

VALUE DISPLAY status and LED “

PR

” will stop flashing.

When 

PA

is displayed, the PASSWORD programmed in the 

PAr

menu 

PAS

parameter must

be entered to access LEVEL 1 MENUS programming.
- Press 

keys simultaneously. 0 will be displayed to ENTER PASSWORD.

- Press 

or 

keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.

- Press 

keys simultaneously to ACCEPT PASSWORD. The first menu “

Po1

” will be

displayed.

Level 2

Parameters

- In the desired menu of LEVEL 1 MENUS, press keys 

simultaneously. LEVEL 2

PARAMETERS programming is accessed. The first parameter of the selected menu is dis-
played on the screen.

- Press 

key to access the next parameter and 

key to return to the previous one.

- Pressing 

keys simultaneously in the last parameter EP, the controller returns to

LEVEL 1 MENUS.

Level 3

Values

- To DISPLAY CURRENT VALUE of any parameter, select the required one and press 

keys simultaneously. Once it is displayed, you can CHANGE VALUE pressing 

or 

key.

- Press 

keys simultaneously to ACCEPT THE NEW VALUE. The programming returns

to LEVEL 2 PARAMETERS.

To fix the unit, place the faste-

ners 

1

over the sliders 

2

as shown

in the figure. Move the fasteners

in the direction of the arrow. By

pressing tab 

3

fasteners may be

moved in the opposite direction of

the arrow.

3.2 Connection:

See diagram on the unit rating plate.
The probe or 4-20 mA output converter and its leads should 

NEVER

be installed in ducting

together with power, control or power supply wiring.
The power supply circuit must be connected with a minimum 2 A, 230 V switch located

close to the unit. Power supply cables must be H05VV-F 2x0,75 mm

2

or H05V-K 1x0,75 mm

2

.

Section of connecting wires for relays contacts must range from 1 mm

2

to 2.5 mm

2

.

NOTE: If no key is pressed for 25 seconds in either of the previous steps, the controller will
automatically return to the VALUE DISPLAY status without modifying any of the parameter
values.

PANEL CUT-OUT

3

2

1

max. 18 mm

61,5

44

28,5

70,5

4- FRONT PANEL FUNCTIONS

AtA

). When pressed for at least 5 seconds, the 

SP2

Set Point of Relay 

R2

is displayed. In

programming, it decreases the displayed value.

5 Sec.

VALUE

DISPLAY

DISPLA

Y SP1

Relay 

R1

 SET POINT

CHANGE SET POINT

ACCEPT THE NEW

CURRENT

SET POINT

NEW

SET POINT

SIMULTANEOUSLY

5 Sec.

DISPLA

Y SP2

Relay 

R2

 SET POINT

- Press + keys

simultaneously to
ACCEPT THE NEW
SET POINT. The dis-
play returns to the
the VALUE DISPLAY
status and LED

PR

” stops flas-

hing.

10 Sec.

CHANGE NUMBER

DISPLA

Y

PARAMETER

PASSWORD

REQUEST

ENTER

PASSWORD

DISPLAY

PASSWORD

CURRENT

VALUE

NEW

VALUE

IF PAS=0

SIMULTANEOUSLY

ACCEPT THE NEW

VALUE

 DISPLAY

LEVEL 1

MENUS

LEVEL 3

VALUES

EXIT

PROGRAMMING

ACCEPT

PASSWORD

PASSWORD

IF PROGRAMMED

CHANGE V

ALUE

SIMULTANEOUSLY

SIMULTANEOUSLY

SIMULTANEOUSLY

SIMULTANEOUSLY

LEVEL 2

PARAMETERS

SIMULTANEOUSLY

DISPLA

Y

VALUE

EXIT TO

LEVEL 1

Reviews: