background image

GENERAL

These luminaires are used in places where
emergency luminaires are needed.
Each luminaire must be permanently connected
to mains power supply In normal operation the
led strip lights and the battery is charging. In
case of a mains power supply failure the
luminaire will light the led strip automatically in
emergency mode.

When the

mains

power

supply is restored the device turns to normal
operation.

1. Operations for installation, maintainance or
testing must be done by authorized personel
only

The device must be connected to the mains

power supply thru a fuse dependent by the total
amount of the line’s  power load

It is sugested to check every month the

indication LED for battery charging, and by
pushing the TEST button (see the paragraph 8
on page 2), to check the emergency cirquit. The
lamp should light as long as the TEST button is
pressed

It is sugested to check every 6 months the

minimum autononous duration by disconnecting
the mains power supply Count the time that the
led strip lights and in case of less time than the
minimum autonomous duration the battery must
be replaced. If the measured time is

.

.

2.

.

3.

4.

.

ΑΤΤΕΝΤΙΟΝ!!!

. In the opposite condition contact the

installer.

considerably less than the minimum autonomous
duration

In case of battery or

led strip replacement, these must be replaced by
parts of the same type

To install the luminaire follow the installation
instructions in page 2.

LED= Light Emitting Diode

t i

in battery recycling points. Do not

incinerate.

NOTE:

LABELING EXPLANATION:
X: Self contained
0: Non Maintained
A: Including test device
*90: 90min duration
180: 180min duration

INSTALLATION

contact the installer.

In case of inactive use for a period greater

than 2 months, disconnect the battery by pulling
out the battery’s connector.

.

5.

6.

I

s not allowed to discard batteries in to

common trash bins, they must be discarded
only

220-240V AC/50-60Hz

Bayblent F 3010 transparent  polycarbonate

TECHNICAL CHARACTERISTICS

OPERATION TEMPERATURE RANGE

R

,

RELATIVE HUMIDITY

EXTERNAL DIMENSIONS

CONSTRUCTION MATERIALS

TYPICAL WEIGHT

GUARANTEE

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERIES Ni-Cd

(

)

CHARGING TIME

INDICATIONS CONTROLS

-

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

ILLUMINATION SOURCE

180min

24h

Charge indication LED  TEST button

,

From overcharge and full discharge

IP 65

370lm

6 power LED’s

EN 60598-1, EN 60598-2-22

0 to 40 C

o

Up to 95%

3 years

year for the battery

(1

)

355 x 145 x 73 mm

4.8V/1.5Ah

4.8V/3Ah

4.8V/4Ah(Ni-MH)

5 VA

6 VA

4 VA

1020gr.

Pamal WP

Reviews: