Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

Version: 6.0

I0000691

RD2432D SERIES

Installation & Operation Instructions

Phone:

 1-888-967-5224

Website:

 workaci.com

CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE 
MAY BE AFFECTED.

 

GENERAL INFORMATION

The RD2432D is an output module that works with the MOD9200 series network transceivers to output four (4) 
analog 0-5 VDC/0-10 VDC and four (4) digital signals (dry contact) for wireless control of modulating actuators or 
wireless status indications. The network transceiver receives the wireless signal from the sensor/input concentrator 
and that data is sent to the BAS via RS-485.  If the BAS determines an action is needed, it then sends the command to 
the transceiver and the transceiver sends that command wirelessly to the RD2432D, which then outputs either an 
analog or digital signal. 

Transmission distance in a typical building is 200-300 feet horizontal depending on the layout and construction of 
the building, and one floor above and one floor below the transceiver. Sensor distance and reliability can be 
increased with the addition of a RR2552B(s) repeater.

PRECAUTIONS
SENSORS, REPEATERS AND RECEIVERS SHOULD 
NOT BE INSTALLED IN THE FOLLOWING AREAS:
• INSIDE METAL ENCLOSURE / PANEL 
• INSIDE OR IMMEDIATELY NEXT TO ELEVATOR 
SHAFT / ELEVATOR BANKS
• IN FRONT OF OR IMMEDIATELY NEXT TO LARGE 
TREES OR LARGE BODY OF WATER
TRANSMISSION DISTANCE AND PERFORMANCE 
WILL BE DRASTICALLY REDUCED.

 

MOUNTING INSTRUCTIONS

Mount the RD2432D output module as close to the 
equipment or controller as possible using four #8 screws 
(mounting dimensions see Figure 1). The maximum 
wiring distance for the analog outputs is 100 ft. 

WIRING INSTRUCTIONS

WIRING PRECAUTIONS
• Do NOT run Analog/Digital Output wires in any 
conduit with line voltage (24/120/230 VAC).
• Remove power before wiring. NEVER connect 
or disconnect wiring with power applied.
• The RD2432D is full wave rectified.
• It is recommended that you use an isolated 
UL-listed Class 2 transformer when powering the 
unit with 24 VAC. Failure to wire the devices with 

the correct polarity when sharing transformers may result in damage to any device powered by the 
shared transformer.

Observe polarity when connecting  analog outputs to the controller inputs.
  

WIRING

Connect 24VAC 60Hz to the TB1 terminals using 16-26 twisted pair wire. Check all connections before 
applying power to the unit.

Select 0-10VDC or 0-5VDC output by moving J4 jumper.

Using the RD2432D configuration information, connect the analog and digital outputs to the appropriate 
control input terminals on the controller using 20AWG wire. The controller input connecting to the 
RD2432D should have a minimum analog input resistance of 20K Ohms. 

While the RD2432D is attempting to connect to the receiver, the Data LED will blink rapidly. Once a 
connection has been established, the Data-Link LED will blink once to indicate the data transmission has 
been received and transmitted successfully. The Active LED will blink once every second to indicate that 
the repeater is functional.

FIGURE 2: 

WIRELESS MULTILEVEL 

DIAGRAM

SENSOR

SENSOR

SENSOR

SENSOR

RECEIVER/REPEATER

Summary of Contents for RD2432D Series

Page 1: ... depending on the layout and construction of the building and one floor above and one floor below the transceiver Sensor distance and reliability can be increased with the addition of a RR2552B s repeater PRECAUTIONS SENSORS REPEATERS AND RECEIVERS SHOULD NOT BE INSTALLED IN THE FOLLOWING AREAS INSIDE METAL ENCLOSURE PANEL INSIDE OR IMMEDIATELY NEXT TO ELEVATOR SHAFT ELEVATOR BANKS IN FRONT OF OR ...

Page 2: ...evice powered by the shared transformer Observe polarity when connecting analog outputs to the controller inputs WIRING Connect 24VAC 60Hz to the TB1 terminals using 16 26 twisted pair wire Check all connections before applying power to the unit Select 0 10VDC or 0 5VDC output by moving J4 jumper Using the RD2432D configuration information connect the analog and digital outputs to the appropriate ...

Page 3: ...ion Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 3 Version 6 0 I0000691 SIDE VIEW TOP VIEW TOP 5 74 145 8mm 8 74 222mm 8 24 209 3mm 4 56 115 8mm Ø0 18 Mounting Holes 8 74 222mm 2 96 75 2mm ...

Page 4: ...y depending on building type and constructions and typically one floor above and below the transceiver vertically Four 4 SPDT Pilot Duty Relays Dry Contact 1 0A 30 VDC 104ºF 40ºC 0 5A 125 VAC 104ºF 40ºC Resistive Mechanical 5 000 000 operations minimum 36K operations hr Electrical 100 000 operations minimum under rated load 1 8K operations hr 1 SPDT Dry contact relay 1 0A 30 VDC 104ºF 40ºC 0 5A 12...

Reviews: